SR4 and SR4B Electric Power Generation Rewind Data Caterpillar


Winding Data for 9Y-1408 Generator through 9Y-9422 Generator

Usage:

SR4B 1BN

9Y-1408 Generator

Table 1
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
736.6 mm (29.0 inch)    

749.3 mm (29.5 inch)    
Slots     72     -    
Coil Throw     1 - 10     -    
Turns/Coil     3     -    
Turns/Pole     -     147.5    
No. & Wire Size     2 - #5 1/2 SQ    
3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2288.5 mm (90.1 inch)    
-    
Copper Weight    
179.6 kg (396.0 lb)    

69.9 kg (154.2 lb)    
Inside Connection (1)     6 Parallel Star     6 in Series    
Line Leads (No. & Size)     36 - #1     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00446 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.161 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     320     8     -    
No. & Size Wire     2 - #18.5 SQ     3 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)     -    
436.9 mm (17.2 inch)    
-    
Copper Weight    
14.8 kg (32.6 lb)    

6.4 kg (14.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series/Parallel     2 Parallel Star     -    
Line Leads     2 - #14 (75 inch) and 2 - #14 (95 inch)     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram F

9Y-1412 Generator

Table 2
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
342.9 mm (13.5 inch)    

342.9 mm (13.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     3.50 (3-4-3-4)     -    
Turns/Pole     -     96    
No. & Wire Size     1 - #16 and 6 - #15 SQ     1 - #9 SQ    
Mean Length Turn    
1163.3 mm (45.8 inch)    
-    
Copper Weight    
19.9 kg (43.8 lb)    

28.6 kg (63.0 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0131 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.8683 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17.0 SQ     1 - #14.5 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 04
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-1423 Generator

Table 3
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
355.6 mm (14.0 inch)    

368.3 mm (14.5 inch)    
Slots     60     -    
Coil Throw     1 - 11     -    
Turns/Coil     7     -    
Turns/Pole     -     216    
No. & Wire Size     2 -
2.5 mm (0.098 inch)×
4.5 mm (0.177 inch)    
#6 SQ    
Mean Length Turn    
1709.4 mm (67.3 inch)    
-    
Copper Weight    
142.5 kg (314.1 lb)    

164.2 kg (362.0 lb)    
Inside Connection (1)     1 Series Star     4 in Series    
Line Leads (No. & Size)     6 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.4050 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.214 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     1     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     8     -    
No. & Size Wire     1 - #15.5     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (39 inch)     3 - #10 (12 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 12
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-1425 Generator

Table 4
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
495.3 mm (19.5 inch)    

495.3 mm (19.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     2     -    
Turns/Pole     -     130    
No. & Wire Size     18 - #14     #8 SQ    
Mean Length Turn    
1645.9 mm (64.8 inch)    
-    
Copper Weight    
52.9 kg (116.7 lb)    

66.4 kg (146.4 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #0     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.014 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.40 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     6     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     150     8     -    
No. & Size Wire     1 - #16     2 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
388.6 mm (15.3 inch)    

350.5 mm (13.8 inch)    
-    
Copper Weight    
4.2 kg (9.1 lb)    

2.2 kg (4.8 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-1427 Generator

Table 5
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
335.3 mm (13.2 inch)    

335.3 mm (13.2 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     1.8 (1-2-2-2-2)     -    
Turns/Pole     -     180    
No. & Wire Size     24 - #14     #6.5 RD    
Mean Length Turn    
1585.0 mm (62.4 inch)    
-    
Copper Weight    
77.5 kg (170.8 lb)    

87.5 kg (193.0 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #000     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00288 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.27 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     160 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-1428 Generator

Table 6
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
414.0 mm (16.3 inch)    

414.0 mm (16.3 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.4 (1-2-1-2-1)     -    
Turns/Pole     -     180    
No. & Wire Size     27 - #14     #6.5 RD    
Mean Length Turn    
1678.9 mm (66.1 inch)    
-    
Copper Weight    
71.8 kg (158.3 lb)    

99.8 kg (220.0 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #000     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00218 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.44 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     160 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-1429 Generator

Table 7
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
431.8 mm (17.0 inch)    

431.8 mm (17.0 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.4 (1-2-1-2-1)     -    
Turns/Pole     -     180    
No. & Wire Size     29 - #14     #6.5 RD    
Mean Length Turn    
1714.5 mm (67.5 inch)    
-    
Copper Weight    
78.9 kg (174.0 lb)    

