3606 and 3608 Engines Caterpillar


Restriction of Air Inlet and Exhaust

Usage:

3608 6MC
The air flow through the air silencer may have a restriction. A restriction can be caused by a used filter element or a plugged filter element. The restriction must not be more than 4.0 kPa (15 inches of H2O). Air flow through the air silencer must not have a restriction of more than 1.25 kPa (5 inches of H2O) with a new filter element.

Note: The restriction at the air silencer is the difference in the pressure between the atmospheric air and the air that has gone through the air silencer.

Back pressure from the exhaust must not be more than 2.5 kPa (10 inches of H2O).

Note: Back pressure is the difference in the pressure between the exhaust at the outlet elbow and the atmospheric air.

Caterpillar Information System:

Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 05 Alarm (Action) Current Below Normal - Test
3116 and 3126 Marine Engines Heat Exchanger - Inspect
Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 03 Alarm (Action) Voltage Above Normal - Test
3408E and 3412E Engines for Caterpillar Built Machines Engine Oil Pan - Remove and Install
G3408 and G3412 Engines Cylinder Liner
3408E and 3412E Engines for Caterpillar Built Machines Engine Oil Cooler Bypass Valve - Remove and Install
Generator Set Control Panel for Switchgear Conversion CID 0263 FMI 03 Sensor Power Supply Voltage Above Normal - Test
Generator Set Control Panel for Switchgear Conversion Alert Indicator - Troubleshoot
3054 Engine for Caterpillar Built Machines Crankshaft Gear - Remove and Install
3054 Engine for Caterpillar Built Machines Piston Cooling Jets - Remove and Install
Generator Set Control Panel for Switchgear Conversion Alarm Silence Switch - Troubleshoot
Generator Set Control Panel for Switchgear Conversion Alert Indicator Description
G3408 and G3412 Engines Flywheel
G3408 and G3412 Engines Gas Pressure Regulator
G3408 and G3412 Engines Magneto
3116 and 3126 Marine Engines Turbocharger - Inspect
G3408 and G3412 Engines Governor
G3408 and G3412 Engines Governor Control
Generator Set Control Panel for Switchgear Conversion CID 0271 FMI 06 Alarm (Action) Current Above Normal - Test
G3408 and G3412 Engines Governor Linkage
Generator Set Control Panel for Switchgear Conversion CID 0263 FMI 04 Sensor Power Supply Voltage Below Normal - Test
Generator Set Control Panel for Switchgear Conversion Charging System - Test
P16, P20, P25, P28, P40 and P60 Pulverizers Gerotor Motor - Install
Generator Set Control Panel for Switchgear Conversion Clear/Mode Switch - Troubleshoot
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.