Electronic Modular Control Panel II (EMCP II) Caterpillar


Starting Motor Remains Engaged (for EUI Engines)

Usage:

3406B 4JK
System Operation Description:

The starting motor remains engaged after the engine has started.

Test Step 1. CHECK THE SETPOINTS.

This test step checks the following setpoints: P11 (crank terminate speed), P17 (total cycle crank time) and P18 (cycle crank time).

  1. View the setpoints and make a note of setpoints P11, P17 and P18. See Systems Operation, "Engine/Generator Setpoint Viewing OP2".

  1. Compare the setpoints with the specified setpoints of the particular generator set. The default value for P11 is 400 rpm. The default value for P17 is 90 seconds. The default value for P18 is 10 seconds.

Expected Result:

The setpoint value that is being viewed should match the specified setpoint value.

Results:

  • OK - The setpoint is correct. Proceed to test step 2.

  • NOT OK - The setpoint that is being viewed does not agree with the specified setpoint.

    Repair: Reprogram setpoints P11, P17 and P18. See Systems Operation, "Engine/Generator Programming OP5-0".

    Stop.

Test Step 2. CHECK THE START FUNCTION OF THE ENGINE.

The following procedure will require checks to be made during simulated engine starting. Disable the fuel system.

  1. To disable the EUI engine ECM, remove the J1-40 pin connector.

  1. Prepare to manually stop the engine from cranking, if necessary. Turn the battery disconnect switch to the OFF position or shut the engine off by using mechanical means.

  1. Turn the engine control switch (ECS) to the START position. Allow the engine to crank.

  1. Turn the ECS to the OFF/RESET position.

Expected Result:

The engine should stop cranking.

Results:

  • OK - The engine does not crank. Proceed to test step 6.

  • NOT OK - The engine continues to crank. Proceed to test step 3.

Test Step 3. CHECK THE START FUNCTION OF THE ENGINE.

  1. The conditions of the previous step remain. The fuel system is disabled. The engine is cranking.

  1. While the engine is still cranking, push the emergency stop push button.

Expected Result:

The engine should stop cranking.

Results:

  • YES - The engine does not crank.

    Repair: Check the wire on "RM-18" of the relay module for a short to +battery. Repair the short or replace the harness. If a short is not found, replace the relay module. See Testing And Adjusting, "Relay Module - Replace".

    Stop.

  • NO - The engine continues to crank. Proceed to test step 4.

Test Step 4. CHECK THE START FUNCTION OF THE ENGINE.

  1. The conditions of the previous step remain. The fuel system is disabled. The engine is cranking.

  1. Stop the engine. Turn the battery disconnect switch to the OFF or shut the engine off by using mechanical means.

  1. Remove all wires from TS1-25 in the control panel.

  1. Turn the ECS to START. Attempt to crank the engine.

Expected Result:

The engine should not crank.

Results:

  • OK - The engine does not crank.

    Repair: The "SMMS" or related wiring has failed. Troubleshoot the "SMMS" and the related wiring. See the Generator Set Wiring Diagram in Testing And Adjusting, "Schematics & Wiring Diagrams".

    Stop.

  • NOT OK - The engine continues to crank. Proceed to test step 5.

Test Step 5. CHECK THE START FUNCTION OF THE ENGINE.

  1. The conditions of the previous step remain. The fuel system is disabled. The engine is cranking.

  1. Stop the engine. Turn the battery disconnect switch to OFF or shut the engine off by using mechanical means.

  1. Disconnect the "B+" wire on the pinion solenoid of the starting motor.

  1. Turn the ECS to START and attempt to crank the engine.

Expected Result:

The engine should not crank.

Results:

  • OK - The engine does not crank.

    Repair: On "EUI" engines, wire 125-152 in the package harness is shorted to the +battery. Troubleshoot the wiring. See the Generator Set Wiring Diagram in Testing And Adjusting, "Schematics And Wiring Diagrams".

    Stop.

  • NOT OK - The engine continues to crank.

    Repair: The starting motor has failed. Troubleshoot the starting motor. Refer to the Starting Motor and/or Engine Service Manuals.

    Stop.

Test Step 6. CHECK THE STARTING MOTOR CYCLING.

  1. The fuel delivery is disabled.

  1. Turn the ECS to the START position.

Expected Result:

The starting motor should cycle on and off according to setpoint P18 (cycle crank time).

Results:

  • OK - If the starting motor cycles correctly, the problem is not present. Stop.

  • NOT OK - If the starting motor remains engaged, the starting motor has failed.

    Repair: Troubleshoot the starting motor. Refer to the Starting Motor and/or Engine Service Manuals.

    Stop.

Caterpillar Information System:

2001/11/01 The Timing Marks Have Been Improved On The Front and Rear Balancer Gears {1220}
3408E and 3412E Engines for Caterpillar Built Machines Finding Top Center Position for No. 1 Piston
3408E and 3412E Engines for Caterpillar Built Machines Basic Engine
SCT673 Truck Mounted PumperPOD Fan Belt - Inspect/Adjust/Replace
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 153-3081 Generator through 153-3098 Generator
Power Module Switchgear (Low Voltage and Medium Voltage) Fire Prevention and Explosion Prevention
G3600 Engines System Overview
3054 and 3056 Engines 550 Generator Set Control Panel Alarm Operation
3054 and 3056 Engines 550 Generator Set Control Panel Normal Operation
SPT343 Truck Mounted Pumper Junction Box
3054 and 3056 Engines 550 Generator Set Control Panel Automatic Operation
Machine Security System Factory Password - Obtain
3408E and 3412E Engines for Caterpillar Built Machines Engine Valve Lash - Inspect/Adjust
3408E and 3412E Engines for Caterpillar Built Machines Cylinder Liner Projection - Inspect
Electronic Modular Control Panel II (EMCP II) Data Link
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 167-1351 Generator through 167-1354 Generator
G3300 Engines Specifications
G3300 Engines Plate Locations and Film Locations
SCT673 Truck Mounted PumperPOD Power End Oil and Filter - Change
Electronic Modular Control Panel II (EMCP II) Shutdown Mode
SCT673 Truck Mounted PumperPOD Manual Stop Procedure
Electronic Modular Control Panel II (EMCP II) Service Mode
G3300 Engines Engine Valve Lash - Inspect/Adjust
C9 Marine Engines Digital Sensor Supply Circuit - Test
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.