102.5 kg (225.9 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     48 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00215 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.545 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     160 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 47
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-1430 Generator

Table 8
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
457.2 mm (18.0 inch)    

457.2 mm (18.0 inch)    
Slots     60     -    
Coil Throw     1 - 12     -    
Turns/Coil     1.4 (1-2-1-2-1)     -    
Turns/Pole     -     180    
No. & Wire Size     34 - #14     #6.5 RD    
Mean Length Turn    
1765.3 mm (69.5 inch)    
-    
Copper Weight    
95.3 kg (210.0 lb)    

106.6 kg (235.0 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     12 - #0000     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00628 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.53 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     160 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 55
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-1431 Generator

Table 9
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
558.8 mm (22.0 inch)    

566.4 mm (22.3 inch)    
Slots     60     -    
Coil Throw     1 - 14     -    
Turns/Coil     1     -    
Turns/Pole     -     180    
No. & Wire Size     35 - #14     #6.5 RD    
Mean Length Turn    
2095.5 mm (82.5 inch)    
-    
Copper Weight    
80.3 kg (177.0 lb)    

123.4 kg (272.0 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     24 - #1     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00574 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.732 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     160 Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    

25.4 mm (1.0 inch)    
Coils/Group     1     1     1    
Slots (Coils)     6     36     48    
Turns (Coils)     140     8     12    
No. & Size Wire     1 - #15.5     2 - #16     4 - #18    
Coil Throw     1 - 2     1 - 6     1 - 4    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

464.8 mm (18.3 inch)    

208.3 mm (8.2 inch)    
Copper Weight    
5.2 kg (11.5 lb)    

2.9 kg (6.4 lb)    

1.8 kg (4.0 lb)    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     1 Series    
Line Leads     1 - #14     3 - #10     3 - #14    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 41
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-2934 Generator

Table 10
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
762.0 mm (30.0 inch)    

774.7 mm (30.5 inch)    
Slots     72     -    
Coil Throw     1 - 14     -    
Turns/Coil     1     -    
Turns/Pole     -     195.5    
No. & Wire Size     6 - #5 SQ    
3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2677.2 mm (105.4 inch)    
-    
Copper Weight    
216.7 kg (477.7 lb)    

398.3 kg (878.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     48 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00137 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.15 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     8     -    
No. & Size Wire     2 - #17 and 1 - #18     3 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
-    
Copper Weight    
14.0 kg (30.9 lb)    

6.4 kg (14.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram I

9Y-2935 Generator

Table 11
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
762.0 mm (30.0 inch)    

774.7 mm (30.5 inch)    
Slots     72     -    
Coil Throw     1 - 14     -    
Turns/Coil     1     -    
Turns/Pole     -     195.5    
No. & Wire Size     6 - #5 SQ    
3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2677.2 mm (105.4 inch)    
-    
Copper Weight    
216.7 kg (477.7 lb)    

398.3 kg (878.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     48 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00137 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.15 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     8     -    
No. & Size Wire     2 - #17 and 1 - #18     3 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
-    
Copper Weight    
14.0 kg (30.9 lb)    

6.4 kg (14.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram I

9Y-3872 Generator

Table 12
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
660.4 mm (26.0 inch)    

673.1 mm (26.5 inch)    
Slots     84     -    
Coil Throw     1 - 14     -    
Turns/Coil     1     -    
Turns/Pole     -     174    
No. & Wire Size     4 -
3.8 mm (0.148 inch)×
3.9 mm (0.153 inch)    

3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2423.2 mm (95.4 inch)    
-    
Copper Weight    
195.1 kg (430.1 lb)    

320.1 kg (705.6 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     48 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00209 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.895 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     8     -    
No. & Size Wire     2 - #17 and 1 - #18     3 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
-    
Copper Weight    
14.0 kg (30.9 lb)    

6.4 kg (14.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram I

9Y-3873 Generator

Table 13
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
660.4 mm (26.0 inch)    

673.1 mm (26.5 inch)    
Slots     84     -    
Coil Throw     1 - 17     -    
Turns/Coil     1     -    
Turns/Pole     -     174    
No. & Wire Size     6 -
3.8 mm (0.148 inch)×
3.9 mm (0.153 inch)    

3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2608.6 mm (102.7 inch)    
-    
Copper Weight    
195.1 kg (430.1 lb)    

