3500B Industrial Engines Caterpillar


System Configuration Parameters

Usage:

3508B BPX
System Configuration Parameters are parameters that affect emissions, power of the engine, and other features. The parameters are programmed at the factory. In most cases, the parameters do not need to be changed. The System Configuration Parameters must be reprogrammed if an ECM is replaced and/or the engine rating is reprogrammed. System Configuration Parameters do not need to be reprogrammed if the Personality Module is replaced. Proper values for these parameters are available on an Electronic Service Tool. Certain Configuration Parameters are also stamped on the Engine Information Plate.

Note: Changing the parameters that are protected by factory passwords may cause your Caterpillar warranty to be voided.

Check Programmable Parameters (268-02)

A 268-02 Check Programmable Parameters diagnostic code will be generated if one or more of the programmable parameters has not been programmed. The unprogrammed parameters will be set to default. Certain aspects of the engine's performance and engine monitoring may be affected.

Personality Module Mismatch (253-02)

The ECM stores a code number in permanent memory. This code is called an Interlock Code that is associated with each personality module part number. The Interlock Code does not allow the engine to run if the wrong Personality Module is FLASH downloaded into the ECM.

The ET will warn you if a file is FLASH downloaded that does not match the last file in the ECM. The Interlock Code must be reprogrammed with the ET in order to allow the engine to run with new software. For instructions on reprogramming the Interlock Code, refer to the Special Instruction, SEHS9343. Installing the incorrect software for the ECM may void the Caterpillar warranty. The ECM that is used in the 3500B is different from the ECM that is used in another piece of Caterpillar equipment. The ECM that is used in the two products may appear to be similar. The ECM that is used in the two different products is different. The different ECM(s) can not be interchanged. For example, a 3412E ECM can not be used to replace a 3500B ECM. The Interlock Code can not be reset if the wrong ECM is installed. Installation of the wrong ECM generates the diagnostic code 253-02 Personality Module Mismatch. The fuel injection is disabled in order to prevent the engine from starting. Verify the correct ECM part number by checking the part number that is listed in the Parts Manual or by checking the last two characters of the ECM serial number. The correct ECM serial number ends with CD.

When the engine is rerated, programming the Interlock Code to zero will prompt the ECM. The ECM will read the stored code and the ECM will match the stored code to the new Interlock Code.

Engine Serial Number

The engine serial number should be programmed to match the engine information plate. The serial number is not programmed on a new ECM.

Rated Fuel Position

This parameter is used to set engine power. A Factory Password is required to change this setting.

Table 1
Minimum     Default     Maximum    
Minimum Rack     Engine Dependent     Engine Dependent    

Low Idle

The parameter defines the lowest rpm level.

Table 2
Minimum     Default     Maximum    
600 rpm     700 rpm     1400 rpm    

Cooldown Speed

This parameter defines the engine speed when the engine shutdown is activated.

Table 3
Minimum     Default     Maximum    
450 rpm     600 rpm     1800 rpm    

Engine Cooldown Duration

This parameter defines engine operation at the cooldown speed. Programming this parameter to 0 will disable this function.

Table 4
Minimum     Default     Maximum    
0 minutes     0 minutes     60 minutes    

Engine Prelube Duration

The parameter sets the amount of time for prelubrication. Programming this parameter to 0 will disable this function.

Table 5
Minimum     Default     Maximum    
0 seconds     0 seconds     210 seconds    

Crank Duration

The crank duration determines when the starting motors will be energized. The crank duration determines when the starting motors will be disengaged. Programming this parameter to 0 will prevent the ECM from engaging the starting motors.

Table 6
Minimum     Default     Maximum    
0 seconds     0 seconds     60 seconds    

Maximum No. Of Cranking Cycles

This parameter is the total number of crank cycles that can be performed.

Table 7
Minimum     Default     Maximum    
0     0     10    

Crank Terminate Speed

This parameter determines when the starting motor will disengage.

Table 8
Minimum     Default     Maximum    
100 rpm     400 rpm     500 rpm    

Air Shutoff

Programming the parameter to "DISABLED" will disable the air shutoff. This parameter should be programmed to "DISABLED" if the function is not being used or installed on this engine. This will prevent air shutoff diagnostics from being logged.

Table 9
Minimum     Default     Maximum    
Disabled     Enabled     Enabled    

Fuel Ratio Control

The ECM determines the offset value for the Fuel Ratio Control (FRC). The FRC Offset value is used to adjust the fuel ratio control. This minimizes the exhaust smoke when the engine is accelerated.

An offset value of ± 25 kPa (± 4 psi) may be used for adjusting customer preference, fuel quality or other factors that affect engine performance. The default setting is 0.

Note: This parameter may not be available on all applications. This parameter takes the place of the mechanical control for the fuel to air ratio. This parameter improves the engine response with improved emission levels.

Table 10
Minimum     Default     Maximum    
-25     0     25    

Ether Control

Programming this parameter to "DISABLED" will disable the Ether functions. This parameter should be programmed to "DISABLED" if the Ether function is not being used or installed on this engine. This will prevent ether control diagnostic codes from being logged.

Table 11
Minimum     Default     Maximum    
Disabled     Disabled     Enabled    

"CCM Interface"

The interface will allow you to control the engine from a remote site.

Table 12
Minimum     Default     Maximum    
Engine Control 1     Engine Control 1     Engine Control 8    

Configuration of Engine Cooling System

The engine can use the separate circuit aftercooler system (SCAC). The engine can use the "jacket water aftercooler system (JWAC)".

Table 13
Minimum     Default     Maximum    
SCAC     SCAC     JWAC    

Cold Mode Cylinder Cutout

This parameter provides the strategy for the cold mode cylinder cutout.

Table 14
Minimum     Default     Maximum    
Disabled     Enabled     Enabled    

Fuel Position Multiplier

This parameter decreases the power output from the engine by reducing the fuel. This parameter is used to control the driven equipment. A decrease in engine power does not require a change in the throttle.

Table 15
Minimum     Default     Maximum    
Disabled     Enabled     Enabled    

Engine Acceleration Rate

This parameter limits the rate of change for the desired engine speed. This parameter may also help reduce smoke when you start the engine.

Table 16
Minimum     Default     Maximum    
5     50     1000    
Back to top