SR4 and SR4B Electric Power Generation Rewind Data Caterpillar


Winding Data for 5N-9081 Generator through 5N-9432 Generator

Usage:

SR4B 1BN

5N-9081 Generator

Table 1
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM WOUND)    
ROTOR
(FORM WOUND)    
Stack Height    
152.4 mm (6.0 inch)    

152.4 mm (6.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     5.6 (6,6,4,6,6)     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     6 - #15     1 - #17     -    
Mean Length Turn    
934.7 mm (36.8 inch)    
-     -    
Copper Weight    
29.2 kg (64.3 lb)    

438.1 kg (965.9 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #4     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.025 ohms     -     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.56 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     105     6    
No. & Size Wire     1 - #15     2 - #14.5    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn (Calc.)    
365.8 mm (14.4 inch)    

304.8 mm (12.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

3.4 kg (7.5 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14 -
965.2 mm (38.0 inch)    
#10 -
152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-9082 Generator

Table 2
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
228.6 mm (9.0 inch)    

228.6 mm (9.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     3.4(3,4,3,4,3)     -     -    
Turns/Pole     -     96     -    
No. & Wire Size     6 - #15     1 - #9     -    
Mean Length Turn    
960.1 mm (37.8 inch)    
-     -    
Copper Weight    
18.6 kg (40.95 lb)    

18.2 kg (40.04 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #4     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0148 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.80 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     160     9    
No. & Size Wire     1 - #16.5     1 - #14    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

113.3 mm (4.46 inch)    

254.0 mm (10.0 inch)    
Copper Weight    
2.7 kg (6.0 lb)    

1.5 kg (3.4 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

914.4 mm (36.0 inch)    
#10

139.7 mm (5.5 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

5N-9083 Generator

Table 3
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
203.2 mm (8.0 inch)    

203.2 mm (8.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 14     -     -    
Turns/Coil     3.4(4,3,3,3,4)     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     8 - #14     1 - #7     -    
Mean Length Turn    
1135.4 mm (44.7 inch)    
-     -    
Copper Weight    
34.9 kg (77.0 lb)    

34.2 kg (75.4 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #6     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.01 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.63 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     95     6    
No. & Size Wire     1 - #14.5     2 - #14.5    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

365.8 mm (14.4 inch)    

304.8 mm (12.0 inch)    
Copper Weight    
3.9 kg (8.7 lb)    

3.4 kg (7.5 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-9084 Generator

Table 4
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
152.4 mm (6.0 inch)    

152.4 mm (6.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     5     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     7 - #15     1 - #7     -    
Mean Length Turn    
934.7 mm (36.8 inch)    
-     -    
Copper Weight    
29.3 kg (64.7 lb)    

29.9 kg (65.9 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     20 - #6     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.01 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.63 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     95     6    
No. & Size Wire     1 - #14.5     2 - #14.5    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

365.8 mm (14.4 inch)    

304.8 mm (12.0 inch)    
Copper Weight    
3.9 kg (8.7 lb)    

3.4 kg (7.5 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-9085 Generator

Table 5
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
228.6 mm (9.0 inch)    

228.6 mm (9.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     5     -     -    
Turns/Pole     -     96     -    
No. & Wire Size     5 - #15     1 - #9     -    
Mean Length Turn    
960.1 mm (37.8 inch)    
-     -    
Copper Weight    
17.2 kg (37.98 lb)    

18.2 kg (40.04 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #6     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.033 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.80 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     160     9    
No. & Size Wire     1 - #16.5     1 - #14    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

113.3 mm (4.46 inch)    

254.0 mm (10.0 inch)    
Copper Weight    
2.7 kg (6.0 lb)    

1.5 kg (3.4 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

914.4 mm (36.0 inch)    
#10

139.7 mm (5.5 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #05
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).

5N-9086 Generator

Table 6
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
203.2 mm (8.0 inch)    

203.2 mm (8.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     4.65(4,4,5,5,5)     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     7 - #15     1 - #7     -    
Mean Length Turn    
1036.3 mm (40.8 inch)    
-     -    
Copper Weight    
27.2 kg (60.0 lb)    

34.2 kg (75.4 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #4     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0192 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.630 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     105     6    
No. & Size Wire     1 - #15     2 - #14.5    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

365.8 mm (14.4 inch)    

304.8 mm (12.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

3.4 kg (7.5 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #05
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).

5N-9087 Generator

Table 7
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
152.4 mm (6.0 inch)    

152.4 mm (6.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     7     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     6 - #16     1 - #7     -    
Mean Length Turn    
934.7 mm (36.8 inch)    
-     -    
Copper Weight    
27.9 kg (61.6 lb)    

29.9 kg (65.9 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #6     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.0366 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.56 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     105     6    
No. & Size Wire     1 - #15     2 - #14.5    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

365.8 mm (14.4 inch)    

304.8 mm (12.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

3.4 kg (7.5 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).

