- Wheel Loader:
- 988F Series II (S/N: 2ZR2-UP)
- 988G (S/N: BNH1-UP; 2TW1-UP)
- 988H (S/N: A7A1-UP; BXY1-UP)
- 990 Series II (S/N: BCR1-UP; 4FR1-UP)
- 990 (S/N: 7HK1-UP)
- 990H (S/N: BWX1-UP)
- 992G (S/N: 7HR1-UP; AZX1-UP; ADZ1-UP)
- 992K (S/N: H4C1-UP)
- 993K (S/N: Z9K1-UP)
- 988G (S/N: BNH1-UP; 2TW1-UP)
Introduction
Use the solution that is identified below to discharge and service the ride control accumulator on the large wheel loaders listed above.
Problem
The Testing and Adjusting information for the large wheel loaders does not provide the correct instructions to discharge the ride control accumulator that is equipped with a 158-2336 Gas Valve .
Solution
Use the following instructions to test and charge the ride control accumulator for the machines listed. The Testing and Adjusting service information for the machines listed have been updated to include this change.
Ride Control Accumulator - Test and Charge
Dry nitrogen is the only gas approved for use in the accumulators. The charging of oxygen gas in an accumulator will cause an explosion. An explosion can be eliminated by using nitrogen gas cylinders with standard CGA (Compressed Gas Association, Inc.) No. 580 connectors. When nitrogen gas is ordered, make sure to order the cylinders with CGA No. 580 connectors. Do not rely on color codes or other methods of identification to tell the difference between nitrogen and oxygen cylinders. In any application, never use an adapter to connect your nitrogen charging group to a valve outlet used on both nitrogen, oxygen, or other gas cylinders. BE SURE YOU USE DRY NITROGEN (99.8% purity). |
Required Tools     | |||
Tool     | Part Number     | Description     | Qty     |
A     | 175-5507     | Nitrogen Charging Group     | 1     |
Machine Preparation
Prepare the machine for testing by completing the procedure that is specified in the Service Manual module Testing and Adjusting, "Machine Preparation for Troubleshooting" for the machine that is being serviced.
Discharging the Accumulator
Illustration 1 | g02606538 |
Accumulator Valve (1) Guard. (2) Charging Valve. (A) Protective Cap. |
- Remove Guard (1) which protects the nitrogen charging valve (2) .
- Remove the protective cap (A) on the nitrogen charging valve (2)
Accumulator equipped with 158-2336 Gas Valve
- Hold the hex nut at location (C) of the nitrogen charging valve with one wrench. Turn the hex nut at location (B) with a second wrench in a counterclockwise direction. Loosening the nut opens the nitrogen charging valve (2). Three turns will fully open the valve. The compressed gas will be released from the ride control accumulator. Now, the ride control accumulator can be removed from the machine.
Illustration 2 | g02606596 |
158-2336 Gas Valve |
Illustration 3 | g02614637 |
158-2336 Gas Valve |
Accumulator equipped with 222-2367 Gas Valve Assembly
Illustration 4 | g02614762 |
222-2367 Gas Valve Assembly |
Illustration 5 | g00282185 |
(3) Nipple. (4) Coupling assembly. (5) Pressure gauge. (6) Hose assembly. (7) Coupling assembly. (8) Nipple. (9) Valve. (10) Pressure gauge. (11) Regulator assembly. (12) Pressure regulating screw. (13) Chuck for the nitrogen cylinder valve. (14) Valve handle. (15) Chuck. (16) Hose assembly. (17) Tee. |
- Identify the correct nitrogen charging chuck.
- Attach hose assembly (16) to nitrogen charging chuck (15)
- Turn on the valve handle (14) of the nitrogen charging chuck (15) all the way in the counterclockwise direction.
Note: Turning the valve handle will ensure that nitrogen charging valve (2) will not be opened when nitrogen charging chuck (15) is attached to nitrogen charging valve (2) .
- Attach nitrogen charging chuck (15) and hose assembly (16) to nitrogen charging valve (2)
- Place the open end of hose assembly (16 ) away from the work area and away from other personnel.
- Turn on the valve handle (14) of the nitrogen charging chuck (15) all the way in the clockwise direction in order to open nitrogen charging valve (2), Turning the valve handle will release all of the nitrogen from the accumulator through hose assembly (16). Remove the hydraulic lines from the accumulator. Now, the accumulator can be removed from the machine.
Testing Procedure for the Accumulator Precharge Pressure
Illustration 6 | g00282185 |
(3) Nipple. (4) Coupling assembly. (5) Pressure gauge. (6) Hose assembly. (7) Coupling assembly. (8) Nipple. (9) Valve. (10) Pressure gauge. (11) Regulator assembly. (12) Pressure regulating screw. (13) Chuck for the nitrogen cylinder valve. (14) Valve handle. (15) Chuck. (16) Hose assembly. (17) Tee. |
Note: Test the accumulator precharge pressure when the machine is not running and the work tool is flat on the ground. The pressure in the hydraulic system must be released. The released pressure will ensure that the accumulator piston has shifted to the oil end of the accumulator.
