Specifications
Show/hide table
    | 50 Hertz Units     | 60 Hertz Units     | ||||||
---|---|---|---|---|---|---|---|---|
    | UPS 120     | UPS 250     | UPS 500     | UPS 750     | UPS 150     | UPS 300     | UPS 600     | UPS 900     |
Rating     | 120 kVA 120 kW     |
250 kVA 200 kW     |
500 kVA 400 kW     |
750 kVA 600 kW     |
150 kVA 150 kW     |
300 kVA 240 kW     |
600 kVA 480 kW     |
900 kVA 720 kW     |
Input Voltage     | 380 VAC 400 VAC 415 VAC     |
480 VAC     | ||||||
Output Voltage     | 380 VAC 400 VAC 415 VAC     |
480 VAC     | ||||||
AC Input     | ||||||||
Nominal Amperage     | 189 A 180 A 173 A     |
316 A 300 A 290 A     |
632 A 600 A 580 A     |
948 A 900 A 870 A     |
192 A 183 A 176 A     |
297 A     | 595 A     | 892 A     |
Maximum Amperage (1)     | 230 A     | 425 A 425 A 410 A     |
850 A 850 A 820 A     |
1275 A 1275 A 1230 A     |
320 A     | 440 A     | 880 A     | 1320 A     |
AC Output     | ||||||||
Nominal Amperage     | 183 A 173 A 167 A     |
380 A 361 A 348 A     |
760 A 722 A 694 A     |
1140 A 1083 A 1044 A     |
180 A     | 361 A     | 722 A     | 1084 A     |
10 min max (2)     | 230 A     | 475 A 452 A 435 A     |
950 A 902 A 870 A     |
1425 A 1356 A 1305 A     |
320 A     | 452 A     | 900 A     | 1355 A     |
Typical System Efficiency     | ||||||||
100 Percent load     | 97 Percent     | 96.4 Percent     | 95 Percent     | 97 Percent     | ||||
Heat Rejection Nominal/Maximum     | ||||||||
kW     |     | 7.5/14.1     | 14.9/28.3     | 22.3/45.9     |     | 7.5/15.3     | 14.8/30.6     | 22.3/45.9     |
BTU/Hr. x 1000     | 14/19     | 25.5/48.2     | 50.9/96.4     | 75.9/156.7     | 21.5/38     | 25.3/52.2     | 50.6/104.5     | 75.9/156.7     |
Specifications for Input     | ||||||||
Voltage     | 380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground     | 380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground (3)     | 380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground (3) (4)     | 480 VAC, 3 phase plus ground     | 480 VAC, 3 phase plus ground (3) (5)     | |||
Voltage Range     | +10 Percent / −15 Percent (3) (6)     |
|||||||
Power Factor     | 0.99 at rated load and nominal voltage     |
|||||||
Harmonic Current Distortion     | ||||||||
Linear Load     | < 3 Percent at 100 Percent linear load     | 3 Percent max at 100 Percent resistive load     | < 3 Percent at 100 Percent linear load     | 3 Percent max at 100 Percent resistive load     | ||||
Nonlinear Load     | < 8 Percent at 100 Percent linear load     | <10 Percent with a 100 Percent nonlinear load     | < 8 Percent at 100 Percent linear load     | <10 Percent with a 100 Percent nonlinear load     | ||||
Input Frequency     |     | 50 Hz ± 10 Percent max (6) (7) (8)     |     | 60 Hz ± 10 Percent max (6) (7)     | ||||
Surge     | IEEE 587/ANSI C62.41     | |||||||
Walk-In Time     | Program from 1 second to 10 seconds     | Program from 1 second to 15 seconds     | Program from 1 second to 10 seconds     | |||||
Specifications for Output     | ||||||||
Voltage     |     | 380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground (2)     |     | 480 VAC, 3 phase plus ground (9)     | ||||
Overload Capability (Normal Operation without bypass)     | 1000 Percent for 10 milliseconds     | |||||||