5N-9088 Generator

Table 8
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
228.6 mm (9.0 inch)    

228.6 mm (9.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     4     -     -    
Turns/Pole     -     96     -    
No. & Wire Size     5 - #15     1 - #9     -    
Mean Length Turn    
960.1 mm (37.8 inch)    
-     -    
Copper Weight    
17.2 kg (37.98 lb)    

18.2 kg (40.04 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #6     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.021 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.80 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     160     9    
No. & Size Wire     1 - #16.5     1 - #14    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

113.3 mm (4.46 inch)    

254.0 mm (10.0 inch)    
Copper Weight    
2.7 kg (6.0 lb)    

1.5 kg (3.4 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

914.4 mm (36.0 inch)    
#10

139.7 mm (5.5 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram E

5N-9089 Generator

Table 9
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
203.2 mm (8.0 inch)    

203.2 mm (8.0 inch)    
-    
Slots     60     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     3.6(3,3,4,4,4)     -     -    
Turns/Pole     -     110     -    
No. & Wire Size     7 - #14     1 - #7     -    
Mean Length Turn    
1036.3 mm (40.8 inch)    
-     -    
Copper Weight    
30.5 kg (67.2 lb)    

442.4 kg (975.4 lb)    
-    
Inside Connection (1)     4/2 Parallel Star     4 in Series     -    
Line Leads (No. & Size)     10 - #2     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
0.012 ohms     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     0.63 ohms     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
76.2 mm (3.0 inch)    

76.2 mm (3.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     105     6    
No. & Size Wire     1 - #15     2 - #14.5    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

365.8 mm (14.4 inch)    

304.8 mm (12.0 inch)    
Copper Weight    
3.9 kg (8.5 lb)    

3.4 kg (7.5 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #02
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

5N-9432 Generator

Table 10
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR
(RANDOM
WOUND)    
ROTOR
(FORM
WOUND)    
Stack Height    
424.2 mm (16.7 inch)    

431.8 mm (17.0 inch)    
-    
Slots     54 (1)     -     -    
Coil Throw     1 - 12     -     -    
Turns/Coil     1     -     -    
Turns/Pole     -     160     -    
No. & Wire Size     30 - #13     1 - #7 sq     -    
Mean Length Turn    
1648.5 mm (64.9 inch)    
-     -    
Copper Weight    
64.2 kg (141.5 lb)    

98.4744 kg (217.1 lb)    
-    
Inside Connection (1)     4 in Series     4 in Series     -    
Line Leads (No. & Size)     20 - #00     -     -    
Terminal bolt size     3/8 inch     -     -    
Low Voltage connected line
resistance at 25 ° C (77 ° F)    
.0131     -     -    
Field lead resistance at
25 ° C (77 ° F)    
-     1.17     -    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)    
Stack Length    
127.0000 mm (5.0 inch)    

127.0000 mm (5.0 inch)    
Coils/Group     1     2    
Slots (Coils)     6     36    
Turns (Coils)     250     6    
No. & Size Wire     1 - #18     2 - #15    
Coil Throw     1 - 2     1 - 6    
Mean Length Turn
(Calculated)    

464.8 mm (18.3 inch)    

406.4 mm (16.0 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (5.9 lb)    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star    
Line Leads     #14

965.2 mm (38.0 inch)    
#10

152.4 mm (6.0 inch)    
( 1 ) Wind 6 coil groups with 4 coils per group, wind 6 coil groups with 5 coils per group. Put coil groups in stator (4,5,4,5-etc).
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #36
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram H

Note: Wires 20, 22, and 24 are brought out as tap connections between the 9th and 10th coil (9 turns from T0).

Caterpillar Information System:

140H and 160H Motor Graders Engine Oil and Filter - Change
24H Motor Grader Fuel Tank Water and Sediment - Drain
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0498 - FMI 06
525B Wheel Skidder and 535B Wheel Skidder Power Train Differential Pinion Preload - Adjust
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0498 - FMI 05
980G Wheel Loader, 824G Wheel Dozer, 825G Soil Compactor and 826G Landfill Compactor Implement Electronic Control System MID 082 - CID 0498 - FMI 03
CS-431C, CP-433C and CS-433C Vibratory Compactors Propel System Flushing Valve (Drum Propel Motor) - Test
140H and 160H Motor Graders Engine Oil Level - Check
2000/05/01 The VIMSpc99 Software Version 1.1.7a Is Now Available {7601}
2000/05/01 The Recommended Setting for the Deadband Has Been Changed in order to Reduce Movement of the Slope Control {5645, 7220}
10-20B Extend-A-Mat<COMP-BREAK TAGNAME=cp850>©<COMP-RESUME> Screed Burner System
24H Motor Grader Fuel System - Prime
776D, 777D and 777D HAA Off-Highway Trucks Machine Systems Control Valve (Hoist) - Assemble
24H Motor Grader Fuses - Replace
776D, 777D and 777D HAA Off-Highway Trucks Machine Systems Control Valve (Hoist) - Install
12H Motor Grader Engine Oil and Filter - Change
2000/05/01 Setting the Ramp Time {5645, 7220}
525B Wheel Skidder and 535B Wheel Skidder Power Train Differential Backlash and Bearings - Adjust
CS-431C, CP-433C and CS-433C Vibratory Compactors Auxiliary Hydraulic System Metering Pump (Steering)
2001/12/10 Correction to Hydraulic Schematic {5050}
69D and 769D Off-Highway Trucks and 771D Quarry Truck Machine Systems Accelerator Control - Remove and Install
24H Motor Grader Hydraulic System Oil - Change
2000/05/01 New Asphalt Deflector Kit {6630, 6631, 6640}
776D, 777D and 777D HAA Off-Highway Trucks Machine Systems Regulator (Power Window) - Remove and Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.