- Remove guard (1) which protects nitrogen charging valve (2) .
- Remove the protective cap on nitrogen charging valve (2) .
- Identify the correct nitrogen charging chuck.
- Turn the handle for valve (14) of the nitrogen charging chuck (15) all the way in the counterclockwise direction.
- Attach nitrogen charging chuck (15) and hose assembly (16) to nitrogen charging valve (2) .
- Attach hose assembly (16) between nitrogen charging chuck (15) and tee (17). Install needle valve (9) on tee (17), as shown. Install an 8T-0858 Pressure Gauge in the remaining open port on the tee. The pressure gauge is rated at 0 to 16000 kPa (0 to 2300 psi).
- Turn the valve handle for needle valve (9) all the way in the clockwise direction. Completely turning the valve handle will ensure that the needle valve (9) is closed.
- Open nitrogen charging valve (2)
- Accumulators equipped with a 158-2336 Gas Valve , hold the hex nut at location (C ) of the nitrogen charging valve with one wrench. Turn the hex nut location (B) with a second wrench in a counterclockwise direction. Loosening the nut opens the nitrogen charging valve (2). Three turns will fully open the valve.
Show/hide tableIllustration 7 g02606596
158-2336 Gas Valve
- Read pressure gauge (10) in order to determine the charge pressure in the accumulator. Refer to Table 2 for the correct pressure reading for your machine.
Show/hide table
Table 2 988F Wheel Loader    
2900 kPa (420 psi) @
21° C (70° F)    988G Wheel Loader    
4480 kPa (650 psi) @
21° C (70° F)    988H Wheel Loader    
3800 kPa (551 psi) @
21° C (70° F)    990 Wheel Loader    
3445 kPa (500 psi) @
21° C (70° F)    990 II Wheel Loader    
3445 kPa (500 psi) @
21° C (70° F)    990H Wheel Loader    
5000 kPa (725 psi) @
21° C (70° F)    992G Wheel Loader    
5000 kPa (725 psi) @
21° C (70° F)    992K Wheel Loader    
5000 kPa (725 psi) @
21° C (70° F)    993K Wheel Loader    
5500 kPa (800 psi) @
21° C (70° F)    Note: If the machine has been running for some time, the ambient temperature of the accumulator may be different from the outside air temperature. Refer to the following table that applies to your machine model for the proper pressure.
Show/hide tableTable 3 988F Accumulator Precharge Pressure/Temperature Relationship for a Typical Accumulator with a Precharge of
2900 kPa (420 psi)    Temperature     Pressure (1)    
−7 °C (20 °F)    
2625 kPa (381 psi)    
−1 °C (30 °F)    
2673 kPa (388 psi)    
4 °C (40 °F)    
2728 kPa (396 psi)    
10 °C (50 °F)    
2784 kPa (404 psi)    
16 °C (60 °F)    
2839 kPa (412 psi)    
21 °C (70 °F)    
2900 kPa (420 psi)    
27 °C (80 °F)    
2949 kPa (428 psi)    
32 °C (90 °F)    
3004 kPa (436 psi)    
38 °C (100 °F)    
3059 kPa (444 psi)    
43 °C (110 °F)    
3114 kPa (452 psi)    
49 °C (120 °F)    
3169 kPa (460 psi)    Show/hide table( 1 ) Nominal allowable tolerance equals 34 kPa (5psi) Show/hide tableTable 4 988G Accumulator Precharge Pressure/Temperature Relationship for a Typical Accumulator with a Precharge of
4480 kPa (650 psi)    Temperature     Pressure    
−7 °C (20 °F)    
4061 kPa (589 psi)    
−1 °C (30 °F)    
4144 kPa (601 psi)    
4 °C (40 °F)    
4226 kPa (613 psi)    
10 °C (50 °F)    
4309 kPa (625 psi)    
16 °C (60 °F)    
4399 kPa (638 psi)    
21 °C (70 °F)    
4482 kPa (650 psi)    
27 °C (80 °F)    
4564 kPa (662 psi)    
32 °C (90 °F)    
4654 kPa (675 psi)    
38 °C (100 °F)    
4737 kPa (687 psi)    
43 °C (110 °F)    
4819 kPa (699 psi)    
49 °C (120 °F)    
