Generator Set Control Panel for Switchgear Conversion Caterpillar


CID 0271 FMI 06 Alarm (Action) Current Above Normal - Test

Usage:

3412C 4BZ
This diagnostic code is recorded when the Main Display Module reads the current in the circuit of the Action Alarm as above normal or the current is shorted to ground. As a result of this fault, the Action Alarm does not sound when the Action Alarm should sound.

  1. Check The Alarm.

    1. Disconnect the engine harness from the Action Alarm.

    1. Measure the resistance across the terminals of the Action Alarm.

      Expected Result: The resistance should measure 200 ± 100 Ohms.

      Results:

      • OK: The resistance of the Action Alarm is correct. If the Action Alarm does not sound, proceed to Step 2.

      • Not OK: The resistance of the Action Alarm is incorrect. Replace the Action Alarm. Proceed to Step 2.

  1. Check The Harness.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Disconnect the engine harness from the Action Alarm.

    1. Disconnect the engine harness from the Main Display Module.

    1. At the engine harness connector for the Main Display Module, measure the resistance from the connector Contact 4 to connector Contact 2 (ground).

      Expected Result: The resistance should be greater than 5000 ohms.

      Results:

      • OK: The resistance is correct. Proceed to Step 3.

      • Not OK: The resistance is less than 5000 ohms. The engine has a problem. Repair the engine harness or replace the engine harness.

  1. Check The Main Display Module.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Use the correct service tools to remove Contact 4 from the engine harness connector for the Main Display Module.

    1. Reconnect the engine harness connector to the Main Display Module.

    1. Turn the "ECS" switch to the COOLDOWN/STOP position.

      Expected Result: FMI 06 should not be active.

      Results:

      • OK: FMI 06 is NOT active. The Main Display Module is NOT causing the problem. The problem is intermittent. The probable cause is a poor electrical connection at the harness connectors or a damaged harness. Check the harness for damage and clean the harness connectors as cleaning is required. STOP.

      • Not OK: FMI 06 is still active. The Main Display Module has a problem. Replace the Main Display Module. For more information, see Testing And Adjusting, "Module - Replace".

Caterpillar Information System:

G3408 and G3412 Engines Governor Control
G3408 and G3412 Engines Governor
3116 and 3126 Marine Engines Turbocharger - Inspect
G3408 and G3412 Engines Magneto
G3408 and G3412 Engines Gas Pressure Regulator
G3408 and G3412 Engines Flywheel
3606 and 3608 Engines Restriction of Air Inlet and Exhaust
Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 05 Alarm (Action) Current Below Normal - Test
3116 and 3126 Marine Engines Heat Exchanger - Inspect
Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 03 Alarm (Action) Voltage Above Normal - Test
3408E and 3412E Engines for Caterpillar Built Machines Engine Oil Pan - Remove and Install
G3408 and G3412 Engines Cylinder Liner
G3408 and G3412 Engines Governor Linkage
Generator Set Control Panel for Switchgear Conversion CID 0263 FMI 04 Sensor Power Supply Voltage Below Normal - Test
Generator Set Control Panel for Switchgear Conversion Charging System - Test
P16, P20, P25, P28, P40 and P60 Pulverizers Gerotor Motor - Install
Generator Set Control Panel for Switchgear Conversion Clear/Mode Switch - Troubleshoot
P16, P20, P25, P28, P40 and P60 Pulverizers Gerotor Motor - Disassemble
3606 and 3608 Engines General Information (Lubrication System)
3408E and 3412E Engines for Caterpillar Built Machines Fuel Transfer Pump
3054 and 3056 Industrial and Generator Set Engines Engine Oil Cooler - Remove
Generator Set Control Panel for Switchgear Conversion Component Location
SR4 HV and SR4B HV Generators Before Starting Engine
3054 Engine for Caterpillar Built Machines Housing (Front) - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.