SR4 and SR4B Electric Power Generation Rewind Data Caterpillar


Winding Data for 109-1595 Generator through 109-3774 Generator

Usage:

SR4B 1BN

109-1595 Generator

Table 1
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18 inch)    

457.2 mm (18 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     3.4 (4-3-3-3-4)     -    
Turns/Pole     -     180    
No. & Wire Size     14 - #14     #6.5 RD    
Mean Length Turn    
1828.8 mm (72 inch)    
-    
Copper Weight    
104.3 kg (229.9 lb)    

106.6 kg (235 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00963 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1596 Generator

Table 2
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18 inch)    

457.2 mm (18 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     3.4 (4-3-3-3-4)     -    
Turns/Pole     -     180    
No. & Wire Size     14 - #14     #6.5 RD    
Mean Length Turn    
1828.8 mm (72 inch)    
-    
Copper Weight    
104.3 kg (229.9 lb)    

106.6 kg (235 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00963 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1597 Generator

Table 3
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18 inch)    

457.2 mm (18 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     3.4 (4-3-3-3-4)     -    
Turns/Pole     -     180    
No. & Wire Size     14 - #14     #6.5 RD    
Mean Length Turn    
1828.8 mm (72 inch)    
-    
Copper Weight    
104.3 kg (229.9 lb)    

106.6 kg (235 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00963 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1598 Generator

Table 4
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
566.4 mm (22.3 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     2.8 (3-3-3-3-2)     -    
Turns/Pole     -     180    
No. & Wire Size     17 - #14     #6.5 RD    
Mean Length Turn    
1983.7 mm (78.1 inch)    
-    
Copper Weight    
106.8 kg (235.5 lb)    

123.4 kg (272 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0074 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1599 Generator

Table 5
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
566.4 mm (22.3 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     2.8 (3-3-3-3-2)     -    
Turns/Pole     -     180    
No. & Wire Size     17 - #14     #6.5 RD    
Mean Length Turn    
1983.7 mm (78.1 inch)    
-    
Copper Weight    
106.8 kg (235.5 lb)    

123.4 kg (272 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0074 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1600 Generator

Table 6
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
566.4 mm (22.3 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     2.8 (3-3-3-3-2)     -    
Turns/Pole     -     180    
No. & Wire Size     17 - #14     #6.5 RD    
Mean Length Turn    
1983.7 mm (78.1 inch)    
-    
Copper Weight    
106.8 kg (235.5 lb)    

123.4 kg (272 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0074 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1601 Generator

Table 7
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18.0 inch)    

457.2 mm (18.0 inch)    
Slots     60     -    
Coil Throw     1 - 14     -    
Turns/Coil     2     -    
Turns/Pole     -     180    
No. & Wire Size     20 - #14     #6.5 RD    
Mean Length Turn    
1823.7 mm (71.8 inch)    
-    
Copper Weight    
82.5 kg (181.9 lb)    

106.6 kg (235.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #0     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00446 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1602 Generator

Table 8
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18.0 inch)    

457.2 mm (18.0 inch)    
Slots     60     -    
Coil Throw     1 - 14     -    
Turns/Coil     2     -    
Turns/Pole     -     180    
No. & Wire Size     20 - #14     #6.5 RD    
Mean Length Turn    
1823.7 mm (71.8 inch)    
-    
Copper Weight    
82.5 kg (181.9 lb)    

106.6 kg (235.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #0     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00446 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1603 Generator

Table 9
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18.0 inch)    

457.2 mm (18.0 inch)    
Slots     60     -    
Coil Throw     1 - 14     -    
Turns/Coil     2     -    
Turns/Pole     -     180    
No. & Wire Size     20 - #14     #6.5 RD    
Mean Length Turn    
1823.7 mm (71.8 inch)    
-    
Copper Weight    
82.5 kg (181.9 lb)    

106.6 kg (235.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #0     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00446 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1604 Generator

Table 10
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
566.4 mm (22.3 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.8 (1-2-2-2-2)     -    
Turns/Pole     -     180    
No. & Wire Size     26 - #14     #6.5 RD    
Mean Length Turn    
1983.7 mm (78.1 inch)    
-    
Copper Weight    
105.0 kg (231.5 lb)    