320.1 kg (705.6 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     48 - #00     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00209 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.895 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     8     -    
No. & Size Wire     2 - #17 and 1 - #18 SQ     3 - #16 SQ     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
-    
Copper Weight    
14.0 kg (30.9 lb)    

6.4 kg (14.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     3 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 43
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram I

9Y-3876 Generator

Table 14
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
424.2 mm (16.7 inch)    

431.8 mm (17.0 inch)    
Slots     84     -    
Coil Throw     1 - 19     -    
Turns/Coil     1.00     -    
Turns/Pole     -     160    
No. & Wire Size     18 - #13     1 - #7    
Mean Length Turn    
1818.6 mm (71.6 inch)    
-    
Copper Weight    
65.4 kg (144.2 lb)    

98.6 kg (217.3 lb)    
Inside Connection (1)     4/2 Parallel Star     4 in Series    
Line Leads (No. & Size)     20 - #000     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0024 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.1792 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     140     7     -    
No. & Size Wire     1 - #15.5     2 - #15.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

406.4 mm (16.0 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.7 kg (6.0 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (78 inch)     3 - #8 (12 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 01
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram A

9Y-7180 Generator

Table 15
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
584.2 mm (23.0 inch)    

596.9 mm (23.5 inch)    
Slots     72     -    
Coil Throw     1 - 10     -    
Turns/Coil     3     -    
Turns/Pole     -     147.5    
No. & Wire Size     2 -
5.1 mm (0.201 inch)×
5.6 mm (0.220 inch)    

3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2014.2 mm (79.3 inch)    
-    
Copper Weight    
224.9 kg (495.9 lb)    

49.1 kg (108.2 lb)    
Inside Connection (1)     6 Parallel Star     6 in Series    
Line Leads (No. & Size)     36 - #2     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0026 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.9625 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     80 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
88.9 mm (3.5 inch)    

88.9 mm (3.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     8     -    
No. & Size Wire     2 - #17 and 1 - #18     3 - #16     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
355.6 mm (14.0 inch)    

436.9 mm (17.2 inch)    
-    
Copper Weight    
14.0 kg (30.9 lb)    

6.4 kg (14.0 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14     6 - #10     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 06
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

9Y-9374 Generator

Table 16
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
215.9 mm (8.5 inch)    

215.9 mm (8.5 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     7.00     -    
Turns/Pole     -     96    
No. & Wire Size     2 - #14 and 1 - #16     1 - #8 3/4 RD    
Mean Length Turn    
909.3 mm (35.8 inch)    
-    
Copper Weight    
14.8 kg (32.7 lb)    

17.6 kg (38.8 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     4 - #6     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.1718 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7924 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17     1 - #14.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 21
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-9375 Generator

Table 17
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
261.6 mm (10.3 inch)    

261.6 mm (10.3 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     5.75 (6-6-6-5)     -    
Turns/Pole     -     96    
No. & Wire Size     2 - #13 and 1 - #16     1 - #9    
Mean Length Turn    
1000.8 mm (39.4 inch)    
-    
Copper Weight    
16.4 kg (36.1 lb)    

24.0 kg (52.9 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     4 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.1272 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7715 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17     1 - #14.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 21
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-9416 Generator

Table 18
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
182.9 mm (7.2 inch)    

182.9 mm (7.2 inch)    
Slots     48     -    
Coil Throw     1 - 10     -    
Turns/Coil     8.00     -    
Turns/Pole     -     96    
No. & Wire Size     1 - #15 and 2 - #16     1 - #8 3/4 RD    
Mean Length Turn    
843.3 mm (33.2 inch)    
-    
Copper Weight    
12.4 kg (27.4 lb)    

16.1 kg (35.4 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     4 - #8     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.2297 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7237 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17     1 - #14.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 21
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-9417 Generator

Table 19
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
182.9 mm (7.2 inch)    

182.9 mm (7.2 inch)    
Slots     48     -    
Coil Throw     1 - 10.9542     -    
Turns/Coil     13-8-8     -    
Turns/Pole     -     96    
No. & Wire Size     1 - #15 and 2 - #16     1 - #8 3/4 RD    
Mean Length Turn    
883.9 mm (34.8 inch)    
-    
Copper Weight    
12.7 kg (27.9 lb)    

16.1 kg (35.4 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     4 - #8     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.2333 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7237 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17     1 - #14.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 26
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-9418 Generator

Table 20
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
215.9 mm (8.5 inch)    

