UPSB130 Uninterruptible Power Supply Caterpillar


General Hazard Information

Usage:

UPSB 130 XTC

Important Safety Information

To reduce the risk of fire or electric shock, install the UPS in an indoor environment that is free of conductive contaminants. This equipment is intended only for installations in a location that is restricted to qualified personnel.

High voltage is present when the enclosures of the UPS are open. The UPS should only be serviced by personnel that are qualified to work on equipment that contains high voltage.

------ DANGER! ------

Working with electrical circuits is hazardous and exposes personnel to electrical potential. To ensure safe operation, personnel must be trained in proper operating procedures. Bodily contact with electrical potential will cause serious personal injury or death.


Safety of Persons

The following sections contain safety precautions to observe as part of a general accident protection program.

The UPS must be installed in a room with restricted access. Only qualified personnel should have access to the room. A UPS has a battery as an internal power source. The power outlets may be energized even if the UPS is disconnected from the AC power source.

High voltage levels are present within the UPS. The UPS should be opened only by service personnel that are qualified.

------ DANGER! ------

High voltage may be present. Work on this equipment must be performed by authorized trained personnel. Failure to disconnect the power source before performing maintenance or removing modules exposes personnel to electrical potential. Bodily contact with electrical potential will cause serious personal injury or death.


After power is removed, wait for 5 minutes before the UPS is opened. This action allows the capacitors to discharge. Ensure that the capacitors are at a zero energy level before performing work.

Personal Protective Equipment (PPE) suitable to the work being performed must be worn when performing maintenance on the UPS.

------ DANGER! ------

High voltage is present. Work on this equipment must be performed by authorized trained personnel. Personnel must be wearing Personal Protective Equipment that meets regulatory requirements to protect the body for the work that is being performed. Failure to use appropriate PPE to protect the body will result in serious personal injury or death.


High Leakage Current




Illustration 1g02174152

The UPS is subject to high leakage current. The UPS must be connected to an earth ground before the supply is connected.

------ DANGER! ------

Failure to connect the unit to a suitable grounding electrode creates an electrical shock hazard. An electrical shock will result in serious personal injury or death.


Leakage current in a UPS is typically caused by input filters that are designed to protect against voltage surges. Some leakage current is allowed to pass from the input to a ground path or wire that leads to earth ground on the system. If there is no earth ground connected on the system, there is no place for this leakage current to pass.

Battery Precautions

  • Never burn the battery. The battery may explode if the battery is burned.

  • Do not attempt to open the battery. The electrolyte is dangerous for the eyes and skin.

  • Comply with all applicable regulations for the disposal of the battery.

  • The battery must be replaced only by qualified personnel.

ReferenceFor additional precautionary statements when working on or near the batteries, refer to Operation and Maintenance Manual, "Battery Service".

Lockout and Tagout Procedures




Illustration 2g02324673

Ensure that all lockout/tagout procedures for the site are followed. Illustration 2 shows some typical items used to lock or tag the power sources. These items ensure that power is not applied while the equipment is being serviced.

Safety of Equipment

  • Circuit breakers must be installed to protect the UPS. A breaker must be installed upstream of the UPS and downstream of the UPS. The breakers must be easy to access in an emergency.

  • Never install the UPS near liquids or in a damp environment.

  • Never permit a liquid or a foreign body to penetrate the inside of the UPS.

  • Never block the grates that are ventilating the UPS.

  • Never expose the UPS to direct sunlight or to a source of heat.

General Precautions

  • Never operate the UPS if the ambient temperature and relative humidity are higher than the levels that are specified in the documentation.

  • The product must be installed on a surface that is not flammable such as concrete.

  • Circuit breakers must be installed to protect the UPS. A breaker must be installed upstream of the UPS and downstream of the UPS. The breakers must be easy to access in an emergency.

  • Never install the UPS near liquids or in a damp environment.

  • Never permit a liquid or a foreign body to penetrate the inside of the UPS.

  • Never block the grates that are ventilating the UPS.

  • Never expose the UPS to direct sunlight or to a source of heat.