150 Percent for 2 minutes | 500 Percent for 1 second     | 150 Percent for 2 minutes     | 500 Percent for 1 second     | |||||
200 Percent for 30 seconds     |     | 200 Percent for 30 seconds     | ||||||
125 Percent for 10 minutes | ||||||||
Voltage Regulation     | ||||||||
Steady state     | ± 2 Percent of nominal for ± 10 Percent input and balanced or unbalanced load     | |||||||
Flywheel Mode     | ± 2 Percent of nominal for steady-state balanced or unbalanced load     | |||||||
Transient     | ± 5 Percent of nominal for 100 Percent load (10)     | |||||||
Voltage Distortion     | 3 Percent at Full Linear Load     | |||||||
5 Percent at Full Nonlinear Load | ||||||||
Output Frequency     | 50 Hz ±3 Percent (11) (12)     | 60 Hz ±10 Percent (11) (12)     | ||||||
Slew Rate     |     | Maximum of 1 Hz per second     |     | Maximum of 1 Hz per second     | ||||
Environmental Specifications     | ||||||||
Audible Noise     | less than 75 dBA 1 m (3.28 ft)     |
less than 70 dBA 1 m (3.28 ft)     |
less than 75 dBA 1 m (3.28 ft)     |
less than 70 dBA 1 m (3.28 ft)     |
||||
Operating Temp     | 0° C (32° F) to 40 °C (104 °F)     |
−20 °C (−4.0 °F) to 40 °C (104 °F)     |
0° C (32° F) to 40 °C (104 °F)     |
−20 °C (−4.0 °F) to 40 °C (104 °F)     |
||||
Storage Temp     | −25 °C (−13 °F) to 70 °C (158 °F)     |
|||||||
Humidity     | 5 Percent to 95 Percent (13)     | |||||||
Altitude     | Up to 914.4 m (3000 ft) (14)     | |||||||
Emissions and Immunity     | FCC Class A, Subpart J of Part 15     | FCC Class A, Subpart J of Part 15 and EN 50091-2     | FCC Class A, Subpart J of Part 15     | FCC Class A, Subpart J of Part 15 and EN 50091-2     | ||||
Minimum Floor Load Capacity     | 325 pounds per square foot     |
Show/hide table
( 1 ) | Includes recharge |
( 2 ) | Amperage |
( 3 ) | from a grounded wye source |
( 4 ) | Except ± 10 Percent max at 380 VAC |
( 5 ) | 4-wire optional |
( 6 ) | programmable |
( 7 ) | ±3 Percent default |
( 8 ) | Also Available with 60 Hz nominal voltage |
( 9 ) | 4-wire with optional 4-wire input |
( 10 ) | 4 milliseconds recovery time |
( 11 ) | utility synchronized, normal operation |
( 12 ) | nominal ± 0.2 Percent free running |
( 13 ) | non-condensable |
( 14 ) | Derate operating temperature by 1.2 °C for every 305 m (1000 ft) above this limit. |
Show/hide table
480 Volt Systems     | ||
---|---|---|
Percent of Load     | Ride-Through Time     | |
    | UPS 150     | UPS 300/ UPS 600/ UPS 900     |
100 Percent     | 26 seconds     | 13 seconds     |
75 Percent     | 35 seconds     | 17 seconds     |
50 Percent     | 52 seconds     | 25 seconds     |
25 Percent     | 89 seconds     | 50 seconds     |
380 VAC/400 VAC/415 VAC Systems     | ||
Percent of Load     | Ride-Through Time     | |
    | UPS 120     | UPS 250/ UPS 500/ UPS 750     |
100 Percent     | 32 seconds     | 15 seconds     |
75 Percent     | 42 seconds     | 20 seconds     |
50 Percent     | 62 seconds     | 25 seconds     |
25 Percent     | 102 seconds     | 60 seconds     |
Dimensions of the Cabinets
Show/hide table
    | 50 Hertz Units     | 60 Hertz Units     | ||||
---|---|---|---|---|---|---|
UPS 250 | UPS 500     | UPS 750     | UPS 300     | UPS 600     | UPS 900     | |
Physical Dimensions     | ||||||
Height (A)     | 1981.2 mm (78 inch) (1)     |
|||||
Wireway Height (B)     |
