C15 Generator Set Caterpillar


Electronic Modular Control Panel 4 (EMCP 4)

Usage:

C15 AR2

EMCP 4.1/4.2 (If Equipped)




Illustration 1g02082653

EMCP 4 Control System Panel

(1) Display screen

(2) AC overview key

(3) Engine overview key

(4) Main menu key

(5) Alarms acknowledge key

(6) Reset shut down Key

(7) Event log

(8) Run key

(9) Auto key

(10) Stop key

(11) Escape key

(12) Up key

(13) Right key

(14) OK key

(15) Down key

(16) Left key

Navigation Keys

Acknowledge Key (5) - Pressing the "ACKNOWLEDGE" key will cause the horn relay to turn off. The horn will be silenced. Pressing this key will also cause any red or yellow flashing lights to either turn off or to come on continuously. Whether red or yellow flashing lights turn off, or comes on continuously depends on the active status of the alarms. The "ACKNOWLEDGE" key may also be configured to send out a global alarm silence signal on the J1939 Data Link. A global alarm silence signal will silence the horns on the annunciators.

Reset Key (6) - Pressing the "RESET" key will reset various events.

Event Log Key (7) - Pressing the "EVENT LOG" key will navigate the display to the event log.

RUN Key (8) - Pressing the "RUN" key will start the engine.

AUTO Key (9) - Pressing the "AUTO" key will cause the engine to enter the "AUTO" mode. The engine will start if the module receives a start command from a remote source.

STOP Key (10) - Pressing the "STOP" key will stop the engine.

Escape Key (11) - The "ESCAPE" key is used in order to navigate through the menus. When the key is pressed, the user moves backward or the user moves upward through the menus. The "ESCAPE" key is also used to exit out of entering data when the user is programming the setpoints. If the "ESCAPE" key is pressed while the user is programming setpoints, none of the changes made on the screen will be saved to memory.

Up Key (12) - The "UP" key is used to navigate through the various menus and monitoring screens. The "UP" key is also used when a setpoint is entered. When entering numeric data, the "UP" key is used in order to increment the digits (0-9). If the setpoint requires selection from a list, the "UP" key is used to navigate UP through the list.

Right Key (13) - The "RIGHT" key is used during setpoint adjustment. The "RIGHT" key is used to select which digit is edited while entering numeric data. The "RIGHT" key is also used during some setpoint adjustments in order to select or to unselect a check box. If a check box has a check mark, the function has been enabled. Pressing the "RIGHT" key will disable the function. Pressing the "RIGHT" key will also cause the check mark to disappear. If the check box does not have a check mark, the function is disabled. Pressing the "RIGHT" key will enable the function. Pressing the "RIGHT" key will also cause a check mark to appear.

Enter Key (14) - The "ENTER" key is used in order to navigate through the menus. When the key is pressed, the user moves forward or the user moves downward through the menus. The "ENTER" key is also used to save any changes while the setpoints are being programmed. Pressing the "OK" key during programming the setpoints causes the changes to be saved to memory.

Down Key (15) - The "DOWN" key is used to navigate downward through the various menus or screens. The "DOWN" key is also used to program the setpoints. The "DOWN" key is used to decrease the digits when entering numeric data. If the setpoint requires selection from a list, the "DOWN" key is used to navigate DOWN through the list.

Left Key (16) - The "LEFT" key is used during setpoint adjustment. The "LEFT" key is used to select the digit that is edited during the entry of numeric data. The "LEFT" key is also used during some of the setpoint adjustments to select a check box. The key is also used to unselect a check box. If a check box has a check mark, pressing the "LEFT" key will disable the function. Pressing the key will also remove the check mark. Pressing the "LEFT" key will also cause the check mark to disappear. If the check box does not have a check mark, pressing the "LEFT" key will enable the function. Pressing the "LEFT" key will also cause a check mark to appear.

Main Menu Key (4) - The "MAIN MENU"key will navigate the display to the main menu directly without having to navigate out of menus.

Engine Overview (3) - The "ENGINE OVERVIEW" key will navigate the display to the first screen of engine information. The "ENGINE OVERVIEW" information contains various engine parameters that summarize the operation of the generator set.

