Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


GSC CID 0442 - FMI 12

Usage:

C32 SXC
Conditions Which Generate This Code:

The GSC+P uses the Generator Fault Relay (GFR) in order to activate the circuit breaker for the shunt trip coil during a shutdown fault. The GFR is located within the relay module. The circuit breaker is located in the generator housing.

Note: Whenever the GSC+P activates or the GSC+P attempts to activate the GFR, "K2" is shown on the lower display. When the GFR is not activated, "K2" is not shown.

The possible cause of a CID 0442 FMI 12 is an open coil or a shorted coil of the GFR.

The system response to this diagnostic code is listed below.

  • When a CID 0442 FMI 12 occurs and the GFR is activated, the diagnostic code will not have an effect on the system. The system is not affected because the circuit breaker is already open and shutdown mode is functioning. The generator is already off-line.

  • If a CID 0442 FMI 12 occurs and the GFR is not activated, the GFR cannot activate the shunt trip coil of the circuit breaker when a shutdown fault occurs.

The GSC+P treats a CID 0442 FMI 12 as an alarm fault. Active alarm faults are shown on the display when the "Alarm Codes" key is pressed. The ECS must be in any position except the OFF/RESET position. Clear the diagnostic code from the fault log after troubleshooting is complete.

This troubleshooting procedure is for an active CID 0442 FMI 12 or the troubleshooting procedure is for an inactive CID 0442 FMI 12.

Test Step 1. CHECK THE STATUS OF THE DIAGNOSTIC CODE.

  1. Turn the ECS to the OFF/RESET position and then turn the ECS to the STOP position.

  1. Press the "Alarm Codes" key.

  1. Observe the upper display. Check that the CID 0442 FMI 12 is active.

  1. If the diagnostic code is not active, enter the Service Mode. View the fault log for a OP1. Check that the diagnostic code is inactive.

Expected Result:

A CID 0442 FMI 12 is displayed as an active diagnostic code or CID 0442 FMI 12 is displayed as an inactive diagnostic code.

Results:

  • OK - The CID 0442 FMI 12 is active or the CID 0442 FMI 12 is inactive. Proceed to Test Step 2.

  • NOT OK - The CID 0442 FMI 12 has not occurred. The diagnostic code is not active and the diagnostic code is not inactive.STOP

Test Step 2. CHECK THE INTERNAL CABLE OF THE RELAY MODULE.

Note: Only open the relay module in a dry environment. If the inspection and repair takes more than approximately twenty minutes replace the desiccant bag in the GSC+P housing. Refer to Testing And Adjusting, "Relay Module - Replace".

  1. Turn the ECS to the OFF/RESET position.

  1. Disconnect the negative battery cable.

  1. Temporarily, remove the relay module from the GSC+P. Refer to Testing And Adjusting, "Relay Module - Replace".

  1. Check the cable that attaches the relay module to the GSC+P.

Expected Result:

The cable should be firmly seated in the connector. The clamp should be in place. The cable should not be damaged.

Results:

  • OK - The cable is firmly seated in the connector. The clamp is in place. The cable is not damaged. Reassemble the relay module to the GSC+P. Proceed to Test Step 3.

  • NOT OK - One or more of the components are damaged or the components are missing.

    Repair: Replace the clamp if the clamp is missing. If the cable is damaged, replace the GSC+P. Refer to Testing and Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    STOP

Test Step 3. PERFORM A FUNCTIONAL CHECK ON THE GFR.

  1. Turn the ECS to the OFF/RESET position.

  1. Reconnect the negative battery cable.

  1. Disconnect all wires from RM-22 of the relay module.

  1. Remove fuse "F5" from the relay module.

  1. At the relay module, measure the resistance from RM-22 to RM-7. Make a note of the resistance measurement.

  1. Turn the ECS to the STOP position and push in the emergency stop push button.

  1. At the relay module, measure the resistance from RM-22 to RM-7. Make a note of the resistance measurement.

Expected Result:

The initial resistance measurement after removing the wires from the relay module should be 5000 ohms. The resistance measurement should be less than 5 ohms when the ECS is placed in the STOP position.

Results:

  • OK - The resistance measurements are correct. The problem does not exist at this time. The initial problem was probably caused by a poor electrical connection or a short at one of the harness connectors that was disconnected and reconnected. Resume normal operation and watch for a recurrence.STOP

  • NOT OK - Either one of the resistance measurements are NOT correct. The relay module has failed.

    Repair: Replace the relay module. refer to Testing And Adjusting, "Relay Module - Replace".

    STOP

Caterpillar Information System:

C9 Petroleum Engines Fan Drive Mounting Group - Remove and Install
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0336 - FMI 02
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0334 - FMI 04
349F and 352F Excavators Machine System Specifications Track Carrier Roller
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0334 - FMI 03
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Planetary - Assemble
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Planetary - Disassemble
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Planetary - Install
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Planetary - Remove
568 Forest Machine Machine System Specifications Track Adjuster
C9 Petroleum Engines Inlet Air Temperature Sensor - Remove and Install
C9 Petroleum Engines Turbocharger Outlet Pressure Sensor - Remove and Install
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0443 - FMI 12
G3600 Engines Ignition Primary - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0446 - FMI 12
Relocating the Air Filter Assembly on C4.4 Engines{1051, 1054} Relocating the Air Filter Assembly on C4.4 Engines{1051, 1054}
C9 Petroleum Engines Electronic Control Module - Remove and Install
3500C Marine Engines Vibration Damper
C175 Generator Sets Manual Stop Procedure
2008/02/11 Update on the Factory Password System {1901, 7620}
G3600 Engines Ignition Secondary - Test
2008/02/18 Update on the Factory Password System {1901, 7620}
2008/02/01 Update on the Factory Password System {1901, 7620}
2008/09/29 An Improved Three-Piece Oil Pan Gasket is Now Used {1302, 7555}
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.