UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


Specifications

Usage:

UPS 250 CNM

Table 1
    50 Hertz Units     60 Hertz Units    
    UPS 120     UPS 250     UPS 500     UPS 750     UPS 150     UPS 300     UPS 600     UPS 900    
Rating     120 kVA
120 kW    
250 kVA
200 kW    
500 kVA
400 kW    
750 kVA
600 kW    
150 kVA
150 kW    
300 kVA
240 kW    
600 kVA
480 kW    
900 kVA
720 kW    
Input Voltage     380 VAC
400 VAC
415 VAC    
480 VAC    
Output Voltage     380 VAC
400 VAC
415 VAC    
480 VAC    
AC Input    
Nominal Amperage     189 A
180 A
173 A    
316 A
300 A
290 A    
632 A
600 A
580 A    
948 A
900 A
870 A    
192 A
183 A
176 A    
297 A     595 A     892 A    
Maximum Amperage (1)     230 A     425 A
425 A
410 A    
850 A
850 A
820 A    
1275 A
1275 A
1230 A    
320 A     440 A     880 A     1320 A    
AC Output    
Nominal Amperage     183 A
173 A
167 A    
380 A
361 A
348 A    
760 A
722 A
694 A    
1140 A
1083 A
1044 A    
180 A     361 A     722 A     1084 A    
10 min max (2)     230 A     475 A
452 A
435 A    
950 A
902 A
870 A    
1425 A
1356 A
1305 A    
320 A     452 A     900 A     1355 A    
Typical System Efficiency    
100 Percent load     97 Percent     96.4 Percent     95 Percent     97 Percent    
Heat Rejection Nominal/Maximum    
kW         7.5/14.1     14.9/28.3     22.3/45.9         7.5/15.3     14.8/30.6     22.3/45.9    
BTU/Hr. x 1000     14/19     25.5/48.2     50.9/96.4     75.9/156.7     21.5/38     25.3/52.2     50.6/104.5     75.9/156.7    
Specifications for Input    
Voltage     380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground     380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground (3)     380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground (3) (4)     480 VAC, 3 phase plus ground     480 VAC, 3 phase plus ground (3) (5)    
Voltage Range    
+10 Percent / −15 Percent (3) (6)    
Power Factor    
0.99 at rated load and nominal voltage
   
Harmonic Current Distortion    
Linear Load     < 3 Percent at 100 Percent linear load     3 Percent max at 100 Percent resistive load     < 3 Percent at 100 Percent linear load     3 Percent max at 100 Percent resistive load    
Nonlinear Load     < 8 Percent at 100 Percent linear load     <10 Percent with a 100 Percent nonlinear load     < 8 Percent at 100 Percent linear load     <10 Percent with a 100 Percent nonlinear load    
Input Frequency         50 Hz ± 10 Percent max (6) (7) (8)         60 Hz ± 10 Percent max (6) (7)    
Surge     IEEE 587/ANSI C62.41    
Walk-In Time     Program from 1 second to 10 seconds     Program from 1 second to 15 seconds     Program from 1 second to 10 seconds    
Specifications for Output    
Voltage         380 VAC, 400 VAC, 415 VAC, 3 phase plus neutral and ground (2)         480 VAC, 3 phase plus ground (9)    
Overload Capability (Normal Operation without bypass)     1000 Percent for 10 milliseconds    
150 Percent for 2 minutes 500 Percent for 1 second     150 Percent for 2 minutes     500 Percent for 1 second    
200 Percent for 30 seconds         200 Percent for 30 seconds    
125 Percent for 10 minutes
Voltage Regulation    
Steady state     ± 2 Percent of nominal for ± 10 Percent input and balanced or unbalanced load    
Flywheel Mode     ± 2 Percent of nominal for steady-state balanced or unbalanced load    
Transient     ± 5 Percent of nominal for 100 Percent load (10)    
Voltage Distortion     3 Percent at Full Linear Load    
5 Percent at Full Nonlinear Load
Output Frequency     50 Hz ±3 Percent (11) (12)     60 Hz ±10 Percent (11) (12)    
Slew Rate         Maximum of 1 Hz per second         Maximum of 1 Hz per second    
Environmental Specifications    
Audible Noise     less than 75 dBA
1 m (3.28 ft)    
less than 70 dBA
1 m (3.28 ft)    
less than 75 dBA
1 m (3.28 ft)    
less than 70 dBA
1 m (3.28 ft)    
Operating Temp    
0° C (32° F) to
40 °C (104 °F)    