AC Overview (2) - The "AC OVERVIEW" key will navigate the display to the first screen of AC information. The "AC OVERVIEW" information contains various AC parameters that summarize the electrical operation of the generator set.

Advanced Genset Controller (AGC) (If Equipped)




Illustration 2g03879782

(17) Measured values button

(18) Log lists button

(19) Parameter settings button

(20) Service menu button

(21) Select/arrow buttons

(22) Alarm list button

(23) Silence horn button

(24) Escape/back button

(25) Test mode button

(26) Lamp test button

(27) Semi-auto mode button

(28) Off mode button

(29) Manual mode button

(30) Auto mode button

(31) Main breaker open button

(32) Main breaker closed button

(33) Generator breaker open button

(34) Generator breaker closed button

(35) Stop button

(36) Start button

Measured values button (17) - this button allows the user to view measured values.

Log lists button (18) - this button displays a list of logged events that are deleted when the AGC is switched OFF. The list holds up to 150 events.

Parameter settings button (19) - this button displays parameter settings.

Service menu button (20) - this button displays the service menu.

Select/arrow buttons (21) - these buttons are used to navigate through the user menus and screens.

Alarm list button (22) - this button displays any alarms that are present.

Silence horn button (23) - this button mutes the horn.

Escape/back button (24) - this button returns the screen to the previous selection.

Test mode button (25) - this button switches the AGC to "TEST" mode.

Lamp test button (26) - this button illuminates the indicators to test for proper function.

Semi-auto mode button (27) - this button switches the AGC to SEMI.

Off mode button (28) - this button switches the AGC to OFF.

Manual mode button (29) - this button switches the AGC to MANUAL.

Auto mode button (30) - this button switches the AGC to AUTO.

Mains breaker open button (31) - this button opens the mains circuit breaker when pressed.

Mains breaker closed button (32) - this button closes the mains circuit breaker when pressed.

Generator breaker open button (33) - this button opens the generator circuit breaker when pressed.

Generator breaker closed button (34) - this button closes the generator circuit breaker when pressed.

Stop button (35) - this button stops the generator set when the EMCP is in AUTO.

Start button (36) - this button starts the generator set when the EMCP is in AUTO.




Illustration 3g03879784

(37) User configurable LED

(38) Power indicator

(39) Alarm indicator

(40) Off indicator

(41) Semi-auto mode indicator

(42) Manual mode indicator

(43) Auto mode indicator

(44) Mains indicator

(45) Mains breaker closed indicator

(46) Generator breaker closed indicator

(47) Voltage frequency indicator

(48) Generator running indicator

User configurable LED (37) - these indicators can be programmed by the user.

AUX power indicator (38) - this indicator will illuminate when the AGC auxiliary power supply input is ON.

Alarm indicator (39) - this indicator will flash when unacknowledged alarms are present. Illuminated but not flashing indicates that all alarms are acknowledged, but some are still present.

Off indicator (40) - this indicator will illuminate when the AGC is in OFF.

Semi-auto mode indicator (41) - this indicator will illuminate when the AGC is in SEMI-AUTO.

Manual mode indicator (42) - this indicator will illuminate when the AGC is in MANUAL.

Auto mode indicator (43) - this indicator will illuminate when the AGC is in AUTO.

Mains indicator (44) - this indicator will illuminate green if the mains is present and within limits. This indicator will illuminate red at a mains failure. This indicator will flash green when the mains returns during the "mains OK delay" time.

Mains breaker closed indicator (45) - this indicator will illuminate when the mains breaker is closed.

Generator breaker closed indicator (46) - this indicator will illuminate when the generator breaker is closed.

Voltage frequency indicator (47) - this indicator will illuminate when the generator voltage, and frequency are within limits.

Generator running indicator (48) - this indicator will illuminate when the generator is running.

AGC Display Navigation

The display is a backlit LCD graphical display. The display light intensity, LED indication, and contrast can be adjusted via menu 9150.

All measured and calculated values can be read in the display, and may be selected via the PC utility software.

