Valve Mechanism Cover - Remove and Install
Removal Procedure
Show/hide table
NOTICE |
---|
Keep all parts clean from contaminants. Contaminants may cause rapid wear and shortened component life. |
- Loosen the nuts on both clamp assemblies (1) .
Show/hide table
Illustration 1 | g01692214 |
Top view |
Show/hide table
Illustration 2 | g01692613 |
Side view |
- Remove clamp assemblies (4) and remove bolts (3) .
- Remove bolt (5) and remove tube assembly (2) .
- Disconnect breather tube (8) from the valve mechanism cover (7) .
Show/hide table
Illustration 3 | g01692637 |
- Remove bolts (6) that hold valve mechanism cover (7) to the valve mechanism cover base. Remove the valve mechanism cover (7) .
Installation Procedure
Show/hide table
NOTICE |
---|
Keep all parts clean from contaminants. Contaminants may cause rapid wear and shortened component life. |
- Position valve mechanism cover (7) on the valve mechanism cover base. Install bolts (6). Tighten the bolts to a torque of 18 ± 3 N·m (13 ± 2 lb ft) in the numerical sequence that is shown in Illustration 5.
Show/hide table
Illustration 4 | g01692637 |
Show/hide table
Illustration 5 | g00579295 |
Tightening sequence |
- Install breather tube (8) to the valve mechanism cover.
- Position tube assembly (2) and install clamp assemblies (4) .
Show/hide table
Illustration 6 | g01692613 |
Side view |
Show/hide table
Illustration 7 | g01692214 |
Top view |
- Install bolts (3) and (5) .
- Install clamp assemblies (1). Tighten the nuts on clamp assemblies (1) to a torque of 14 ± 1 N·m (124 ± 9 lb in). Lightly tap around the diameter of the clamp assembly with a soft hammer. Tighten the nut to a torque of 14 ± 1 N·m (124 ± 9 lb in).
Caterpillar Information System:
C18 Fire Pump Industrial Engine Housing (Front) - Install
C18 Fire Pump Industrial Engine Housing (Front) - Remove
3516C HD Generator Set with Gearbox Emergency Stopping
TH55FT-E70 and TH55FT-E90 Transmissions Breather (Transmission) - Clean
R250 Automatic Voltage Regulator Remote Voltage Control
R250 Automatic Voltage Regulator Voltage - Adjust
R250 Automatic Voltage Regulator Stability - Adjust
Visual Inspection of Main Bearings and Connecting Rod Bearings {1202, 1203, 1225, 1230} Visual Inspection of Main Bearings and Connecting Rod Bearings {1202, 1203, 1225, 1230}
3516C Generator Sets Configuration Parameters
G3516 Petroleum Engines Crankcase Breather - Remove and Install
2008/10/01 A New Fuel Enable Valve Is Now Used {5479}
TH55FT-E70 and TH55FT-E90 Transmissions Safety Messages
2009/01/26 Improved Fuel Injection Pump Timing Tool {1251}
PM3516 Power Modules Refill Capacities and Recommendations
C18 Fire Pump Industrial Engine Inlet Air Temperature Sensor - Remove and Install
3512B SR4B Generator Sets Radiator - Clean
C18 Fire Pump Industrial Engine Turbocharger Outlet Pressure Sensor - Remove and Install
C6.6 Marine Generator Set Engine Design
2008/10/27 A New Heat Shield for the Exhaust Manifold is Available {1067}
2008/12/15 A New Pressure Gauge Is Now Used. {7456}
Winding Insulation Maintenance and Cleaning and Drying of the Generators {4450} Winding Insulation Maintenance and Cleaning and Drying of the Generators {4450}
C18 Fire Pump Industrial Engine Electronic Control Module - Remove and Install
G3516 Petroleum Engines Fuel Control Actuator - Remove and Install
C18 Fire Pump Industrial Engine Alternator - Remove and Install