4902 kPa (711 psi)    Show/hide tableTable 5 988H Accumulator Precharge Pressure/Temperature Relationship for a Typical Accumulator with a Precharge of
3800 kPa (551 psi)    Temperature     Pressure    
−7 °C (20 °F)    
3428 kPa (497 psi)    
−1 °C (30 °F)    
3508 kPa (509 psi)    
4 °C (40 °F)    
3574 kPa (518 psi)    
10 °C (50 °F)    
3654 kPa (530 psi)    
16 °C (60 °F)    
3734 kPa (542 psi)    
21 °C (70 °F)    
3800 kPa (551 psi)    
27 °C (80 °F)    
3880 kPa (563 psi)    
32 °C (90 °F)    
3946 kPa (572 psi)    
38 °C (100 °F)    
4026 kPa (584 psi)    
43 °C (110 °F)    
4092 kPa (593 psi)    
49 °C (120 °F)    
4172 kPa (605 psi)    Show/hide tableTable 6 990 & 990 Series II Accumulator Precharge Pressure/Temperature Relationship for a Typical Accumulator with a Precharge of
3445 kPa (500 psi)    Temperature     Pressure (1)    
−7 °C (20 °F)    
3100 kPa (450 psi)    
−1 °C (30 °F)    
3170 kPa (460 psi)    
4 °C (40 °F)    
3240 kPa (470 psi)    
10 °C (50 °F)    
3310 kPa (480 psi)    
16 °C (60 °F)    
3375 kPa (490 psi)    
21 °C (70 °F)    
3445 kPa (500 psi)    
27 °C (80 °F)    
3515 kPa (510 psi)    
32 °C (90 °F)    
3585 kPa (520 psi)    
38 °C (100 °F)    
3655 kPa (530 psi)    
43 °C (110 °F)    
3725 kPa (540 psi)    
49 °C (120 °F)    
3790 kPa (550 psi)    Show/hide table( 1 ) Nominal allowable tolerance equals 70 kPa (10 psi) Show/hide tableTable 7 990H, 992G & 992K Accumulator Precharge Pressure/Temperature Relationship for a Typical Accumulator with a Precharge of
5000 kPa (725 psi)    Temperature     Pressure    
−7 °C (20 °F)    
4530 kPa (657 psi)    
−1 °C (30 °F)    
4624 kPa (671 psi)    
4 °C (40 °F)    
4717 kPa (684 psi)    
10 °C (50 °F)    
4810 kPa (698 psi)    
16 °C (60 °F)    
4905 kPa (711 psi)    
21 °C (70 °F)    
5000 kPa (725 psi)    
27 °C (80 °F)    
5092 kPa (739 psi)    
32 °C (90 °F)    
5185 kPa (752 psi)    
38 °C (100 °F)    
5198 kPa (754 psi)    
43 °C (110 °F)    
5270 kPa (764 psi)    
49 °C (120 °F)    
5364 kPa (778 psi)    Show/hide tableTable 8 993K Accumulator Precharge Pressure/Temperature Relationship for a Typical Accumulator with a Precharge of
5500 kPa (800 psi)    Temperature     Pressure    
−7 °C (20 °F)    
5000 kPa (725 psi)    
−1 °C (30 °F)    
5105 kPa (740 psi)    
4 °C (40 °F)    
5235 kPa (760 psi)    
10 °C (50 °F)    
5340 kPa (775 psi)    
16 °C (60 °F)    
5420 kPa (785 psi)    
21 °C (70 °F)    
5500 kPa (800 psi)    
27 °C (80 °F)    
5605 kPa (815 psi)    
32 °C (90 °F)    
5735 kPa (830 psi)    
38 °C (100 °F)    
5840 kPa (845 psi)    
43 °C (110 °F)    
5920 kPa (860 psi)    
49 °C (120 °F)    
6000 kPa (870 psi)    
- Proceed to Step 11 if the accumulator precharge pressure is within the specification.
You will need to charge the accumulator if the pressure is not within the specification. Proceed to the ""Charging Procedure" " for instructions to charge the accumulator.
- Close nitrogen charging valve (2) .
- Accumulators equipped with a 158-2336 Gas Valve , with a wrench, tighten hex nut at location (B) of the nitrogen charging valve in a clockwise direction to close the nitrogen charging valve (2). Tighten the hex nut at to a torque of 8.8 ± 2 N·m (6.5 ± 1.5 lb ft)
Show/hide tableIllustration 9 g02606737
158-2336 Gas Valve
- Turn on the handle for needle valve (9) in a counterclockwise direction. Turning the handle will allow the pressure in hose (16) to vent.
- Remove Tool (A) from the machine.
- Install the protective cap on nitrogen charging valve (2) .
- Install guard (1) on the accumulator.