The display includes two menu systems which can be used without password entry:

View menu system - The commonly used menu system. 20 windows are configurable and can be entered by using the arrow buttons.

Setup menu system (not commonly used by the operator) - The menu system that is used to set up the unit. Setup menu system is also used if the operator needs detailed information that is not available in the view menu system. Changing of parameter settings is password protected.

Entry window

When the unit is powered up, an entry window appears. The entry window is gateway to other menus. The entry window can always be reached by pushing the "Escape/back" button (37) 3 times.

Note: The event and alarm list will appear at power up if an alarm is present.




Illustration 4g03845202

View menu

The view menus (V1, V2, and V3) are the daily use menus for the operator.




Illustration 5g03845200

In the view menus, various measured values are on display.

First display line - operational status or measurements

Second display line - measurements relating to operational status

Third display line - measurements relating to operational status

Fourth display line - selection of setup and view menus

Display of measured values according to the selections made during configuration.

For detailed information about configuration, reference OEM manual"Designer's Reference Handbook".

The views contain up to 20 different windows which can be navigated/selected using the "UP", and "DOWN" arrow buttons (34) to move the cursor. Once the cursor has reached the desired value, use "SEL" (center of (34) ) to make a selection.

Status line text

There are a number of messages that may appear in the status line of the AGC display. The messages are explained in the table, and figures below.

Table 1
Status text     Condition     Comment    
BLOCK     Block mode is activated        
SIMPLE TEXT     Test mode is activated        
LOAD TEST    
FULL TEST    
SIMPLE TEST ###.#min     Test mode is activated, and test timer is counting down        
LOAD TEST ###.#min    
FULL TEST ###.#min    
ISLAND MAN     Genset is stopped or running, and no other action is taking place        
ISLAND SEMI    
READY ISLAND AUTO     Genset is stopped in AUTO        
ISLAND ACTIVE     Genset is running in AUTO        
AMF MAN     Genset is stopped or running, and no other action is taking place        
AMF SEMI    
READY AMF AUTO     Genset is stopped in AUTO        
AMF ACTIVE     Genset is running in AUTO        
FIXED POWER MAN     Genset is stopped or running, and no other action is taking place        
FIXED POWER SEMI    
READY FIXED P AUTO     Genset is stopped in AUTO        
FIXED POWER ACTIVE     Genset is running in AUTO        
PEAK SHAVING MAN     Genset is stopped or running, and no other action is taking place        
PEAK SHAVING SEMI    
READY PEAK SHAV AUTO     Genset is stopped in AUTO        
PEAK SHAVING ACTIVE     Genset is running in AUTO        
LOAD TAKEOVER MAN     Genset is stopped or running, and no other action is taking place        
LOAD TAKEOVER AUTO    
READY LTO AUTO     Genset is stopped in AUTO        
LTO ACTIVE     Genset is running in AUTO        
MAINS P EXPORT MAN     Genset is stopped or running, and no other action is taking place        
MAINS P EXPORT SEMI    
READY MPE AUTO     Genset is stopped in AUTO        
MPE ACTIVE     Genset is running in AUTO        
DG BLCKD FOR START     Generator is stopped and active alarms present on the generator        
GB ON BLOCKED     Generator is running, generator breaker is open and an active "TRIP GB" alarm is present        
SHUTDOWN OVERRIDE     The configurable input is active        
ACCESS LOCK     The configurable input is activated, and the operator tries to activate one of the blocked keys        
GB TRIP EXTERNALLY     Some external equipment has tripped the breaker     An external trip is logged in the event log    
MB TRIP EXTERNALLY     Some external equipment has tripped the breaker     An external trip is logged in the event log    
IDLE RUN     The "idle run" function is active. The genset will not stop, until a timer has expired        
IDLE RUN ###.#min     The timer in the "idle run"function is active        
COMPENSATION FREQ.     Compensation is active     The frequency is not at the nominal setting    
Aux. test ###.#V ####     Battery test activated        
DELOAD     Decreasing the load of the genset in order to open the breaker        
START DG(s) IN ###S     The start genset set point is exceeded        
STOP DG(s) IN ###S     The stop genset point is exceeded        
START PREPARE     The start prepare relay is activated        
START RELAY ON     The start relay is activated        
START RELAY OFF     The start relay is deactivated during the start sequence        
MAINS FAILURE     Mains failure and mains failure timer expired        
MAINS FAILURE IN ###S     Frequency or voltage measurement is outside the limits     The timer shown is the mains failure delay    
MAINS U OK DEL ###S     Mains voltage is OK after a mains failure     The timer shown is the mains OK delay    
MAINS f OK DEL ###S     Mains voltage is OK after a mains failure     The timer shown is the mains OK delay    
Hz/V OK IN ###S     The voltage and frequency of the genset is OK     When the timer runs out, it is allowed to operate the generator breaker    
COOLING DOWN ###S     Cooling down period is activated        
Genset STOPPING     This info is shown when cooling down has finished        
EXT. STOP TIME ###S            
PROGRAMMING LANGUAGE     This info is shown if the language file is downloaded from the PC utility software        
EXT. START ORDER     A planned AMF sequence is activated     There is no failure on the mains during this sequence    
30 min data storage     A safety precaution to protect the flash memory storage     Activated because too many parameters have been changed within a short time. When active, no flash or settings are stored. This condition can be caused by M-Logic or Modbus    
SELECT Genset MODE     Power management has been deactivated and no other genset mode has been selected        
QUICK SETUP ERROR     Quick setup of the application failed        
MOUNT CAN CONNECTOR     Connect the power management CAN line        
ADAPT IN PROGRESS     The AGC 200 is receiving the application that has recently been connected        
SETUP IN PROGRESS     The new AGC is being added to the existing application        
SETUP COMPLETED     Successful update of the application in all AGC units        

