UPSB130 Uninterruptible Power Supply Caterpillar


Shutdown or Power Off Connection

Usage:

UPSB 130 XTC
Pressing the button for general shutdown causes the UPS to shut down. Shutting down the UPS opens the battery circuit breaker with the opening of the bypass static switch which depends on the personalization settings.

Pressing the "REPO" button also causes the circuit breakers for the normal upstream AC power source and the bypass AC power source to open.

Note: In parallel configurations, there must be a single general button for shutdown with a separate contact for each UPS system.




Illustration 1g02162498

Connection of General Shutdown or Remote Emergency Power OFF (REPO) Terminal Block

  1. Remove the wire jumper from terminal block "XMB06" (7) .

    Note: "XMB06" can serve as the General Shutdown or as the REPO connection point. Breaking this connection will shut down the UPS.

  1. Connect the general shutdown NC contact to terminals 1 and 2 "SELV".

  1. Secure the cable with a cable strap.

Caterpillar Information System:

UPSB130 Uninterruptible Power Supply Auxiliary Connection
UPSB130 Uninterruptible Power Supply Parallel UPS Connection
UPSB130 Uninterruptible Power Supply Single UPS Connection
UPSB130 Uninterruptible Power Supply Product Location
UPSB130 Uninterruptible Power Supply Electrical Specification
UPSB130 Uninterruptible Power Supply Component Description
UPSB130 Uninterruptible Power Supply General Information
UPSB130 Uninterruptible Power Supply Product Identification
UPSB130 Uninterruptible Power Supply General Hazard Information
C13, C15, and C18 Engines for Caterpillar Built Machines Cooling Fan - Calibrate
UPSB130 Uninterruptible Power Supply Regulatory Compliance
CG137-08 and CG137-12 Industrial Engines Gas Pressure Regulator
UPSB130 Uninterruptible Power Supply Communication Card Installation
UPSB130 Uninterruptible Power Supply Relay Communication Card Installation
UPSB130 Uninterruptible Power Supply Cable Routing
2009/11/23 Custom Hydraulic Service Literature Is Being Removed from the Service Information System (SIS) {5050, 7000}
C18 Generator Set Fuel Manifold - Remove
C18 Generator Set Fuel Manifold - Install
UPSB130 Uninterruptible Power Supply Battery Circuit Breaker Installation
UPSB130 Uninterruptible Power Supply Single UPS Startup and Shutdown
UPSB130 Uninterruptible Power Supply Parallel UPS Startup and Shutdown
UPSB130 Uninterruptible Power Supply Mimic Panel Indicator
UPSB130 Uninterruptible Power Supply UPS Personalization
3508, 3512 and 3516 Generator Set Engines Spacer Plate - Remove and Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.