C15-XQ400 Rental Generator Set Caterpillar


Setup

Usage:

C15 X4R

------ WARNING! ------

Discharge air is hot and could cause property damage and/or personal injury.




Illustration 1g00777368
Typical flow of the exhaust

Do not operate the unit below any overhang.



Illustration 2g00779623
Top view of the unit
Typical clearance around the unit

The unit should have adequate clearance on all sides in order to allow proper air flow. Allow approximately 2 m (6.6 ft) of clearance on all sides.

  • Place the unit in a stable position.

  • Ensure that you use wheel chocks that are suitable for the trailer.

  • Unfasten the tow vehicle before you operate the unit.

------ WARNING! ------

Failure to close doors when the unit is operating can result in doors opening and closing at a high rate of speed. Contact with the doors may cause personal injury or death.




Illustration 3g00778215
Typical chocking of the wheels
Door latches

Close all the doors and ensure that the doors are latched. This will provide maximum performance from the unit.

XQ400 Dual Voltage Distribution Panel



Illustration 4g01221081
XQ400 dual voltage distribution panel

The XQ400 dual voltage distribution panel is equipped with a single adjustable main circuit breaker that is adjustable for 240 volts or 480 volts. The panel is equipped with a manual voltage changeover board and a single main load connection.

XQ400 Single Voltage Distribution Panel



Illustration 5g01221094
XQ400 single voltage distribution panel

The XQ400 single voltage distribution panel is equipped with a single main circuit breaker that is rated at 600 volts and a single main load connection.

Manually Change the Voltage for the Dual Voltage Distribution Panel with the Voltage Changeover Board on XQ400 Generator Sets

------ DANGER! ------

DANGER: Shock/Electrocution Hazard-Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death.


  1. Ensure that the generator set is not operating. Place the handle of the main circuit breaker in the "OFF" position. The "OFF" position is the open position.


    Illustration 6g01221117

  2. Loosen thumb screws (1) and open the door for the load buses (2).


    Illustration 7g01221175

  3. Loosen thumb screws (3) and open the door (4) for the voltage changeover board.


    Illustration 8g01221190

  4. Remove 10 hex nuts and washers (5) that fasten the voltage changeover board (6).


    Illustration 9g01221199

  5. Position the voltage changeover board (6) to the left for low voltage (240V). The position of the voltage changeover board is indicated through the cutout (7). Fasten the voltage changeover board (6) with nuts and washers (5).


    Illustration 10g01221205

  6. Position the voltage changeover board to the right for high voltage (480V). The position of the voltage changeover board is indicated through the cutout (7). Fasten the voltage changeover board (6) with nuts and washers (5).


    Illustration 11g01221175

  7. Close the door for the voltage changeover board (4) and fasten the door with thumb screws (3).


    Illustration 12g01224659

  8. Remove the clear plastic shield on the main circuit breaker (8) which covers the switches for the rotary trip adjustment.


    Illustration 13g01221233

  9. Use a small screwdriver to adjust the switches (9) of the rotary trip adjustment to the correct amperage.

    • "HIGH (480V) - 400 Amp"

    • "LOW (240V) - 800 Amp"

  10. Install the clear plastic shield on the main circuit breaker (8) in order to cover the switches (9) of the rotary trip adjustment.


    Illustration 14g01221117

  11. Proceed with the load connections. Close the door (2) for the load buses and fasten the door (2) with thumb screws (1) after the connections to the load buses have been made.

Load Connections

------ DANGER! ------

DANGER: Shock/Electrocution Hazard-Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death.



NOTICE

Verify the correct load phase rotation with the generator prior to connecting the output power cables.


Note: The procedure for the load connection is illustrated by using a XQ400 dual voltage distribution panel. All of the instructions are typical for both the dual voltage distribution panel and for the single voltage distribution panel.



Illustration 15g01221275
(1) Main circuit breakers
(2) Thumb screws
(3) Bus bars
(4) Ground connection
(5) Receptacles
(6) Connection for remote start/stop
(7) Circuit breakers for receptacles

  1. Ensure that the generator set is not operating. Place main circuit breakers (1) in the "OFF" position. The "OFF" position is the open position.

    Dual voltage distribution panels can have two different voltages. Determine the voltage to use. Use either HIGH (480 V) or LOW (240 V) voltage. Select the applicable receptacles (5) or bus bars (3).

  2. Connect the output power cables to the receptacles (5) or to the bus bars (3).

    If it is necessary to connect the output power cables to the bus bars:

    1. Loosen thumb screws (2) and open the door to the load connections. The shunt trips for the main circuit breaker are activated when the door is opened.

    2. Connect the output power cables to the appropriate bus bars (3).

    3. Close the door to the load connections and secure the door with thumb screws (2). The shunt trips for the main circuit breakers will activate if the door is not properly secured.

    ------ WARNING! ------

    Failure to connect the unit to a suitable grounding electrode can result in electrical shock and may cause injury or death.


  3. Connect the ground connection (4) to a suitable grounding electrode of no more than 25 ohms.

  4. Connect the control wiring (if equipped) for the automatic start/stop to the connection points for the remote start/stop (6).

  5. Close circuit breakers (1) after the connection is made and the engine is running.

Caterpillar Information System:

C27 and C32 Generator Set Engines Vibration Damper and Pulley - Remove and Install
C175 Generator Set Engines Flywheel Housing - Install
330D and 336D Excavators Leaving the Machine
2005/12/12 New Flash File on C18 Marine Engines {7620}
C15 and C18 Industrial Engines Vibration Damper
C15-XQ400 Rental Generator Set Plate Locations and Film Locations
C27 and C32 Generator Set Engines Flywheel Housing - Remove and Install
C7 Urban Transit Bus Engines Monitoring System
2005/11/14 New Aftercoolers are Now Used {1063}
2011/11/16 A New Connecting Rod Is Used in 3500B and 3500C High Displacement Engines {1218}
C27 PET GEN SET Electric Power Generation and C27 KNOCKDOWN K Petroleum Power Train Package Electronic Modular Control Panel 3 (EMCP 3)
C27 and C32 Generator Set Engines Crankshaft Rear Seal - Install
C32 Petroleum Generator Sets Generator Operation
TH31-E61 and TH35-E81 Petroleum Transmissions Lubricant Viscosities
CX35 On-Highway Transmission Oil Filter (Transmission) - Replace
C175 Generator Set Engines Engine Oil Pan - Install
C27 and C32 Generator Set Engines Crankshaft Front Seal - Remove
TH31-E61 and TH35-E81 Petroleum Transmissions Lifting and Tying Down the Transmission
C3.3 and C4.4 Rental Generator Sets Before Towing
C27 and C32 Generator Set Engines Crankshaft Front Seal - Install
2006/01/30 New Oil Drain Tube for the Turbocharger {1052, 1307}
TH31-E61 and TH35-E81 Petroleum Transmissions Capacities (Refill)
C15-XQ400 Rental Generator Set Fan Drive Bearing - Lubricate