Electric Power Generation Principles Caterpillar


Load Transfer

Usage:

SR4B 1BN
When two or more electric sets are operating in parallel and it is known that the total load will be less than the capacity of all the units and will not cause an overload if the number of paralleled units is reduced by disconnecting one or more units, the load can be transferred to an adequate number of units and the others disconnected from the load. The following discussion is an explanation of the actions of governors and regulators on engine electric sets during load transfer and the disconnection of one or more units from parallel operation. This discussion will cover the operation of two units. If more than two units are operating, the same principles apply to the complete system.

If the system were initially started with the units unloaded before being paralleled, the speed of each engine would be rated speed plus speed droop as shown at points A and D of Illustration 1. The voltage of each unit would be rated voltage plus voltage droop as shown by points G and K. With these conditions, the circuit breakers can be closed to place the units in parallel. When the system is loaded, the engine speed will follow the governor sped droop characteristics and the generator voltages will follow the regulator voltage droop characteristics. With 50% load on each unit, the engine speeds (and the frequency of the system) will be as shown by points E and F, and the voltage of the system will be as shown by points L and M. At full load on each unit, the engine speed and the frequency of the system will be as shown by points B and C and the voltage of the system will be as shown by H and J.




Illustration 1g01059140

Load transfer and disconnections of paralleled generators.

If it is known than the steady load on the system for a period of time will be 50% or less of the total capacity of the generators, it may be desirable to transfer the load to one unit and disconnect the other unit from the system. In this case, the unit still operating will be loaded to 100% or less of its rating. Note that in the preceding paragraphs, the two units were paralleled with the governors at their high idle settings. In order to transfer the load to just one unit, for example Unit Two, the governor control of Unit One is moved in the "reduce speed" direction until the k.w. meter for generator one indicates zero k.w. In the event that there are no k.w. meters for the installation, then the ammeter for generator one should show a minimum indication which is not necessarily zero amperes. At this point, Unit Two is carrying all the load and, if this load is 100% of the rating of the unit, the speed of the system will tend to be at point C and the voltage of the system will tend to be at point J.

What has occurred in the above paragraph is that the governor characteristic of Unit One has been moved down to the points A' and B' (Illustration 1) and this unit is floating on the line, but carrying no k.w. load; however, as the load was increase on Unit Two, its speed followed the governor characteristic line from point F to point C. AS the load increase on Unit Two, the voltage of the generator tended to follow the voltage droop characteristic from point M to point J. Also the voltage of generator one tended to follow its voltage droop characteristics from point L to point G. This tendency for the voltage of the unloaded unit to rise as the k.w. load on the unit is reduced can result in an indication of amperes on the ammeter for generator one even though the unit is delivering no k.w. to the system. What has occurred is that the voltage droop circuit of the regulator has tended to increase voltage as the load on the generator is reduced. This is accomplished by the exciter furnishing additional magnetizing power to the generator. This magnetizing power is in excess of that required to maintain rated voltage in the system and magnetizing amperes are delivered to the system. These magnetizing amperes are shown by the indication of the ammeter for generator one. If this indication is a fairly small value such as 20% or less of generator rated amperes, the circuit breaker for Unit One can be opened and the unit can be disconnected from the system.

If the amperes indicated on the ammeter for generator one are greater than 20% of the governor rated amperes, or if the device for disconnecting the unit from the system is a knife switch, it may be desirable to reduce the magnetizing amperes to a much smaller value before disconnecting the unit from the system. This is accomplished by reducing the setting of the voltage level control of generator one. Turning the voltage level control in the direction to reduce the voltage will reduce the magnetizing power of the generator and the voltage droop characteristics of generator one has been moved down to the points G' and H'. Under these conditions Unit One can be disconnected with a minimum of disturbance to the system and Unit Two will be carrying the complete load. If the voltage or the frequency of Unit Two is varied from the desired values during this operation, they can be corrected by minor adjustments to the governor and the voltage level controls.

Caterpillar Information System:

Electric Power Generation Principles Parallel Operation of Generators
C-15 Petroleum Engine Turbocharger - Install
C-15 Petroleum Engine Turbocharger - Remove
2004/03/01 Revised Special Instruction, REHS0147, "Installation Of The Hydraulic Actuator System (Hydrax System) on G3606 and G3608 Engines" Is Available {1901}
2004/03/01 New Special Instruction, REHS1708, "Installation of the Advanced Digital Engine Management (ADEM) III on G3606 and G3608 Engines" Is Available {1901}
G3520C and G3520E Engines Temperature Sensor
Electric Power Generation Principles Parallel Operation of Governors
3406E, C-10 and C-12 On-highway Engines Engine Cranks but Will Not Start
Electric Power Generation Principles Alternating Current Generator
C18 Marine Auxiliary Engines Injector Solenoid Circuit - Test
3406E, C-10 and C-12 On-highway Engines Cruise Control, Idle, or PTO Can Not Be Set
Electric Power Generation Principles Governor
Electric Power Generation Principles Switchgear Instrumentation
Electric Power Generation Principles Power Factor
3406E, C-10 and C-12 On-highway Engines Engine Misfires, Runs Rough or Is Unstable
C-15 Petroleum Engine Exhaust Manifold - Remove and Install
Electric Power Generation Principles Voltage Control
3126B Petroleum Engine Safety Messages
3126B Petroleum Engine Engine Description
3126B Petroleum Engine Plate Locations and Film Locations
2004/05/01 A Wiring Harness Kit is Now Available {1290, 1408}
2004/05/10 The Procedure for the Installation of the Electronic Unit Injector has changed. {1290}
2004/05/10 The Procedure for the Removal of the Electronic Unit Injector has Changed. {1290}
3406E, C-10 and C-12 On-highway Engines Excessive Black Smoke
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.