Removal Procedure
Required Tools     | |||
---|---|---|---|
Tool     | Part Number     | Part Description     | Qty     |
A     | 9U-5103     | Socket (Slotted)     | 1     |
NOTICE |
---|
Keep all parts clean from contaminants. Contaminants may cause rapid wear and shortened component life. |
NOTICE |
---|
Care must be taken to ensure that fluids are contained during performance of inspection, maintenance, testing, adjusting and repair of the product. Be prepared to collect the fluid with suitable containers before opening any compartment or disassembling any component containing fluids. Refer to Special Publication, NENG2500, "Caterpillar Tools and Shop Products Guide" for tools and supplies suitable to collect and contain fluids on Caterpillar products. Dispose of all fluids according to local regulations and mandates. |
- Drain the level of the coolant below the coolant temperature sensor. Drain the coolant into a suitable container for storage or disposal.
Illustration 1 | g00518087 |
- Disconnect harness assembly (2) from coolant temperature sensor (1) .
- Remove coolant temperature sensor (1) with Tooling (A) .
Installation Procedure
Required Tools     | |||
---|---|---|---|
Tool     | Part Number     | Part Description     | Qty     |
A     | 9U-5103     | Socket (Slotted)     | 1     |
NOTICE |
---|
Keep all parts clean from contaminants. Contaminants may cause rapid wear and shortened component life. |
- Install coolant temperature sensor (1) with Tooling (A). Tighten coolant temperature sensor (1) to a torque of 20 ± 3 N·m (15 ± 2 lb ft).
Illustration 2 | g00518087 |
- Connect harness assembly (2) to coolant temperature sensor (1) .
- Fill the cooling system with coolant to the correct level. Refer to the Operation and Maintenance Manual for the correct procedure.