ReferenceRefer to Operation and Maintenance Manual, "UPS Characteristics" for the environmental specifications for the UPS.

Storage

The maximum storage time of the UPS is limited due to the need to recharge the integrated battery. The failure of battery does not constitute a failure of the UPS. The UPS and the batteries are not integrated into each other even though both rely on each other. The UPS may be inoperable because the batteries fail. The installed batteries may not have the same operating conditions of the UPS. Consult the Battery manufacture for specifics of the batteries.

  • If the UPS must be stored prior to installation, the storage area must be dry.

  • The UPS must be stored in an area that is 35° ± 10°C (95° ± 18°F).

  • Energize the UPS on a monthly basis for at least 24 hours when the UPS is stored for extended periods. This action charges the battery. If this action is not performed, the battery may be damaged beyond repair.

Installation and Operations

Install the UPS in compliance with the following:

IEC 60364-4-42 - "Protection Against Thermal Effects"

IEC 60364-4-41 - "Protection Against Electric Shock"

IEC 60364-4-482 - "Electrical Installations of Buildings"

NFC 15-100 - Standard for low voltage that applies only for installations in France

  • The instructions for connecting the UPS that are contained in this manual must be followed in the order that is indicated.

  • Ensure that the specifications that are on the rating plate correspond to the AC power system. Ensure that the ratings correspond to the total power consumption of all of the equipment that will be connected to the UPS.

The UPS is designed for normal operating conditions of altitude, ambient operating temperature, relative humidity, and ambient transport and storage. The UPS will operate correctly under normal conditions, but the battery may fail.

The following operating conditions may justify special measures of design or protection:

  • Smoke, dust, or abrasive dust

  • Humidity, vapor, salt air, bad weather, or dripping

  • Dust and gas mixture that is explosive

  • Extreme temperature variations

  • Improper ventilation

  • Conductive heat or radiant heat from other sources

  • Cooling water that contains acid or impurities that could cause scale, silt, electrolysis, or corrosion of the parts that are exposed to the water

  • Strong electromagnetic fields

  • Levels of radiation that are higher than the natural environment

  • Fungus, insects, or rodents

  • Operating conditions of the battery

Caterpillar Information System:

C13, C15, and C18 Engines for Caterpillar Built Machines Cooling Fan - Calibrate
UPSB130 Uninterruptible Power Supply Regulatory Compliance
CG137-08 and CG137-12 Industrial Engines Gas Pressure Regulator
120M, 12M, 140M and 160M Motor Graders Machine Systems Position Sensor (Articulation)
3508, 3512 and 3516 Generator Set Engines Gear Group (Rear) - Remove and Install
2009/12/03 Gasket for the Water Pump on 3054C, 3054E, C4.4 and C6.6 Engines {1361, 1395, 7555}
Hydraulic Excavator Idler Disassembly and Assembly Procedures {0729, 4159} Hydraulic Excavator Idler Disassembly and Assembly Procedures {0729, 4159}
G3500B Engines Engine Governing - Adjust
3508, 3512 and 3516 Generator Set Engines Balancer Group (Front) - Remove and Install - 3508 Engine
C13 Industrial Engines Engine Oil Pan
C13 Industrial Engines Engine Oil Pan
C13 Industrial Engines Engine Oil Pan
UPSB130 Uninterruptible Power Supply Product Identification
UPSB130 Uninterruptible Power Supply General Information
UPSB130 Uninterruptible Power Supply Component Description
UPSB130 Uninterruptible Power Supply Electrical Specification
UPSB130 Uninterruptible Power Supply Product Location
UPSB130 Uninterruptible Power Supply Single UPS Connection
UPSB130 Uninterruptible Power Supply Parallel UPS Connection
UPSB130 Uninterruptible Power Supply Auxiliary Connection
UPSB130 Uninterruptible Power Supply Shutdown or Power Off Connection
UPSB130 Uninterruptible Power Supply Communication Card Installation
UPSB130 Uninterruptible Power Supply Relay Communication Card Installation
UPSB130 Uninterruptible Power Supply Cable Routing
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.