−20 °C (−4.0 °F) to
40 °C (104 °F)    

0° C (32° F) to
40 °C (104 °F)    

−20 °C (−4.0 °F) to
40 °C (104 °F)    
Storage Temp    
−25 °C (−13 °F) to
70 °C (158 °F)    
Humidity     5 Percent to 95 Percent (13)    
Altitude     Up to 914.4 m (3000 ft) (14)    
Emissions and Immunity     FCC Class A, Subpart J of Part 15     FCC Class A, Subpart J of Part 15 and EN 50091-2     FCC Class A, Subpart J of Part 15     FCC Class A, Subpart J of Part 15 and EN 50091-2    
Minimum Floor Load Capacity     325 pounds per square foot    
( 1 ) Includes recharge
( 2 ) Amperage
( 3 ) from a grounded wye source
( 4 ) Except ± 10 Percent max at 380 VAC
( 5 ) 4-wire optional
( 6 ) programmable
( 7 ) ±3 Percent default
( 8 ) Also Available with 60 Hz nominal voltage
( 9 ) 4-wire with optional 4-wire input
( 10 ) 4 milliseconds recovery time
( 11 ) utility synchronized, normal operation
( 12 ) nominal ± 0.2 Percent free running
( 13 ) non-condensable
( 14 ) Derate operating temperature by 1.2 °C for every 305 m (1000 ft) above this limit.

Table 2
480 Volt Systems    
Percent of Load     Ride-Through Time    
    UPS 150     UPS 300/ UPS 600/ UPS 900    
100 Percent     26 seconds     13 seconds    
75 Percent     35 seconds     17 seconds    
50 Percent     52 seconds     25 seconds    
25 Percent     89 seconds     50 seconds    
380 VAC/400 VAC/415 VAC Systems    
Percent of Load     Ride-Through Time    
    UPS 120     UPS 250/ UPS 500/ UPS 750    
100 Percent     32 seconds     15 seconds    
75 Percent     42 seconds     20 seconds    
50 Percent     62 seconds     25 seconds    
25 Percent     102 seconds     60 seconds    

Dimensions of the Cabinets

Table 3
    50 Hertz Units     60 Hertz Units    
UPS 250 UPS 500     UPS 750     UPS 300     UPS 600     UPS 900    
Physical Dimensions    
Height (A)    
1981.2 mm (78 inch) (1)    
Wireway
Height (B)    

452 mm (17.8 inch)
   
Depth (C)    
863.6 mm (34.0 inch)    
Width (D)    
3226 mm (127 inch)    

4318 mm (170 inch)    

5410 mm (213 inch)    

3226 mm (127 inch)    

4318 mm (170 inch)    

5410 mm (213 inch)    
Weight    
3280 kg (7230 lb)    

5322 kg (11730 lb)    

7364 kg (16230 lb)    

3017 kg (6650 lb)    

5059 kg (11150 lb)    

7101 kg (15650 lb)    
Access for Cable     Top or Bottom    

Table 4
    50 Hertz Units     60 Hertz Units    
UPS 250 (N+1 Option) UPS 500 (N+1 Option)     UPS 750 (N+1 Option)     UPS 300 (N+1 Option)     UPS 600 (N+1 Option)     UPS 900 (N+1 Option)    
Physical Dimensions    
Height (A)    
1981.2 mm (78 inch) (1)    
Wireway
Height (B)    

452 mm (17.8 inch)
   
Depth (C)    
863.6 mm (34.0 inch)    
Width (D)    
4318 mm (170 inch)    

5410 mm (213 inch)    

6502 mm (256 inch)    

4318 mm (170 inch)    

5410 mm (213 inch)    

6502 mm (256 inch)    
Weight    
5322 kg (11730 lb)    

7364 kg (16230 lb)    

9406 kg (20737 lb)    

5059 kg (11150 lb)    

7101 kg (15650 lb)    

9406 kg (20737 lb)    
Access for Cable     Top or Bottom    

The UPS 250 (Expandable) and the UPS 300 (Expandable)




Illustration 1g01778284

The UPS 500 and the UPS 600




Illustration 2g01778294

The UPS 750 and the UPS 900




Illustration 3g01778295

The UPS 250 (Expandable) (N+1 Option) and the UPS 300 (Expandable) (N+1 Option)




Illustration 4g01778294

The UPS 500 (N+1 Option) and the UPS 600 (N+1 Option)




Illustration 5g01778295

The UPS 750 (N+1 Option) and the UPS 900 (N+1 Option)




Illustration 6g01778297