C18 Generator Set Caterpillar


Product Installation

Usage:

C18 DDS

Assembly Instructions for Partially Completed Machinery per the EU Machinery Safety Directive 2006/42/EC

To ensure that this product is correctly installed and does not compromise safety and health, please refer to the material in the appropriate Application and Installation Guide and the material contained in this Operations and Maintenance Manual.

Receiving Inspection

If the generator is received during cold weather, allow the unit to reach room temperature before you remove the protective packing material. Warming the generator to room temperature will prevent the following problems:

  • Water condensation on cold surfaces

  • Early failures due to wet windings

  • Early failures due to wet insulating materials

Unpacking and Storage

Moving the Generator

------ WARNING! ------

Improper lift rigging can allow unit to tumble causing injury and damage.

----------------------


NOTICE

Do not use the engine lifting eyes to remove the engine and generator together.


Unpack the equipment with care in order to avoid scratching painted surfaces. Move the unit to the mounting location. The unit can be moved by either of the following methods:

  • Attach an overhead crane to the eyebolts that are installed on the generator frame.

  • Use a lift truck in order to lift the generator.

The hoist and the hoist cables should have a rating that is greater than the weight of the generator. When the unit is moved, ensure that the generator is completely supported by the lift truck's fork tines. Also ensure that the generator is balanced on the lift truck's fork tines. Slide the fork tines beneath the attached skid in order to lift the generator.

Storage

Short Time Storage

If the generator is not installed immediately, store the generator in a clean area. This area should also have the following conditions: low humidity, stable humidity and stable temperature. Space heaters must be energized in order to keep condensation from the windings. All accessory equipment that is supplied with the unit should be stored with the generator. The combined unit should be covered with a durable cover in order to protect against the following contaminants:

  • Dust

  • Dirt

  • Moisture

  • Other airborne abrasive material

Long Time Storage

Refer to Special Instructions, "Preservation Procedures and Practices for Extended Storage" for information concerning long term storage.

Bearing Inspection

Ball bearing generators use grease. This grease is subject to deterioration. If the generator is stored longer than one year, new ball bearings should be installed. These bearings should be greased to the proper level prior to being put into operation. If inspection indicates that bearings are free of rust or corrosion, and no noise or excessive vibration appear on start-up, replacement is not necessary.

Location

The location of the generator must comply with all local regulations. The location of the generator must also comply with all special industrial regulations. Locate the generator in an area that meets the following requirements:

  • Clean

  • Dry

  • Well ventilated

  • Easily accessible for inspection and maintenance

Access to the radiator filler cap is on the roof of the enclosure. There must be safe access to the roof of the enclosure. There must be sufficient clearance above the roof of the enclosure.

Do not obstruct air inlet openings. Do not obstruct discharge openings. Air flow must reach these openings. If the generator is exposed to harsh environmental conditions, the generator can be modified in the field in order to add filters and space heaters. In addition, a more rigid periodic maintenance schedule should be established.

Electrical Measurements

Measure the insulation resistance of each winding if the generator was exposed to the following conditions:

  • Rapid changes in temperature

  • Freezing

  • Wet climate during shipment

  • Wet climate during storage

Note: These tests should be conducted prior to any power connections that are being made. These tests should be conducted prior to any control connections that are being made.

Refer to this Operation and Maintenance Manual, "Rotating Rectifier - Test" in order to measure the following items:

  • Exciter field (stator)

  • Exciter armature (rotor)

  • Generator field (rotor)

  • Generator armature (stator)

Protective Devices

The output to the load of the generator should always be protected with an overload protection device such as a circuit breaker or fuses. Fuses should be sized by using the lowest possible current rating. However, this rating must be above the current rating for full load. A common recommendation is 115 percent of rated current. Determine the size of fuses or determine the size of circuit breakers in accordance with NEMA, IEC, and Local Electrical Codes.

Back to top