Generator Set Control Panel for Switchgear Conversion Caterpillar


CID 0271 FMI 05 Alarm (Action) Current Below Normal - Test

Usage:

3412C 4BZ



Illustration 1g00565138

This diagnostic code is recorded when the Main Display Module of the Caterpillar Monitoring System reads the current of the circuit for the Action Alarm below normal. Also, this diagnostic code is recorded when the Main Display Module reads an open circuit with the Action Alarm. As a result of this action, the Action Alarm does not sound when the Action Alarm should sound.

  1. Check The Alarm.

    1. Disconnect the engine harness from the Action Alarm.

    1. Place a jumper wire across the two leads of the Action Alarm of the engine harness.

      Expected Results: CID 0271 FMI 05 should remain active.

      Results:

      • OK: The FMI 05 diagnostic code is still active. The Action Alarm is not causing the problem. Measure the resistance across the terminals of the Action Alarm. The resistance should be 200 ± 100 ohms. If the resistance of the Action Alarm is good, but the alarm does not sound, proceed to Step 2.

      • Not OK: If the FMI 05 diagnostic code is not active, the Action Alarm has a problem. Measure the resistance across the terminals of the Action Alarm. The resistance should be 200 ± 100 ohms. If the resistance of the Action Alarm is good, but the alarm does not sound, proceed to Step 2. If the resistance of the Action Alarm is not good, then replace the Action Alarm. Proceed to Step 2.

  1. Check The Harness.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Remove the jumper wire from the harness leads of the Action Alarm.

    1. Reconnect the harness leads to the Action Alarm.

    1. Disconnect the engine harness from the Action Alarm.

    1. At the engine harness connector for the Main Display Module, measure the resistance from Contact 4 to Contact 2 (ground).

      Expected Results: The resistance should be less than 300 ohms.

      Results:

      • OK: The resistance is less than 300 ohms. The harness resistance is correct. Proceed to Step 4.

      • Not OK: The resistance is greater than 300 ohms. The harness circuit is open. Proceed to Step 3.

  1. Check The Harness.

    1. Disconnect the engine harness from the Action Alarm.

    1. Check for an open circuit. The open circuit may be located between the Main Display Module of the Caterpillar Monitoring System (Contact 4) and the Action Alarm output (Terminal 1).

    1. Check for an open circuit between the lead of the Action Alarm (Terminal 2) and ground.

    1. If an open circuit is found, repair the harness or replace the harness.

  1. Check the Main Display Module.

    1. Turn the "ECS" switch to the OFF/RESET position.

    1. Reconnect the engine harness connector to the Main Display Module.

    1. Turn the "ECS" switch to the COOLDOWN/STOP position.

      Expected Result: The FMI 05 diagnostic code should not be active.

      Results:

      • OK: The FMI 05 diagnostic code is not active. The Main Display Module of the Caterpillar Monitoring System is not the cause of the problem. The problem is intermittent. The probable cause is a poor electrical connection at the harness connectors or a damaged harness. Check the harness for damage and clean the connectors when cleaning is required.

      • Not OK: The FMI 05 diagnostic code is still active. The Main Display Module has a problem. Replace the Main Display Module. For more information, see Testing And Adjusting, "Module - Replace".

Caterpillar Information System:

3116 and 3126 Marine Engines Heat Exchanger - Inspect
Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 03 Alarm (Action) Voltage Above Normal - Test
3408E and 3412E Engines for Caterpillar Built Machines Engine Oil Pan - Remove and Install
G3408 and G3412 Engines Cylinder Liner
3408E and 3412E Engines for Caterpillar Built Machines Engine Oil Cooler Bypass Valve - Remove and Install
Generator Set Control Panel for Switchgear Conversion CID 0263 FMI 03 Sensor Power Supply Voltage Above Normal - Test
Generator Set Control Panel for Switchgear Conversion Alert Indicator - Troubleshoot
3054 Engine for Caterpillar Built Machines Crankshaft Gear - Remove and Install
3054 Engine for Caterpillar Built Machines Piston Cooling Jets - Remove and Install
Generator Set Control Panel for Switchgear Conversion Alarm Silence Switch - Troubleshoot
Generator Set Control Panel for Switchgear Conversion Alert Indicator Description
3408E and 3412E Engines for Caterpillar Built Machines Atmospheric Pressure Sensor - Remove and Install
3606 and 3608 Engines Restriction of Air Inlet and Exhaust
G3408 and G3412 Engines Flywheel
G3408 and G3412 Engines Gas Pressure Regulator
G3408 and G3412 Engines Magneto
3116 and 3126 Marine Engines Turbocharger - Inspect
G3408 and G3412 Engines Governor
G3408 and G3412 Engines Governor Control
Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 06 Alarm (Action) Current Above Normal - Test
G3408 and G3412 Engines Governor Linkage
Generator Set Control Panel for Switchgear Conversion CID 0263 FMI 04 Sensor Power Supply Voltage Below Normal - Test
Generator Set Control Panel for Switchgear Conversion Charging System - Test
P16, P20, P25, P28, P40 and P60 Pulverizers Gerotor Motor - Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.