Charging Procedure
Illustration 11 | g02606538 |
Accumulator Valve (1) Guard. (2) Charging Valve. (A) Protective Cap. |
Illustration 12 | g00282185 |
(3) Nipple. (4) Coupling assembly. (5) Pressure gauge. (6) Hose assembly. (7) Coupling assembly. (8) Nipple. (9) Valve. (10) Pressure gauge. (11) Regulator assembly. (12) Pressure regulating screw. (13) Chuck for the nitrogen cylinder valve. (14) Valve handle. (15) Chuck. (16) Hose assembly. (17) Tee. |
Before proceeding to the test procedure that follows, complete the procedure:
- Testing and Adjusting, "Machine Preparation for Troubleshooting"
- Perform Step 1 through Step 9 of the ""Testing Procedure for the Accumulator Precharge Pressure" " for instructions on the installation of the nitrogen charging group.
- Use Caterpillar Electronic Technician (ET) in order to turn the ride control ON.
- Open the software program for the ET.
- Select "Transmission ECM".
- Select "Override Parameters" from the drop-down menu that is located under "Diagnostics".
- Select "Change".
- Select "ON" for the "New Value" .
- Select "OK".
- A window will appear on the screen that will ask you if you want to change the parameter. Select "Yes".
- Open needle valve (9) .
- Start the engine.
- Pull back on the lift control lever in order to raise the boom to full lift.
- Recenter the lift control lever.
- Pull back on the lift control lever again. Pulling back on the control lever will cause the lift circuit to reach relief pressure.
- Close needle valve (9) .
- Lower the boom in order to place the work tool on the ground.
- Move the lift control lever into the FLOAT.
- Attach the open end of hose assembly (6) to needle valve (9) by using coupling (7) and nipple (8) .
- Attach regulator assembly (11) to a nitrogen tank.
- Adjust pressure regulating screw (12) in order to obtain the correct pressure reading on gauge (5). Refer to Table 2 for the correct pressure for your machine.
Note: The pressure reading in Table 2 is the appropriate pressure for the accumulator when the ambient temperature is 21 °C (70 °F). If the machine has been running for some time, the temperature of the accumulator may be different from the ambient temperature of the outside air. Refer to Table 4 through 8 for the proper pressure for your machine.
- Open needle valve (9). Measure the amount of time that is required for gauge (10) to obtain the charge pressure. Charging time should take 10 to 20 seconds.
Note: If the charging time is less than 10 seconds, repeat Step 1 through Step 8 in order to exhaust the nitrogen gas from the accumulator. Repeat Steps 9 through 14 in order to charge the accumulator.
- Once the accumulator is charged, close the nitrogen charging valve.
- Accumulators equipped with a 158-2336 Gas Valve , with a wrench, tighten hex nut at location (B) of the nitrogen charging valve in a clockwise direction to close the nitrogen charging valve (2). Tighten the hex nut to a torque of 8.8 ± 2 N·m (6.5 ± 1.5 lb ft)
Show/hide tableIllustration 13 g02606758
158-2336 Gas Valve
- Accumulators equipped with a 222-2367 Gas Valve Assembly , turn valve handle (14) in a counterclockwise direction in order to close nitrogen charging valve (2) .
Illustration 14 | g02614762 |
222-2367 Gas Valve Assembly |
- Close the valve on the nitrogen cylinder.
- Slowly loosen chuck (15) from accumulator valve (2) and allow the pressure to vent from hose (16). Observe gauge (10) in order to determine when the pressure has been released from hose (16) .
- Remove chuck (15) from accumulator valve (2) .
- Install the protective cap (A) on accumulator valve (2) .
- Install guard (1) .
- Use the ET to return the ride control to the automatic mode.
- Select "Transmission ECM".
- Select "Override Parameters".
- Select "Disable Override".
- Exit the ET software.
Diverter Valve Test
Note: The following steps are used to determine if the diverter valve is operating correctly. This test should be performed in order to verify that the ride control is being activated.
- Lift the front wheels off the ground by moving the bucket to the full LOWER position. With the front wheels off the ground, place the lift control lever in the HOLD position.
- Use Caterpillar Electronic Technician (ET) in order to turn the ride control ON.
- Open the software program for the ET.
- Select "Transmission ECM".
- Select "Override Parameters" that is located in the drop-down menu under "Diagnostics".
- Select "Change".
- Select "ON" for the "New Value" .
- Select "OK".
- A window will appear on the screen that will ask you if you want to change the parameter. Select "Yes".
Note: The ride control will activate when "Yes" is selected. The front wheels should lower to the ground. If the wheels do not lower to the ground, the diverter spool has not shifted to the ON position. The following causes could be the reason that the diverter spool does not move to the ON position:
- a failure of the ride control switch
- a failure of the solenoid coil on the diverter valve
- a failure of the cartridge valve in diverter valve
- a failure of the spool valve in the diverter valve
- a blockage in pilot circuit to the diverter valve
- a failure of the ride control switch