452 mm (17.8 inch)     |
|||||
Depth (C)     | 863.6 mm (34.0 inch)     |
|||||
Width (D)     | 3226 mm (127 inch)     |
4318 mm (170 inch)     |
5410 mm (213 inch)     |
3226 mm (127 inch)     |
4318 mm (170 inch)     |
5410 mm (213 inch)     |
Weight     | 3280 kg (7230 lb)     |
5322 kg (11730 lb)     |
7364 kg (16230 lb)     |
3017 kg (6650 lb)     |
5059 kg (11150 lb)     |
7101 kg (15650 lb)     |
Access for Cable     | Top or Bottom     |
Show/hide table
    | 50 Hertz Units     | 60 Hertz Units     | ||||
---|---|---|---|---|---|---|
UPS 250 (N+1 Option) | UPS 500 (N+1 Option)     | UPS 750 (N+1 Option)     | UPS 300 (N+1 Option)     | UPS 600 (N+1 Option)     | UPS 900 (N+1 Option)     | |
Physical Dimensions     | ||||||
Height (A)     | 1981.2 mm (78 inch) (1)     |
|||||
Wireway Height (B)     |
452 mm (17.8 inch)     |
|||||
Depth (C)     | 863.6 mm (34.0 inch)     |
|||||
Width (D)     | 4318 mm (170 inch)     |
5410 mm (213 inch)     |
6502 mm (256 inch)     |
4318 mm (170 inch)     |
5410 mm (213 inch)     |
6502 mm (256 inch)     |
Weight     | 5322 kg (11730 lb)     |
7364 kg (16230 lb)     |
9406 kg (20737 lb)     |
5059 kg (11150 lb)     |
7101 kg (15650 lb)     |
9406 kg (20737 lb)     |
Access for Cable     | Top or Bottom     |
The UPS 250 (Expandable) and the UPS 300 (Expandable)
Show/hide table
Illustration 1 | g01778284 |
The UPS 500 and the UPS 600
Show/hide table
Illustration 2 | g01778294 |
The UPS 750 and the UPS 900
Show/hide table
Illustration 3 | g01778295 |
The UPS 250 (Expandable) (N+1 Option) and the UPS 300 (Expandable) (N+1 Option)
Show/hide table
Illustration 4 | g01778294 |
The UPS 500 (N+1 Option) and the UPS 600 (N+1 Option)
Show/hide table
Illustration 5 | g01778295 |
The UPS 750 (N+1 Option) and the UPS 900 (N+1 Option)
Show/hide table
Illustration 6 | g01778297 |
Caterpillar Information System:
3054 and 3056 Marine Generator Sets Engine Oil and Filter - Change
G3406 Engine Ignition System
3126E On-highway Engine System Configuration Parameters
G3406 Engine Exhaust Bypass Valve
C-10, C-12, C-15 and C-16 Industrial Engines Warning Lamp Circuit - Test
G3304 and G3306 Engines Lubrication
G3304 and G3306 Engines Pressure Regulating Valve
UPS 250 and UPS 300 Uninterruptible Power Supplies Site Preparation
3054, 3054B and 3056 Marine Engines Engine Oil Level - Check
G3304 and G3306 Engines Vibration Damper - Check
3054, 3054B and 3056 Marine Engines Engine Air Cleaner Element - Clean/Replace
C-10, C-12, C-15 and C-16 Industrial Engines Maintenance Due Lamp Circuit - Test
G3304 and G3306 Engines Cylinder Block
C-10, C-12, C-15 and C-16 Industrial Engines Diagnostic Lamp Circuit - Test
3054 and 3056 Marine Generator Sets Fuel System Primary Filter (Water Separator) Element - Replace
C7 and C9 On-Highway Engines Engine Misfires, Runs Rough or Is Unstable
G3406 Engine Visual Inspection
G3304 and G3306 Engines Testing the Cooling System
3054, 3054B and 3056 Marine Engines Vibration Damper and Pulley - Remove and Install
G3406 Engine Governor - Adjust
3054, 3054B and 3056 Marine Engines Sea Water Strainer - Clean/Inspect
G3500 Engines Restriction of Air Inlet and Exhaust
3054 and 3056 Marine Generator Set Engines Rocker Arm and Shaft - Remove
3054, 3054B and 3056 Marine Engines Valve Mechanism Cover - Remove and Install - 3056 Engine