REMOVE CAN CONNECTOR    
Remove the power management CAN lines        
RAMP TO #####kW     The power ramp is ramping in steps, and the next step that will be reached after the timer has expired will be displayed        
DERATE TO #####kW     Displays the ramp down set point        
DG unit    
BLACKOUT ENABLE     This information is shown if a CAN failure is present in a power management application        
UNIT STANDBY     If redundant mains units are present, this message is shown on the redundant unit        
DELOADING BTB XX     DG units are load sharing asymmetrically to deload BTB XX dividing two sections in an application        
BTB XX DIVIDING SEC.     BTB XX is dividing two sections in an application        
SYNCHRONISING TB XX     TB XX is synchronizing        
SYNCHRONISING MB XX     MB XX is synchronizing        
SYNCHRONISING BTB XX     BTB XX is synchronizing        
Mains unit    
UNIT STANDBY     If redundant mains units are present, this message is shown on the redundant unit        
TB TRIP EXTERNALLY     Some external equipment has tripped the breaker     An external trip is logged in the event log    
BTB unit    
DIVIDING SECTION     A BTB unit is dividing two sections in an application        
READY AUTO OPERATION     BTB unit in Auto and ready for breaker operation (no active "BTB trip" alarm        
SEMI OPERATION     BTB unit in Semi-automatic        
AUTO OPERATION     BTB unit in Auto, but not ready for breaker operation (active "BTB trip" alarm)        
BLOCKED FOR CLOSING     Last open BTB in a ring bus        
BTB TRIP EXTERNALLY     Some external equipment has tripped the breaker     An external trip is logged in the event log    
All units    
BROADCATING APPL. #     Broadcast of an application through the CAN line     Broadcasts one of the four applications from one unit to the other AGCs in the power management system    
RECEIVING APPL. #     AGC 200 receiving an application        
BROADCAST COMPLETED     Successful broadcast of an application        
RECEIVE COMPLETED     Application received successfully        
BROADCAST ABORTED     Broadcast terminated        
RECEIVE ERROR     Application is not received correctly        



Illustration 6g03847499

Typical example of a view menu

Synchronization status

There are a number of statuses that may be shown on the AGC display, that concern synchronization. Those include text and graphics, and will look similar to the images in illustrations 7, 8, and 9.




