UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


System Startup

Usage:

UPS 250 CNM
Note: Refer to Operation and Maintenance Manual, SEBU7464, "Initial Startup Procedure" in this manual before proceeding with this procedure.

Starting the Single Module System (SMS)

  • Single Module System (SMS) with a Bypass Cabinet

  • SMS without a Bypass Cabinet

SMS with a Bypass Cabinet




    Illustration 1g01797996

    Side view of the Bypass Cabinet

    (10) Bypass Switch

    (11) Output Switch

    (12) Input Switch

  1. Close the Output Switch (11) that is located in the Bypass Cabinet. Refer to Illustration 1.



    Illustration 2g01801509

    User Interface Panel on the Flywheel Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the Flywheel Cabinet to the "On-Line" position. Refer to Illustration 2.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.

  1. Verify that the flywheel enters the "On-Line" mode. The LED on the user interface panel lights when the system enters the "On-Line" mode. Refer to Illustration 2.

    The system is ready for operation.

SMS without a Bypass Cabinet

  1. Close the external output circuit breaker that connects the system output to the load of the facility.

  1. Open the external bypass switch.



    Illustration 3g01801509

    User Interface Panel on the Flywheel Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the Flywheel Cabinet to the "On-Line" position. Refer to Illustration 3.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.

  1. Verify that the flywheel enters the "On-Line" mode. The LED on the user interface panel lights when the system enters the "On-Line" mode. Refer to Illustration 3.

    The system is ready for operation.

Starting the Multiple Module System (MMS)

Single Input Without Switches




    Illustration 4g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Close the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 4.

  1. Close the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 4.

  1. Connect the output bus of the system to the load of the facility.



    Illustration 5g01801509

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "On-Line" position. Refer to Illustration 5.



    Illustration 6g01802256

    User Interface Panel on the MMU Cabinet

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Online" position. Refer to Illustration 6.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.




    Illustration 7g00948128

  1. Hit the "Menu" button on the User Interface Panel of the last MMU. Refer to Illustration 7.

  1. Select "Telemetry".

  1. Select "MMU Summary".

  1. Verify that the MMU is in the "Online" mode. The flywheel should be spinning at 7700 rpm and the energy should be at "100%". Perform this procedure for each MMU.

  1. The system is ready for operation.

  1. Verify that the "KVA" and the "KW" values are equal to the load of the facility on the User Interface Panel of each MMU.

Single Input With Three Switches




    Illustration 8g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Close the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 8.

  1. Close the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 8.



    Illustration 9g01802293

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

    (5) Input Isolation Switch

  1. Close the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 9.



    Illustration 10g01801509

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "On-Line" position. Refer to Illustration 10.



    Illustration 11g01802256

    User Interface Panel on the MMU Cabinet

    (2) Keyswitch

  1. Turn the keyswitch (2) on the MMU Cabinet to the "Online" position. Refer to Illustration 11.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.




    Illustration 12g00948128

  1. Hit the "Menu" button on the User Interface Panel of the last MMU. Refer to Illustration 12.

  1. Select "Telemetry".

  1. Select "MMU Summary".

  1. Verify that the MMU is in the "Online" mode. The flywheel should be spinning at 7700 rpm and the energy should be at "100%". Perform this procedure for each MMU.

  1. The system is ready for operation.

  1. Verify that the "KVA" and the "KW" values are equal to the load of the facility on the User Interface Panel of each MMU.

Dual Input Without Switches

  1. Apply facility power to the Bypass Input of the system.

  1. Apply facility power to the input node of the system.



    Illustration 13g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Close the Input Isolation Switches (6) for each MMU that are located in the System Cabinet. Refer to Illustration 13.

  1. Close the Output Isolation Switches (7) for each MMU that are located in the System Cabinet. Refer to Illustration 13.

  1. Connect the output bus of the system to the load of the facility.



    Illustration 14g01801509

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "On-Line" position. Refer to Illustration 14.



    Illustration 15g01802256

    User Interface Panel on the MMU Cabinet

    (2) Keyswitch

  1. Turn the keyswitch (2) on the MMU Cabinet to the "Online" position. Refer to Illustration 15.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.




    Illustration 16g00948128

  1. Hit the "Menu" button on the User Interface Panel of the last MMU. Refer to Illustration 16.

  1. Select "Telemetry".

  1. Select "MMU Summary".

  1. Verify that the MMU is in the "Online" mode. The flywheel should be spinning at 7700 rpm and the energy should be at "100%". Perform this procedure for each MMU.

  1. The system is ready for operation.

  1. Verify that the "KVA" and the "KW" values are equal to the load of the facility on the User Interface Panel of each MMU.

Dual Input With Two Switches




    Illustration 17g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Close the Input Isolation Switches (6) for each MMU that are located in the System Cabinet. Refer to Illustration 17.

  1. Close the Output Isolation Switches (7) for each MMU that are located in the System Cabinet. Refer to Illustration 17.



    Illustration 18g01798373

    System Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

  1. Close the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 18.



    Illustration 19g01801509

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "On-Line" position. Refer to Illustration 19.



    Illustration 20g01802256

    User Interface Panel on the MMU Cabinet

    (2) Keyswitch

  1. Turn the keyswitch (2) on the MMU Cabinet to the "Online" position. Refer to Illustration 20.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.




    Illustration 21g00948128

  1. Hit the "Menu" button on the User Interface Panel of the last MMU. Refer to Illustration 21.

  1. Select "Telemetry".

  1. Select "MMU Summary".

  1. Verify that the MMU is in the "Online" mode. The flywheel should be spinning at 7700 rpm and the energy should be at "100%". Perform this procedure for each MMU.

  1. The system is ready for operation.

  1. Verify that the "KVA" and the "KW" values are equal to the load of the facility on the User Interface Panel of each MMU.

Dual Input With Three Switches




    Illustration 22g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Close the Input Isolation Switch (6) that is located in the System Cabinet. Refer to Illustration 22.

  1. Close the Output Isolation Switch (7) that is located in the System Cabinet. Refer to Illustration 22.



    Illustration 23g01779896

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

    (5) Input Isolation Switch

  1. Close the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 23.



    Illustration 24g01801509

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "On-Line" position. Refer to Illustration 24.



    Illustration 25g01802256

    User Interface Panel on the MMU Cabinet

    (2) Keyswitch

  1. Turn the keyswitch (2) on the MMU Cabinet to the "Online" position. Refer to Illustration 25.

    Note: The system will enter the "Bypassed-Auto Start" mode. The system will begin to charge the flywheel. The system will change to the "On-Line" mode when the flywheel reaches 4000 rpm.




    Illustration 26g00948128

  1. Hit the "Menu" button on the User Interface Panel of the last MMU. Refer to Illustration 26.

  1. Select "Telemetry".

  1. Select "MMU Summary".

  1. Verify that the MMU is in the "Online" mode. The flywheel should be spinning at 7700 rpm and the energy should be at "100%". Perform this procedure for each MMU.

  1. The system is ready for operation.

  1. Verify that the "KVA" and the "KW" values are equal to the load of the facility on the User Interface Panel of each MMU.
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.