MID 039 - Machine Control Module (MCM)
CID 3244 - Fire Suppression Relay
FMI 03 - Voltage Above Normal
MID 039 CID 3244 FMI 03 appears when the Input/Output Module (I/O Module) has determined the Remote Fire Suppression Activation Relay voltage is above normal.
Illustration 1 | g03815018 |
NOTICE |
---|
Before performing any testing or diagnosis of the remote fire suppression activation, disconnect the fire suppression system from the autonomy cabinet. Failure to do so may result in inadvertent activation of the fire suppression system. |
Test Step 1. CHECK THE ENERGIZE CIRCUIT OF THE RELAY FOR A SHORT TO THE +BATTERY CIRCUIT
- Turn the keyswitch and battery disconnect switch to the OFF position.
- Disconnect the Remote Fire Suppression Activation Relay (R9) from the Relay Panel. Disconnect the machine harness connectors J1 and J2 from the Input/Output Module (I/O Module).
- At the machine harness connector J1, measure the resistance from contact J1-66 (wire 811-GY(Grey)) to all J1 and J2 contacts that are connected to +battery.
Expected Result:
Each resistance measurement is greater than 5000 ohms.
Results:
- OK - Each resistance measurement is greater than 5000 ohms. The machine harness is correct. Proceed to Test Step 2
- NOT OK - Each resistance measurement is not greater than 5000 ohms. There is a short in the machine harness. The short is between J1-66 (wire 811-GY(Grey)) and the circuit that has a low resistance measurement.
Repair: Repair the machine harness or replace the machine harness.
STOP
Test Step 2. CHECK IF THE DIAGNOSTIC CODE IS STILL ACTIVE
- The keyswitch and battery disconnect switch remain in the OFF position.
- Inspect the contacts of the harness connectors that are used in the relay circuit. Ensure that the contacts are secure. Clean all of the contacts in the harness connectors.
- Reconnect all harness connectors.
- Turn the disconnect switch and the keyswitch to the ON position.
- Operate the machine.
- Determine if the diagnostic code is active.
Expected Result:
The diagnostic code is active.
Results:
- YES - CID 3244 FMI 03 is active.
Repair: Repeat this procedure. If the problem remains, replace the R9 relay . After the relay is replaced, repeat this Test Step again. If the diagnostic code is still active, the I/O Module may be faulty. However, I/O Module failure is unlikely. Exit this procedure and perform this procedure again. If the cause of the diagnostic code is not found, replace the ECM. Refer to Testing and Adjusting, KENR8394, "Electronic Control Module (ECM) – Replace".
STOP
- NO - CID 3244 FMI 03 is not active. The problem does not exist at this time.
Repair: The initial diagnostic code was probably caused by a poor electrical connection or a short at one of the harness connectors that was disconnected and reconnected. Resume normal machine operation.
STOP