Electronic Modular Control Panel II (EMCP II) Caterpillar


Shutdown Mode

Usage:

3406B 4JK
The shutdown mode prevents damage to the generator set when a shutdown fault is occurring. A shutdown fault is critical. When a shutdown fault occurs, the GSC automatically activates shutdown mode until the shutdown fault is corrected. The GSC shuts down the engine when the GSC is in shutdown mode. The GSC prevents starting of the engine and the GSC alerts the operator.

The GSC alerts the operator and the GSC identifies the shutdown fault by FLASHING the corresponding shutdown indicator. The name of the shutdown indicator identifies the shutdown fault.

Shutdown Indicators

  • Low oil pressure

  • Emergency stop

  • High water temperature

  • Engine overspeed

  • Low coolant level

  • Engine overcrank

  • Fault shutdown

If the fault shutdown indicator is the only indicator FLASHING, additional information is available. A fault code is shown on the upper display which more precisely identifies the cause of the shutdown fault. See Systems Operation, "Fault Description" for more information.

Shutdown Mode Sequence

  1. A shutdown fault occurs and the GSC detects the shutdown fault.

  1. To shut off the fuel, the GSC deactivates the fuel control relay (FCR). On EUI engines, in order to shut off the fuel, the GSC deactivates the electronic governor relay (EGR).

  1. In order to prevent the engine from starting, the GSC deactivates the run relay (RR), and the GSC deactivates the starting motor relay (SMR).

  1. In order to remove the generator load, the GSC activates the generator fault relay (GFR). This activates the circuit breaker shunt trip coil.

    Note: The spare output may also be programmed to activate when a shutdown occurs. This output can drive a relay in order to open the circuit breaker, or the output can open a transfer switch. See Systems Operation, "Spare Input/Output Programming OP6".

  1. When the engine speed reaches 0 rpm, the GSC deactivates the crank termination relay (CTR). The electronic governor relay (EGR) is deactivated when the engine oil pressure reaches the setpoint (P14) for low oil pressure shutdown at the idle speed 70 kPa (10 psi).

  1. The GSC FLASHES the corresponding shutdown indicator. If the fault shutdown indicator is FLASHING, a fault code is shown on the upper display. See Systems Operation, "Fault Description".

  1. If the fault shutdown indicator is the only indicator FLASHING, additional information is available. A fault code is shown on the upper display that more precisely identifies the cause of the shutdown fault. See the Systems Operation, "Fault Description".

  1. The lower display continues to show the engine data.

  1. The relay status indicators show.

    • K2 (GFR)

Engine Starting Sequence

  1. Correct the shutdown fault. See the Testing And Adjusting, "Fault Identification".

  1. Reset the GSC by turning the ECS to "OFF/RESET". If no shutdown fault is active, the GSC returns to normal mode and the engine is able to start.

Caterpillar Information System:

SCT673 Truck Mounted PumperPOD Power End Oil and Filter - Change
G3300 Engines Plate Locations and Film Locations
G3300 Engines Specifications
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 167-1351 Generator through 167-1354 Generator
Electronic Modular Control Panel II (EMCP II) Data Link
3408E and 3412E Engines for Caterpillar Built Machines Cylinder Liner Projection - Inspect
3408E and 3412E Engines for Caterpillar Built Machines Engine Valve Lash - Inspect/Adjust
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for EUI Engines)
2001/11/01 The Timing Marks Have Been Improved On The Front and Rear Balancer Gears {1220}
3408E and 3412E Engines for Caterpillar Built Machines Finding Top Center Position for No. 1 Piston
3408E and 3412E Engines for Caterpillar Built Machines Basic Engine
SCT673 Truck Mounted PumperPOD Fan Belt - Inspect/Adjust/Replace
SCT673 Truck Mounted PumperPOD Manual Stop Procedure
Electronic Modular Control Panel II (EMCP II) Service Mode
G3300 Engines Engine Valve Lash - Inspect/Adjust
C9 Marine Engines Digital Sensor Supply Circuit - Test
Electronic Modular Control Panel II (EMCP II) for EUI Engines General Information
Electronic Modular Control Panel II (EMCP II) Hourmeter Programming OP7
SPT343 Truck Mounted Pumper Product Description
3054 and 3056 Industrial and Generator Set Engines Troubleshooting
2002/03/01 A New Cover Assembly Helps Hold The Oil Screen In Place {1302}
C0.5, C0.7, C1.1/3011C, C1.5/3013C, C1.6 and C2.2/3024C/3024CT Industrial Engines and Engines for Caterpillar Built Machines Cylinder Block - Inspect
2001/11/01 A New Edition of the Special Publication, SEBD0640, "Oil and Your Engine" is Available {1348}
3126 Truck Engine (Military) Gear Group (Front) - Time
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.