Illustration 7g03848742

Generator is synchronizing




Illustration 8g03848769

Generator running too slow during synchronizing




Illustration 9g03848777

Generator running too fast during synchronizing

Modes of Operation

"SEMI" (Semi-automatic)

"SEMI" mode is activated by pressing the "SEMI" button (40) on the front of the AGC controller.

The display buttons ( (30) - (49) ) are active and can be used by the operator.

The regulators are also active. The speed control will bring the generator to nominal speed upon start.

When pushing a breaker button for closing, the AGC will synchronize (if allowed) the breaker. When the breaker closes, the regulation continues, but no breakers are opened or closed.

"TEST"

"TEST" mode is activated by pressing the "Test mode" button (38) on the front of the AGC controller.

The unit will start the generator, carry out the test sequence (predefined time period) and stop the generator again. The generator will return to "AUTO" or "SEMI" mode (defined in parameter 7043) after the test sequence. The mains breaker will remain closed, and the generator breaker will remain open.

Note: The test running can be: Simple test(starting the generator set without closing the generator breaker), Load test (parallel to the mains and take load to a predefined value), or Full test(transfer the load to the generator set and open the mains breaker if the generator set can take the full load.

"AUTO"

"AUTO" mode is activated by pressing the "Auto mode" button (43) on the front of the AGC controller.

The unit will automatically carry out the selected genset/plant mode (AMF, fixed power, and so on).

The display control buttons ( (46) - (49) ) are disabled.

If the selected genset/plant mode is any of the following, start/stop can be used:

  • fixed power

  • mains power export

  • load takeover (island)

  • timer start/stop (week watch)

  • binary input

In PM systems, start/stop buttons can only be used from a mains unit with parameter 8021 set to "LOCAL". If used in a single DG application, start can only be set with a digital input or timer.

"MAN"

"MAN" mode is activated by pressing the "Manual mode" button (42) on the front of the AGC controller.

The display control buttons ( (48) , (49) ) are active and can be used by the operator.

The regulators are not active. Speed (and voltage) control has to take place using external controls for generator speed and possibly generator voltage control.

The breakers will be able to open or close at any time. A synchronization check will always be performed to ensure safe closing of the breakers.

"BLOCK"

"BLOCK" mode is activated by pressing the "Off mode" button (41) on the front of the AGC controller.

The unit will not be able to start. "BLOCK" mode can be selected during standstill, or when running. If activated when running, the generator set will stop and enter "BLOCK" mode. When "BLOCK" mode is activated, no inputs will be able to start the genset. To exit "BLOCK" mode, press the "AUTO" (43) , "SEMI" (40) , or "MAN" (42) button.

Alarms

When an alarm occurs, the unit will automatically go to the alarm list, if selected (setting 6900 Alarm jump) for display of the alarm. If setting 6900 is "OFF", press the alarm list button (35) to enter the alarm list.

Use the "escape/back" button (37) to exit the alarm list when required.

The alarm list contains both acknowledged and unacknowledged alarms if the alarm condition is still present. Once an alarm is acknowledged and the condition has disappeared, the alarm will no longer be displayed in the alarm list.

If there are no alarms, the alarm list will say "no alarms."




Illustration 10g03845199

A typical example of an unacknowledged alarm.

Only one alarm is displayed at a time.

To see the other alarms, use the "UP", and "DOWN" arrow buttons (34) to scroll in the display. To acknowledge an alarm, place the cursor over the channel number and then press "SEL" (center of (34) ).

Log list

The log is divided into three different lists:

  • Events

  • Alarms

  • Battery test

The log list contains up to 150 events. The alarm list contains up to 30 historical alarms. The battery test list contains up to 52 historical battery tests.

An example of an "event" is the closing of a breaker, or starting of an engine. An example of an "alarm" is over-current, or high cooling water temperature. An example of a battery test is "OK," or "test failed."

To enter the log list:

  1. Press the "log lists button" (31)

  1. Use the "UP", and "DOWN" arrow buttons (34) to scroll to the desired list, then press "SEL" (center of (34) ).
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.