Electronic Modular Control Panel II+ Paralleling (EMCP II+P) Caterpillar


GSC CID 0268 - FMI 02

Usage:

C32 SXC
Conditions Which Generate This Code:

A portion of memory within the GSC+P stores the setpoints of important generator set conditions. The setpoints are listed below.

  • engine/generator setpoint programming OP5-0

  • protective relaying setpoints OP5-1

  • spare input/output programming OP6

  • voltmeter/ammeter setpoint programming OP8

The GSC+P detects a CID 0268 FMI 02 when the setpoint data is invalid or the setpoint data is out of range. After detecting a CID 0268 FMI 02, the GSC+P sets the affected setpoints to the default value. For more information regarding setpoints and default values, refer to the topics that are listed below.

  • Systems Operation, "Engine/Generator Programming OP5-0"

  • Systems Operation, "Protective Relaying Programming OP5-1"

  • Systems Operation, "Spare Input/Output Programming OP6"

  • Systems Operation, "Voltmeter/Ammeter Programming OP8"

The possible cause of a CID 0268 FMI 02 is electrical interference.

This procedure is designed to correct an active CID 0268 FMI 02 or the procedure is designed to correct an inactive CID 0268 FMI 02. Clear the diagnostic code from the fault log after troubleshooting is complete.

The GSC+P treats a CID 0268 FMI 02 as an alarm fault or the GSC+P treats a CID 0268 FMI 02 as a shutdown fault. The treatment depends on the particular setpoint with bad data. The ring gear teeth P009 setpoint and the engine overspeed P010 setpoints are treated as shutdown faults when the particular data is corrupted. All other setpoints are treated as alarm faults when the particular data is corrupted.

Note: The GSC+P setpoints must be programmed in the OFF/RESET position when a shutdown fault is active. If the alarm for the fault indicator is FLASHING the GSC+P can be programmed with the ECS in the OFF/RESET position or the COOLDOWN/STOP position.

Test Step 1. CHECK THE SETPOINTS.

  1. View the setpoints that are stored in the memory of the GSC+P. Refer to Systems Operation, "Engine/Generator Setpoint Viewing OP2-0".

  1. Also check Systems Operation, "Spare Input/Output Programming (OP6)" and Systems Operation, "Voltmeter/Ammeter Programming (OP8)".

  1. Compare the stored setpoints to the specified setpoints of the particular generator set.

Expected Result:

The stored setpoints and the specified setpoints should match.

Results:

  • OK - All the setpoints match. Start the engine. Check the upper display for a CID 0268 FMI 02. If the diagnostic code was inactive prior to performing this procedure, then these steps should have corrected the problem.

    Repair: If the diagnostic code remains active, The GSC+P may have failed. It is unlikely that the GSC+P has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC+P. Refer toTesting And Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    STOP

  • NOT OK - One or more of the setpoints do not match.

    Repair: Program the setpoints. Refer to the following sections.

    • Systems Operation, "Engine/Generator Programming OP5-0"

    • Systems Operation, "Protective Relaying Programming OP5-1"

    • Systems Operation, "Spare Input/Output Programming OP6"

    • Systems Operation, "Voltmeter/Ammeter Programming OP8"

    STOP

Caterpillar Information System:

C13 and C15 On-highway Engines Engine Monitoring System
C175-16 Locomotive Engine Water Pump
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0190 - FMI 03
G3500 A3 Engines Exhaust Temperature Module
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Hydraulic Control - Assemble
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Hydraulic Control - Disassemble
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Hydraulic Control - Install
TH55-E70 and TH55-E90 Petroleum Transmissions Transmission Hydraulic Control - Remove
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0190 - FMI 02
2007/12/01 Procedure to Use the Correct Mounting Bolts with the 10R-2356 Flywheel As {1156}
2007/12/24 Procedure to Use the Correct Mounting Bolts with the 10R-2356 Flywheel As {1156}
2011/02/11 Procedure to Use the Correct Mounting Bolts with the 10R-2356 Flywheel As {1156}
C9 Petroleum Engines Atmospheric Pressure Sensor - Remove and Install
C27 and C32 Engines for Caterpillar Built Machines Electronic Service Tool Does Not Communicate
C9 Petroleum Engines Coolant Temperature Sensor - Remove and Install
C9 Petroleum Engines Engine Oil Pressure Sensor - Remove and Install
3176C, 3406E and 3456 Industrial Engines Electrical Connectors
2007/12/17 The Caterpillar Digital Voltage Regulator (CDVR) Has been Improved {4467}
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0269 - FMI 04
C9 Petroleum Engines Fuel Pressure Sensor - Remove and Install
C13 and C15 On-highway Engines Solenoid Valve - Test
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0333 - FMI 03
C9 Petroleum Engines Injection Actuation Pressure Sensor - Remove and Install
Electronic Modular Control Panel II+ Paralleling (EMCP II+P) GSC CID 0333 - FMI 04
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.