123.4 kg (272.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00319 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     1 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1605 Generator

Table 11
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
566.4 mm (22.3 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.8 (1-2-2-2-2)     -    
Turns/Pole     -     180    
No. & Wire Size     26 - #14     #6.5 RD    
Mean Length Turn    
1983.7 mm (78.1 inch)    
-    
Copper Weight    
105.0 kg (231.5 lb)    

123.4 kg (272.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00319 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-1606 Generator

Table 12
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
566.4 mm (22.3 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.8 (1-2-2-2-2)     -    
Turns/Pole     -     180    
No. & Wire Size     26 - #14     #6.5 RD    
Mean Length Turn    
1983.7 mm (78.1 inch)    
-    
Copper Weight    
105.0 kg (231.5 lb)    

123.4 kg (272.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00319 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     240 Hz    
Exciter Poles     6     16    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 30
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-3375 Generator

Table 13
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
304.8 mm (12.0 inch)    

304.8 mm (12.0 inch)    
Slots     48     -    
Coil Throw     1 - 9     -    
Turns/Coil     3     -    
Turns/Pole     -     130    
No. & Wire Size     Winding #1
8 - #14    
Winding #2
2 - #14
2 - #15    
#8 SQ    
Mean Length Turn    
1186.2 mm (46.7 inch)    
-    
Copper Weight    
37.3 kg (82.3 lb)    

48.3 kg (106.5 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     8 - #2/0     6 - #2/0     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00603 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.015 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 56
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

109-3394 Generator

Table 14
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
198.1 mm (7.8 inch)    

198.1 mm (7.8 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     4.5 (4-5-4-5)     -    
Turns/Pole     -     130    
No. & Wire Size     9 - #15     #8 SQ    
Mean Length Turn    
1028.7 mm (40.5 inch)    
-    
Copper Weight    
29.9 kg (66.0 lb)    

38.1 kg (84.1 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0127 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.811 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     7     -    
No. & Size Wire     1 - #16     2 - #15.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    
-    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

109-3766 Generator

Table 15
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
198.1 mm (7.8 inch)    

198.1 mm (7.8 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     4.5 (4-5-4-5)     -    
Turns/Pole     -     130    
No. & Wire Size     9 - #15     #8 SQ    
Mean Length Turn    
1028.7 mm (40.5 inch)    
-    
Copper Weight    
29.9 kg (66.0 lb)    

38.1 kg (84.1 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0127 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.811 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     120 Hz    
Exciter Poles     6     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    

31.8 mm (1.25 inch)    
Coils/Group     1     2     1    
Slots (Coils)     6     36     24    
Turns (Coils)     150     7     12    
No. & Size Wire     1 - #16     2 - #15.5     2 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    

330.2 mm (13.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    

0.5 kg (1.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     Star    
Line Leads     2 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

109-3768 Generator

Table 16
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
223.5 mm (8.8 inch)    

223.5 mm (8.8 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     4     -    
Turns/Pole     -     130    
No. & Wire Size     8 - #14 and 1 - #15     #8 SQ    
Mean Length Turn    
1079.5 mm (42.5 inch)    
-    
Copper Weight    
34.4 kg (75.9 lb)    

40.6 kg (89.4 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00982 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.828 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     120 Hz    
Exciter Poles     6     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    

31.8 mm (1.25 inch)    
Coils/Group     1     2     1    
Slots (Coils)     6     36     24    
Turns (Coils)     150     7     12    
No. & Size Wire     1 - #16     2 - #15.5     2 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    

330.2 mm (13.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    

0.5 kg (1.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     Star    
Line Leads     2 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

109-3770 Generator

Table 17
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
223.5 mm (8.8 inch)    

223.5 mm (8.8 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     4     -    
Turns/Pole     -     130    
No. & Wire Size     8 - #14 and 1 - #15     #8 SQ    
Mean Length Turn    
1079.5 mm (42.5 inch)    
-    
Copper Weight    
34.4 kg (75.9 lb)    

