UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Caterpillar


IGBT - Test

Usage:

UPSB 125 SEP


NOTICE

Electrostatic discharge can damage integrated circuits or semiconductors if you touch the connector pins. When not in use, keep modules in static shielded bags. Follow these guidelines when you handle modules:

Allow a minimum of 5 minutes for capacitors to discharge.

Touch a grounded object to discharge static potential.

Wear a wrist-strap grounding device.

Do not touch the connector pins.

Do not touch circuit components inside the module.

If available, use a static-safe work station.


Note: The 355-8580 Test Kit is used for this procedure.

Ensure that all lockout/tagout procedures for the site are followed to ensure that power is not applied while the equipment is being serviced.

Personal Protective Equipment (PPE) suitable to the work being performed must be worn when performing maintenance on the UPS.

------ DANGER! ------

High voltage is present. Work on this equipment must be performed by authorized trained personnel. Personnel must be wearing Personal Protective Equipment that meets regulatory requirements to protect the body for the work that is being performed. Failure to use appropriate PPE to protect the body will result in serious personal injury or death.


  1. Remove power from the UPS by following the appropriate shutdown routine.

    After power is removed, wait for 5 minutes before the UPS is opened. This action allows the capacitors to discharge. Ensure that the capacitors are at a zero energy level before performing work.

    ReferenceOperation and Maintenance Manual, SEBU8516, "Single UPS Startup and Shutdown" and "Parallel UPS Startup and Shutdown".




    Illustration 1g02138908

    Power modules

    (1) TESTN boards

    (2) PFC module

    (3) INV/OND module

    (4a) Leg 1

    (4b) Leg 2

    (4c) Leg 3

  1. Plug the TESTN boards (1) into the following IGBT power modules: PFC module (2) and INV/OND module (3) .



    Illustration 2g02138915

    TESTN board

    (5a) LED" HE2"

    (5b) LED" HE1"

    (5c) LED" HE4"

    (5d) LED" HE3"

  1. Verify that power is present for the following:power supply and the IGBTs on each leg (5x). Refer to Illustration 1.

    LED "HE1" (5b) - The power is present on the leg.

    LED "HE2" (5a) - The IGBT command is present on the leg.

    LED "HE3" (5d) - The power is present on the leg.

    LED "HE4" (5c) - The IGBT command is present on the leg.

  1. Verify the status by observing the LEDs. Refer to Table 1.

    Table 1
    UPS Tuner Mode     Step     Status     PFC Power Module     Converter Power Module    
    HE1 HE2 HE3 HE4     HE1     HE2     HE3     HE4    
    Manual Mode
    (Test operation)    
    1     Q1 OFF
    Q4S ON    
    OFF     ON     OFF     ON     OFF     ON     OFF     ON    
    2 Q1 ON
    Q4S ON
    +
    During the AC N Static switch ramp    
    OFF     ON     OFF     ON     OFF     ON     OFF     ON    
    (2) Q1 ON
    Q4S ON
    +
    During the PFC Static switch ramp    
    ON     ON     ON     ON     OFF     ON     OFF     ON    
    Without Manual Mode
    (Normal operation)    
    4     Q1 OFF
    Q4S ON
    +
    UPS Tuner (normal mode)    
    OFF     ON     OFF     ON     OFF     ON     OFF     ON    
    5 Q1 ON
    Q4S ON
    Normal mode    
    ON     ON     ON     ON     OFF     ON     OFF     ON    
    6 Q1 ON
    Q4S ON
    +
    Inverter ON    
    ON     ON     ON     ON     ON     ON     ON     ON    
    ( 2 ) During the PFC Static switch ramp

    Note: Any indication other than listed in Table 1 indicates that there is a problem.

  1. Remove power to the UPS.

  1. Remove the TESTN boards.

Caterpillar Information System:

C9 Industrial Engines Product Lifting
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz IGBT for MUTEN-MUTON Circuit Board - Replace
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz IGBT for DCHEN-DCHON Circuit Board - Replace
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz IGBT for CSNEN-CSNON Circuit Board - Replace
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz IGBT for CSIEN-CSION-CSPEN Circuit Board - Replace
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Component Location
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz General Information
TA19 Transmission Speed Sensor (Transmission Input) - Remove and Install
Cat® Grade Control Depth & Slope for E-Series and F-Series Excavators End User License Agreement
TA19 Transmission Speed Sensor (Transmission Output) - Remove and Install
3516C Generator Sets Fuel Injector - Inspect/Adjust
330F MHPU Mobile Hydraulic Power Unit Machine System Control Valve (Boom Lowering) - Manual
Installation Procedure for 374-5523 Stick Lines Gp on Certain Hydraulic Excavators {5057} Installation Procedure for 374-5523 Stick Lines Gp on Certain Hydraulic Excavators {5057}
TA19 Transmission Pressure Sensor (Transmission Oil) - Remove and Install
146-4080 Digital Multimeter Specification, Testing, and Maintenance Manual{0374, 0599, 0709} 146-4080 Digital Multimeter Specification, Testing, and Maintenance Manual{0374, 0599, 0709}
C9 Industrial Engines Engine Oil and Filter - Change
C9 Industrial Engines Fuel System - Prime
C7 Engines for Caterpillar Built Machines Valve Mechanism
390F Excavator Machine System Bucket Linkage
2011/05/25 New Software Is Available for Certain C13 Industrial Engines {1901, 1920}
Vane Type Hydraulic Pump Identification Guidelines {5055} Vane Type Hydraulic Pump Identification Guidelines {5055}
C9 Industrial Engines Refill Capacities
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Troubleshooting
UPSB125 Uninterruptible Power Supply UPS Battery - 50Hz Configuration - Check
Back to top