SR4 HV and SR4B HV Generators Caterpillar


Generator Set - Test

Usage:

3516B 1NW



Illustration 1g00935076

PMPE Generator Wiring Diagrams for 2400, 2500, 2800, and 2900 frames

(CR1-CR6) Diodes

(CR7) Varistor

(L1) Exciter field (stator)

(L2) Exciter armature (rotor)

(L3) Main field (rotor)

(L4) Main armature (stator)

(L5) Pilot exciter armature

(PM) Permanent magnet

(RFA) Rotating field assembly

(CST) Customer supplied transformer

(B) External 12 Volt DC Power Source




Illustration 2g00935050

PMPE Generator Wiring Diagrams for 2600 frames

(CR1-CR6) Diodes

(CR7) Varistor

(L1) Exciter field (stator)

(L2) Exciter armature (rotor)

(L3) Main field (rotor)

(L4) Main armature (stator)

(L5) Pilot exciter armature

(PM) Permanent magnet

(RFA) Rotating field assembly

(CST) Customer supplied transformer

(B) External 12 Volt DC Power Source

------ DANGER! ------

Dangerous voltages are present at both the generator and the system bus.

Under no circumstances should any attempt be made to connect instrumentation to these points until you are certain all power is off.

All instruments must be connected to the generator and the system bus through potential transformers, which provide a maximum of 600 volts to the instruments.

Failure to follow instructions will result in death or serious injury.


Dangerous voltages are present at the generator's output terminals. Until the power is verified to be OFF, there should not be any device that is connected to the following terminals: (T1), (T2) and (T3). The voltmeter must be connected to the generator through potential transformers. Potential transformers provide a maximum of 600 volts to the voltmeter.

Table 1
Tools Needed    
Part Number     Part     Quantity    
6V-7070     Digital Multimeter     1    
    12 VDC battery     1    
    Potential Transformer     1    

The generator set functional test is a simplified test that can be performed in order to determine if the generator is functional. The generator set functional test should be performed on a generator set that is under load.

The generator set functional test determines if the following statements happen:

  • A phase voltage is being generated.

  • The phase voltages are balanced.

  • The phase voltages change relative to engine speed.

The generator set functional test consists of the following steps:

  1. Stop the generator. Connect the potential transformer's high voltage winding to the generator terminals (T1) and (T2). Connect the voltmeter to the low voltage winding. If two transformers are available, connect the high voltage winding of the second transformer to the generator terminals (T1) and (T3). Connect the secondary terminals that correspond to generator terminal (T2) of both transformers together.

  1. Disconnect wires "F1+" and "F2-" from the voltage regulator. Disconnect the generator from the load.

  1. Connect a 12 Volt DC power source to wires "F1+" and "F2-"for 2600 frames. Connect a 12 Volt DC power source to wires "F1-" and "F2+"for all other frames.


    NOTICE

    Do not operate the generator set at a speed that is higher than one-half of the rated speed.

    Higher speeds under these test conditions can cause damage to the system.


  1. Operate the generator set at half the rated speed.

  1. Measure the AC voltage across the low voltage terminals of the transformer that correspond to the following generator terminals: "T1" and "T2", "T2" and "T3" and "T3" and "T1". Record the voltages.

  1. Monitor the voltage between any two of the locations in step 5. Decrease the generator set speed by 10%. Increase the generator set speed by 10%.

  1. The voltages that were measured in Step 5 should be nearly equal. These voltages should measure a minimum of 85 VAC.

  1. When the generator set speed is decreased by 10%, the voltages that were measured in Step 6 should decrease by 10%. When the generator set speed is increased by 10%, the voltages that were measured in Step 6 should increase by 10% .

Caterpillar Information System:

2002/12/01 New Thermocouples Are Used To Measure The Engine Exhaust Temperature {1059, 1919}
G3500 Engines Exhaust Manifold - Dry
C7 and C9 On-Highway Engines Air Inlet Heater Circuit - Test
Test Sequence for Pencil Type Fuel Nozzles{1254} Test Sequence for Pencil Type Fuel Nozzles{1254}
3056E Industrial Engine Fuel Injection Nozzles - Install
3056E Industrial Engine Fuel Injection Nozzles - Remove
G3520C and G3520E Generator Set Engines Cat Data Link - Test
G3520B Industrial Engine MID 036 - CID 1720 - FMI 09 Turbocharger Compressor Bypass Valve Actuator not communicating on link
G3520B Industrial Engine MID 036 - CID 1440 - FMI 09 Unable to communicate with Throttle Actuator Drv
G3408C and G3412C Engines Engine Oil Filter Base
G3406 Engines Engine Oil Filter Base
2002/12/16 New Water Seals Provide Increased Stability At Higher Temperatures {1100, 1124}
3056E Industrial Engine Exhaust Manifold - Remove and Install - Three-Piece Exhaust Manifold
G3500 Engines Exhaust Manifold - Dry
G3520C and G3520E Engines Spark Plug
416C, 426C, 428C, 436C and 438C Backhoe Loaders Emissions Certification Film
G3408 and G3412 Engines Idler Gear Assembly
2002/11/01 A New Fuel Transfer Pump Group Is Used {1256}
3056E Industrial Engine Exhaust Manifold - Remove and Install - Two-Piece Exhaust Manifold
G3408 and G3412 Engines Piston and Rings
C13 On-highway Engine Engine Design
3056E Industrial Engine Valve Mechanism Cover - Remove and Install
C11 and C13 On-Highway Engines Engine Design
3056E Industrial Engine Boost Pressure Sensor - Remove and Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.