40.6 kg (89.4 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00982 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.828 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     120 Hz    
Exciter Poles     6     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    

31.8 mm (1.25 inch)    
Coils/Group     1     2     1    
Slots (Coils)     6     36     24    
Turns (Coils)     150     7     12    
No. & Size Wire     1 - #16     2 - #15.5     2 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    

330.2 mm (13.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    

0.5 kg (1.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     Star    
Line Leads     2 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

109-3772 Generator

Table 18
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
254.0 mm (10.0 inch)    

254.0 mm (10.0 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     3.5 (3-4-3-4)     -    
Turns/Pole     -     130    
No. & Wire Size     8 - #13     #8 SQ    
Mean Length Turn    
1165.9 mm (45.9 inch)    
-    
Copper Weight    
36.1 kg (79.5 lb)    

43.5 kg (95.8 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00827 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.909 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     120 Hz    
Exciter Poles     6     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    

31.8 mm (1.25 inch)    
Coils/Group     1     2     1    
Slots (Coils)     6     36     24    
Turns (Coils)     150     7     12    
No. & Size Wire     1 - #16     2 - #15.5     2 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
363.2 mm (14.3 inch)    

325.1 mm (12.8 inch)    

330.2 mm (13.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

2.2 kg (4.8 lb)    

0.5 kg (1.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     Star    
Line Leads     2 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

109-3774 Generator

Table 19
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
276.9 mm (10.9 inch)    

276.9 mm (10.9 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     3.25 (3-3-3-4)     -    
Turns/Pole     -     130    
No. & Wire Size     9 - #14     #8 SQ    
Mean Length Turn    
1231.9 mm (48.5 inch)    
-    
Copper Weight    
31.4 kg (69.3 lb)    

45.6 kg (100.6 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00895 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.961 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     120 Hz    
Exciter Poles     6     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    

31.8 mm (1.25 inch)    
Coils/Group     6     2     1    
Slots (Coils)     6     36     24    
Turns (Coils)     150     8     12    
No. & Size Wire     1 - #16     2 - #16     2 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    

330.2 mm (13.0 inch)    
Copper Weight    
4.1 kg (9.1 lb)    

2.2 kg (4.8 lb)    

0.5 kg (1.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     Star    
Line Leads     2 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 03
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

Caterpillar Information System:

325D and 329D Excavators Swing Bearing - Lubricate
3612 and 3616 Engines Camshaft Timing
345C Excavator and 345C Material Handler Machine System Specifications Travel Motor
3406C Truck Engine Engine Has Early Wear
C15 and C18 Petroleum Generator Sets Generator Set Intended for Stationary Use Only
3612 and 3616 Engines Timing Adjustments for Fuel System
C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Self-Diagnostics
3612 and 3616 Engines Finding the Top Center Position for the No. 1 Piston
797 Off-Highway Truck Power Train Relief Valve (Transmission Lubrication)
P16, P20, P25, P28, P40 and P60 Pulverizers Crushing Arm - Install
3612 and 3616 Engines Engine Rotation
2000/03/01 Be Sure The 163-6108 Timing Control (G3412) And 163-6164 Timing Control (G3408) Is Correctly Installed On Engines Equipped With The CAT Digital Ignition System {1901}
320D Excavator Swing Drive Oil - Change
3406C Truck Engine Engine Misfires, Runs Rough or Is Unstable
2000/04/01 New Water Pump Group Includes Many Improvements {1361}
3612 and 3616 Engines Start Up Procedure
G3516B Engines Electrical Connectors and Functions
320D Excavator Swing Drive Oil Level - Check
3612 and 3616 Engines Crankshaft Position for Fuel Timing and Valve Lash Adjustment
325D and 329D Excavators Swing Gear - Lubricate
3612 and 3616 Engines Fuel Timing
3406C Truck Engine Engine Misfires, Knocks, or Is Unstable (at Idle Only)
G3516B Engines Programming Parameters
3612 and 3616 Engines Fuel Injector Synchronization
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.