Indicator Identification Diagram
Illustration 1 | g00835403 |
520 Control Module (Generator Set) (1) Indicator for engine overspeed (2) Indicator for coolant temperature (3) Indicator for oil pressure (4) Indicator for alarm (5) Automatic start position (6) Programmable indicators (7) Manual start position (8) Engine control switch (ECS) (9) Indicator for engine overcrank (10) Indicator for emergency stop (11) Stop/Reset position |
Note: The software disk that is supplied with the "P808 For Windows" interface contains a Microsoft Word document for the automatic generation of suitable label inserts for the Programmable indicators (6) .
Standard Configuration
Miscellaneous Items
Start Attempts ... 3
Generator Frequency Input Present ... Yes
Nominal Frequency ... 50 Hz
Generator Poles ... 4
Engine Speed Sensor Input Present ... No
Flywheel Teeth ... 118
Nominal RPM ... 1500
Lamp Test EnabIed ... No
Start Button ... None
Stop Button ... None
Safety On Delay Time Termination ... Premature
Load Transfer Mode ... Normal
Preheat Mode ... Normal
Tachometer Full Scale Current ... 0.5 mA
Tachometer Full Scale RPM ... 2500
Electrical Trip EnabIed ... No
Configurable Inputs
Input Channel     | Polarity     | Type     | Activation Time     |
Remote Start     | Close to activate     | -     | -     |
Oil pressure     | Close to activate     | Shutdown     | Activate from safety on     |
Coolant Temperature     | Close to activate     | Shutdown     | Activate from safety on     |
Programmable Input 1     | Close to activate     | Warning     | Always active     |
Programmable Input 2     | Close to activate     | Warning     | Activate from safety on     |
Programmable Input 3     | Close to activate     | Shutdown     | Activate from safety on     |
Programmable Input 4     | Close to activate     | Indication     | Always active     |
Relay Outputs
Output Channel     | Polarity     | Control Source     |
Programmable Output 1     | Energize     | 1 Preheat     |
Programmable Output 2     | Energize     | 18 Common Alarm     |
Programmable Output 3     | Energize     | 4 Load transfer     |
Front Panel Indicators
Indicator     | Polarity     | Control Source     |
1     | Lit     | 29 Programmable IP 1 active     |
2     | Lit     | 30 Programmable IP 2 active     |
3     | Lit     | 31 Programmable IP 3 active     |
4     | Lit     | 32 Programmable IP 4 active     |
5     | Lit     | 25 Remote start present     |
6     | Lit     | 27 Oil Pressure alarm     |
7     | Lit     | 28 Coolant Temp alarm     |
8     | Lit     | 20 Engine Overspeed alarm     |
9     | Lit     | 7 Engine Overcrank alarm     |
10     | Lit     | 21 Emergency Stop alarm     |
11     | Lit     | 18 Common alarm     |
System Timers
Timer     | Mins:secs     |
Remote start delay time     | 0:05     |
Remote stop delay time     | 0:30     |
Cranking time     | 0:10     |
Crank reset time     | 0:10     |
Safety on delay time     | 0:10     |
Warm up time     | 0:05     |
Cooling time     | 0:30     |
Fail to stop time     | 0:30     |
ETS hold time     | 0:00     |
Preheat time     | 0:00     |
Sensor fail delay time     | 0:02     |
Smoke limiting time     | 0:00     |
Smoke limiting ramp time     | 0:00     |
Analogue Levels
Overspeed on alternator frequency ... 57.0 Hz
Overspeed on engine speed sensor ... 1750 RPM
Overspeed overshoot during safety on delay ... 0%
Underspeed on alternator frequency ... 30.0 Hz
Underspeed on engine speed sensor ... 1250 RPM
Crank disconnect on alternator frequency ... 21.0 Hz
Crank disconnect on engine speed sensor ... 600 RPM
Crank disconnect alternator voltage ... 30.0 V
Charge fail voltage ... 8.0 V