This configuration parameter is the total number of switches that are used. The switches can be individual switches or a multiple rotary switch.
Range | Default |
---|---|
0 to 2 | 0 |
This parameter is a non-programmable parameter that represents the number of possible combinations of switch positions. This parameter is based on the value that is programmed into the "Number of Switch Inputs" parameter.
Mode Selection Switch Input 2 and Mode Selection Switch Input 1
The number of these non-programmable parameters that are visible depends on the value that is programmed into the "Number of Switch Inputs" parameter. "Open" signifies that the switch is in the OFF position. "Ground" signifies that the switch is in the ON position.
If "Yes" is selected on the drop-down menu, the ECM is programmed to use the values in the "Rating Number", "Throttle 1 Droop Percentage", "Throttle 2 Droop Percentage" and "TSC1 Droop Percentage" for the given combination of switch positions.
Values | Default | Factory Password |
---|---|---|
Yes
No |
No | No |
The "High Idle Speed" is the maximum engine rpm.
Minimum | Maximum | Default |
---|---|---|
1800 rpm | 2800 rpm | 2420 rpm |
This parameter is the engine rating that is used by the Electronic Control Module (ECM) for a given combination of switch positions. There is a maximum of four ratings in a flash file.
Range | Default | Factory Password |
---|---|---|
1 to the maximum number of ratings in the currently installed Flash File | 1 | No |
This parameter represents the engine speed that is selected when the mode switch or the mode switches are in a particular position.
Range | Default | Factory Password |
---|---|---|
"Programmed Low Idle" to "Programmed High Idle" | 2100 rpm | No |
This parameter represents a maximum of 112% of the rated speed that is selected when the mode switch or the mode switches are in a particular position.
Range | Default | Factory Password |
---|---|---|
"1800 to 2800 rpm" | 112% of rated speed | No |
This parameter represents the mode of operation of the governor that is installed on the engine.
Range | Default | Factory Password |
---|---|---|
"Min/Max speed (rpm)" or "All Speed" | All Speed | No |
This parameter represents the amount of droop that is applied to the "Throttle 1" input.
Range | Default | Factory Password |
---|---|---|
0 to 10 percent | 5.0% | No |
This parameter represents the amount of droop that is applied to the "Throttle 2" input.
Range | Default | Factory Password |
---|---|---|
0 to 10 percent | 5.0% | No |
This parameter represents the amount of droop that is applied to the "Torque Speed Control 1(TSC1)" input.
Range | Default | Factory Password |
---|---|---|
0 to 10 percent | 5.0% | No |