The GSC+ alerts the operator and the GSC+ identifies the shutdown fault by FLASHING the corresponding shutdown indicator. The name of the shutdown indicator identifies the shutdown fault.
Shutdown Indicators
- Low oil pressure
- Emergency stop
- High water temperature
- Engine overspeed
- Engine overcrank
- Fault shutdown
- Spare 1, Spare 2 and Spare 3 accompanied by the fault shutdown indicator
If the fault shutdown indicator is the only indicator FLASHING, additional information is available. A fault code is shown on the upper display which more precisely identifies the cause of the shutdown fault. See System Operation, "Fault Description" for more information.
- A shutdown fault occurs and the GSC+ detects the shutdown fault.
- On EUI engines, in order to shut off the fuel, the GSC+ deactivates the electronic governor relay (EGR).
On PEEC engines, the GSC+ deactivates the run relay (RR). The normally open contacts of the run relay de-energize the coil of the crank relay (CR). The engine shutdown relay (ESDR) is de-energized. The normally closed contacts of the engine shutdown relay (ESDR) send a ground signal to the PEEC in order to shut down the engine.
- In order to prevent the engine from starting, the GSC+ deactivates the run relay (RR), and the GSC+ deactivates the starting motor relay (SMR).
- In order to remove the generator load, the GSC+ activates the genset fault relay (GFR). This activates the optional circuit breaker shunt trip coil.
Note: The spare output may also be programmed to activate when a shutdown occurs. This output can drive a relay in order to open the circuit breaker, or the output can open a transfer switch. See System Operation, "Spare Input/Output Programming OP6".
- When engine speed reaches 0 rpm, the GSC+ deactivates the crank termination relay (CTR). The electronic governor relay (EGR) is deactivated when the engine oil pressure reaches the setpoint P014 for low oil pressure shutdown at idle speed 70 kPa (10 psi).
- The GSC+ FLASHES the corresponding shutdown indicator. If the fault shutdown indicator is FLASHING, a fault code is shown on the upper display. See Systems Operation, "Fault Description".
- If the fault shutdown indicator is the only indicator FLASHING, additional information is available. A fault code is shown on the upper display that better identifies the cause of the shutdown fault. See the Systems Operation, "Fault Description".
- The lower display continues to show the engine data.
- The relay status indicators show.
- K2 (GFR)
- K7 (FCR) - (ETS fuel systems) for 70 seconds after engine speed decreases to 40 rpm and oil pressure decreases to 80 kPa (12 psi). (K7 is not shown for ETR fuel systems.)
- K2 (GFR)
Engine Start Sequence After Shutdown
- Correct the shutdown fault. See the System Operation, "Fault Identification".
- Turning the engine control switch (ECS) to the OFF/RESET position resets the GSC+. If no shutdown fault is active, the GSC+ returns to normal mode and the engine is able to start.