Power Transformer Failures Due to Overburden of the Medium Voltage Power Transformers Caterpillar


Power Transformer Failures Due to Overburden of the Medium Voltage Power Transformers

Usage:

Power Transformer Failures Due to Overburden of the Medium Voltage Power Transformers

CONFIDENTIAL

TECHNICAL INFORMATION BULLETIN

October 24, 2001

Engines

 

 

 

 

 

 

 

 

 

 

Generator Sets

3508 (23Z, 69Z, 70Z, 96Y, 3LS,

5XM)

3508B (6PN, 4GM, 2HW)

3512 (24Z, 66Z, 67Z, 6PM, 3MS,

50Y)

3512B (8RM, 6WN, 5AW, 4AW)

3516 (29Z, 25Z, 72Z, 73Z, 4XF

5SJ, 4MJ, 7KM, 3NS)

3516B (7RN, 6HN, 2JW, 1NW)

G3508 (2JF, 4WD, 9TG, 2TJ)

G3512 (4KC, 5JD, 7NJ)

G3516 (3RC, 8LD, 4EK)

3516 (8TW)

3516B (8NW)

G3508 (CPJ, CPS)

G3512 (CSP, CRN)

G3516 (CPG, CSZ)

`

Component Code(s) 1409

SUBJECT: Power Transformer (PT) Failures Due to Overburden of the Medium Voltage Power Transformers

PROBLEM: The 149-3403 Transformer is a medium voltage power transformer that is rated at 5 VA maximum output. On a 149-3403 Transformer with 240 volt load-share module sensing, the load puts a total burden of approximately 6.47 VA on phase two of the three-phase transformer configuration. This can lead to early failure of the solder connection and can cause corona damage inside the generator cabinet.

SOLUTION: Using the 35:1 PT secondary leads instead of the 17.5:1 leads, rewire the load-share-sensing voltage to the 120 VAC input. At 120 VAC sensing, the VA rating of the Woodward load-share-sensing circuit drops to approximately 2.35 VA per phase.

Perform the following steps in order to reduce the load on the transformers and to provide long-term reliable operation.

  1. Remove the load share sensing leads from terminals 20, 22, and 24. Re-attach these leads to terminals T1, T3, and T2 on the 170-5400 Terminal Strip Group. Refer to Illustration 1, Illustration 2, and Illustration 3.
  2. Locate the leads of the TX1 secondary output and the TX2 secondary output. The leads of the TX1 secondary output and the TX2 secondary output are black with white tracers. These leads should be connected to terminal T1 and terminal T3 on the 170-5400 Terminal Strip Group.
  3. Install a 14 gauge jumper wire from terminal 24 (170-5400 Terminal Strip Group) to terminal T2 (170-5400 Terminal Strip Group). This will bring the total burden on the potential transformers to approximately 4 VA.
  4. If main the Terminal Strip does not have T2, refer to Illustration 3 in order to connect the Load Share Module.

Note: When medium voltage generator transformer sensing leads are attached to the bus bars, apply an equal amount of torque to connections T1, T2, T3, and T0. If equal torque is not applied to these connections, voltage losses across the poor connections could cause voltage readout accuracy errors on the EMCPII.

During operation, there should be approximately 120 ACV across any two of the following 170-5400 Terminal Strip terminals: T1, T2, and T3. Refer to Table 1.

 

Table 1

170-5400 Terminal Strip Voltages

Terminals Measured

Voltage Across Terminals

T1 and T2

120 ACV

T1 and T3

120 ACV

T2 and T3

120 ACV

 

 

 

 

Illustration 1. Old 240 volt wiring

 

Illustration 2. New 120 Volt Wiring

 

 

Illustration 3. New 120 volt wiring

 

COPYRIGHT 2001 CATERPILLAR
ALL RIGHTS RESERVED

Caterpillar Information System:

An Improperly Vented Aftercooler May Force Coolant Out Of The Radiator Overflow Tube An Improperly Vented Aftercooler May Force Coolant Out Of The Radiator Overflow Tube
Software Update Software Update
Lack Of Power, Engine Speed Does Not Return To Rated Or High Idle Speed Lack Of Power, Engine Speed Does Not Return To Rated Or High Idle Speed
Low Level Leakage Experienced With The New Caterpillar Yellow Rod Seals Low Level Leakage Experienced With The New Caterpillar Yellow Rod Seals
Air Inlet Heater Air Inlet Heater
Lack Of Power, Engine Speed Does Not Return To Rated Or High Idle Speed Lack Of Power, Engine Speed Does Not Return To Rated Or High Idle Speed
3500B Engines That Are Used On EPG Applications And Have An Emergency Stop Box Are Wired Incorrectly 3500B Engines That Are Used On EPG Applications And Have An Emergency Stop Box Are Wired Incorrectly
Air Inlet Heater Air Inlet Heater
Slow Vessel Mode (550 RPM) Slow Vessel Mode (550 RPM)
168-7823 Time Delay Relay In The Engine Supervisory System (ESS) 168-7823 Time Delay Relay In The Engine Supervisory System (ESS)
Flywheel Housing Failures Flywheel Housing Failures
Incorrect Assembly Instructions For Rod Seals In Hydraulic Cylinders Incorrect Assembly Instructions For Rod Seals In Hydraulic Cylinders
Aftercooler Condensate Drains Aftercooler Condensate Drains
A Loose Or Missing Plug Will Allow A Boost Pressure Leak That May Result In Decreased Performance A Loose Or Missing Plug Will Allow A Boost Pressure Leak That May Result In Decreased Performance
Identification Of Failed Hydrax Actuator Solenoids Identification Of Failed Hydrax Actuator Solenoids
G3516B Maintenance Guidelines G3516B Maintenance Guidelines
Turbocharger Oil Drain Lines Turbocharger Oil Drain Lines
XQ 2000 Power Module Slide Rail on 3500B Diesel Generator Sets XQ 2000 Power Module Slide Rail on 3500B Diesel Generator Sets
Auto-Up Stabilizer Auto-Up Stabilizer
Wiring Change For The Starter Motor Magnetic Switch Wiring Change For The Starter Motor Magnetic Switch
Excessive Blow-By And Oil Consumption Complaints Excessive Blow-By And Oil Consumption Complaints
Air Inlet Heater And Air Inlet Heater Relay Wiring Air Inlet Heater And Air Inlet Heater Relay Wiring
Belt Squeal Belt Squeal
Engine Oil Dilution By Fuel Engine Oil Dilution By Fuel
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.