Inlet Air Temperature Sensor - Remove and Install
Removal Procedure
Show/hide table
NOTICE |
---|
Keep all parts clean from contaminants. Contaminants may cause rapid wear and shortened component life. |
- Disconnect harness assembly (2) .
Show/hide table
Illustration 1 | g01693295 |
- Remove inlet air temperature sensor (1) from the aftercooler.
- Remove O-ring seal (3) from inlet air temperature sensor (1) .
Show/hide table
Illustration 2 | g01694055 |
Installation Procedure
Show/hide table
NOTICE |
---|
Keep all parts clean from contaminants. Contaminants may cause rapid wear and shortened component life. |
- Install a new O-ring seal (3) on inlet air temperature sensor (1) .
Show/hide table
Illustration 3 | g01694055 |
- Install inlet air temperature sensor (1) and tighten to a torque of 20 ± 5 N·m (15 ± 4 lb ft).
Show/hide table
Illustration 4 | g01693295 |
- Connect harness assembly (2) .
Caterpillar Information System:
PM3516 Power Modules Refill Capacities and Recommendations
2009/01/26 Improved Fuel Injection Pump Timing Tool {1251}
C18 Fire Pump Industrial Engine Valve Mechanism Cover - Remove and Install
C18 Fire Pump Industrial Engine Housing (Front) - Install
C18 Fire Pump Industrial Engine Housing (Front) - Remove
3516C HD Generator Set with Gearbox Emergency Stopping
TH55FT-E70 and TH55FT-E90 Transmissions Breather (Transmission) - Clean
R250 Automatic Voltage Regulator Remote Voltage Control
R250 Automatic Voltage Regulator Voltage - Adjust
R250 Automatic Voltage Regulator Stability - Adjust
Visual Inspection of Main Bearings and Connecting Rod Bearings {1202, 1203, 1225, 1230} Visual Inspection of Main Bearings and Connecting Rod Bearings {1202, 1203, 1225, 1230}
3516C Generator Sets Configuration Parameters
3512B SR4B Generator Sets Radiator - Clean
C18 Fire Pump Industrial Engine Turbocharger Outlet Pressure Sensor - Remove and Install
C6.6 Marine Generator Set Engine Design
2008/10/27 A New Heat Shield for the Exhaust Manifold is Available {1067}
2008/12/15 A New Pressure Gauge Is Now Used. {7456}
Winding Insulation Maintenance and Cleaning and Drying of the Generators {4450} Winding Insulation Maintenance and Cleaning and Drying of the Generators {4450}
C18 Fire Pump Industrial Engine Electronic Control Module - Remove and Install
G3516 Petroleum Engines Fuel Control Actuator - Remove and Install
C18 Fire Pump Industrial Engine Alternator - Remove and Install
C18 Fire Pump Industrial Engine Air Cleaner - Remove and Install
C18 Fire Pump Industrial Engine Expansion Tank - Remove and Install
C18 Fire Pump Industrial Engine Heat Exchanger - Remove