Note: Changing the parameters that are protected by factory passwords may cause your Caterpillar warranty to be voided.
Check Programmable Parameters (268-02)
A 268-02 Check Programmable Parameters diagnostic code will be generated if one or more of the programmable parameters has not been programmed. The unprogrammed parameters will be set to default. Certain aspects of the engine's performance and engine monitoring may be affected.
Personality Module Mismatch (253-02)
The ECM stores a code number in permanent memory. This code is called an Interlock Code that is associated with each personality module part number. The Interlock Code does not allow the engine to run if the wrong Personality Module is FLASH downloaded into the ECM.
The ET will warn you if a file is FLASH downloaded that does not match the last file in the ECM. The Interlock Code must be reprogrammed with the ET in order to allow the engine to run with new software. For instructions on reprogramming the Interlock Code, refer to the Special Instruction, SEHS9343. Installing the incorrect software for the ECM may void the Caterpillar warranty. The ECM that is used in the 3500B is different from the ECM that is used in another piece of Caterpillar equipment. The ECM that is used in the two products may appear to be similar. The ECM that is used in the two different products is different. The different ECM(s) can not be interchanged. For example, a 3412E ECM can not be used to replace a 3500B ECM. The Interlock Code can not be reset if the wrong ECM is installed. Installation of the wrong ECM generates the diagnostic code 253-02 Personality Module Mismatch. The fuel injection is disabled in order to prevent the engine from starting. Verify the correct ECM part number by checking the part number that is listed in the Parts Manual or by checking the last two characters of the ECM serial number. The correct ECM serial number ends with CD.
When the engine is rerated, programming the Interlock Code to zero will prompt the ECM. The ECM will read the stored code and the ECM will match the stored code to the new Interlock Code.
Engine Serial Number
The engine serial number should be programmed to match the engine information plate. The serial number is not programmed on a new ECM.
Rated Fuel Position
This parameter is used to set engine power. A Factory Password is required to change this setting.
Minimum     | Default     | Maximum     |
Minimum Rack     | Engine Dependent     | Engine Dependent     |
Low Idle
The parameter defines the lowest rpm level.
Minimum     | Default     | Maximum     |
600 rpm     | 700 rpm     | 1400 rpm     |
Cooldown Speed
This parameter defines the engine speed when the engine shutdown is activated.
Minimum     | Default     | Maximum     |
450 rpm     | 600 rpm     | 1800 rpm     |
Engine Cooldown Duration
This parameter defines engine operation at the cooldown speed. Programming this parameter to 0 will disable this function.
Minimum     | Default     | Maximum     |
0 minutes     | 0 minutes     | 60 minutes     |
Engine Prelube Duration
The parameter sets the amount of time for prelubrication. Programming this parameter to 0 will disable this function.
Minimum     | Default     | Maximum     |
0 seconds     | 0 seconds     | 210 seconds     |
Crank Duration
The crank duration determines when the starting motors will be energized. The crank duration determines when the starting motors will be disengaged. Programming this parameter to 0 will prevent the ECM from engaging the starting motors.
Minimum     | Default     | Maximum     |
0 seconds     | 0 seconds     | 60 seconds     |
Maximum No. Of Cranking Cycles
This parameter is the total number of crank cycles that can be performed.
Minimum     | Default     | Maximum     |
0     | 0     | 10     |
Crank Terminate Speed
This parameter determines when the starting motor will disengage.
Minimum     | Default     | Maximum     |
100 rpm     | 400 rpm     | 500 rpm     |
Air Shutoff
Programming the parameter to "DISABLED" will disable the air shutoff. This parameter should be programmed to "DISABLED" if the function is not being used or installed on this engine. This will prevent air shutoff diagnostics from being logged.
Minimum     | Default     | Maximum     |
Disabled     | Enabled     | Enabled     |
Fuel Ratio Control
The ECM determines the offset value for the Fuel Ratio Control (FRC). The FRC Offset value is used to adjust the fuel ratio control. This minimizes the exhaust smoke when the engine is accelerated.
An offset value of ± 25 kPa (± 4 psi) may be used for adjusting customer preference, fuel quality or other factors that affect engine performance. The default setting is 0.
Note: This parameter may not be available on all applications. This parameter takes the place of the mechanical control for the fuel to air ratio. This parameter improves the engine response with improved emission levels.
Minimum     | Default     | Maximum     |
-25     | 0     | 25     |
Ether Control
Programming this parameter to "DISABLED" will disable the Ether functions. This parameter should be programmed to "DISABLED" if the Ether function is not being used or installed on this engine. This will prevent ether control diagnostic codes from being logged.
Minimum     | Default     | Maximum     |
Disabled     | Disabled     | Enabled     |
"CCM Interface"
The interface will allow you to control the engine from a remote site.
Minimum     | Default     | Maximum     |
Engine Control 1     | Engine Control 1     | Engine Control 8     |
Configuration of Engine Cooling System
The engine can use the separate circuit aftercooler system (SCAC). The engine can use the "jacket water aftercooler system (JWAC)".
Minimum     | Default     | Maximum     |
SCAC     | SCAC     | JWAC     |
Cold Mode Cylinder Cutout
This parameter provides the strategy for the cold mode cylinder cutout.
Minimum     | Default     | Maximum     |
Disabled     | Enabled     | Enabled     |
Fuel Position Multiplier
This parameter decreases the power output from the engine by reducing the fuel. This parameter is used to control the driven equipment. A decrease in engine power does not require a change in the throttle.
Minimum     | Default     | Maximum     |
Disabled     | Enabled     | Enabled     |
Engine Acceleration Rate
This parameter limits the rate of change for the desired engine speed. This parameter may also help reduce smoke when you start the engine.
Minimum     | Default     | Maximum     |
5     | 50     | 1000     |