215.9 mm (8.5 inch)    
Slots     48     -    
Coil Throw     1 - 10.9446     -    
Turns/Coil     13-7-7     -    
Turns/Pole     -     96    
No. & Wire Size     2 - #14 and 1 - #16     1 - #8 3/4 RD    
Mean Length Turn    
950.0 mm (37.4 inch)    
-    
Copper Weight    
14.9 kg (32.9 lb)    

17.6 kg (38.8 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     4 - #6     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.1731 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7924 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17     1 - #14.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 26
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-9419 Generator

Table 21
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
261.6 mm (10.3 inch)    

261.6 mm (10.3 inch)    
Slots     48     -    
Coil Throw     1 - 11.1144     -    
Turns/Coil     11-6-5     -    
Turns/Pole     -     96    
No. & Wire Size     2 - #13 and 1 - #15     1 - #9    
Mean Length Turn    
1049.0 mm (41.3 inch)    
-    
Copper Weight    
17.2 kg (37.9 lb)    

24.0 kg (52.9 lb)    
Inside Connection (1)     2 Parallel Star     4 in Series    
Line Leads (No. & Size)     4 - #4     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.1214 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.7293 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
50.8 mm (2.0 inch)    

50.8 mm (2.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     180     10     -    
No. & Size Wire     1 - #17     1 - #14.5     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
315.0 mm (12.4 inch)    

254.0 mm (10.0 inch)    
-    
Copper Weight    
2.7 kg (6.0 lb)    

1.4 kg (3.1 lb)    
-    
Insulation     Heavy Nytherm    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #12 (5.5 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 26
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram D

9Y-9421 Generator

Table 22
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
482.6 mm (19.0 inch)    

495.3 mm (19.5 inch)    
Slots     60     -    
Coil Throw     1 - 13     -    
Turns/Coil     3.00     -    
Turns/Pole     -     216    
No. & Wire Size     14 - #14     #6 SQ    
Mean Length Turn    
1993.9 mm (78.5 inch)    
-    
Copper Weight    
94.8 kg (208.9 lb)    

196.9 kg (434.0 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     16 - #0     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.00963 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     1.476 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     90 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     6    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
127.0 mm (5.0 inch)    

127.0 mm (5.0 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     6     36     -    
Turns (Coils)     125     6     -    
No. & Size Wire     1 - #15     2 - #15     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
464.8 mm (18.3 inch)    

406.4 mm (16.0 inch)    
-    
Copper Weight    
5.2 kg (11.5 lb)    

2.8 kg (5.9 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     2 - #14 (44 inch)     3 - #10 (26 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 10
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram B

9Y-9422 Generator

Table 23
MAIN STATOR AND ROTOR WINDING DATA    
ITEM     STATOR     ROTOR    
Stack Height    
520.7 mm (20.5 inch)    

538.5 mm (21.2 inch)    
Slots     72     -    
Coil Throw     1 - 14     -    
Turns/Coil     2     -    
Turns/Pole     -     175    
No. & Wire Size     16 - #12    
3.7 mm (0.144 inch)×
7.3 mm (0.288 inch)    
Mean Length Turn    
2115.8 mm (83.3 inch)    
-    
Copper Weight    
146.2 kg (322.3 lb)    

275.5 kg (607.4 lb)    
Inside Connection (1)     4 Parallel Star     4 in Series    
Line Leads (No. & Size)     16 - #000     -    
Terminal bolt size     3/8 in     -    
Low Voltage connected line resistance at 25 ° C (77 ° F)     0.0043 ohms     -    
Field lead resistance at 25 ° C (77 ° F)     -     0.795 ohms    
EXCITER WINDING DATA    
Exciter Frequency (Hz)     120 Hz     Permanent Magnet Frequency     - Hz    
Exciter Poles     8    
ITEM     STATOR (FIELD)     ROTOR (ARMATURE)     Permanent Magnet Stator    
Stack Length    
63.5 mm (2.5 inch)    

63.5 mm (2.5 inch)    
-    
Coils/Group     1     2     -    
Slots (Coils)     8     48     -    
Turns (Coils)     160     7     -    
No. & Size Wire     1 - #14     3 - #15     -    
Coil Throw     1 - 2     1 - 6     -    
Mean Length Turn (Calc.)    
330.2 mm (13.0 inch)    

386.1 mm (15.2 inch)    
-    
Copper Weight    
11.1 kg (24.5 lb)    

6.2 kg (13.7 lb)    
-    
Insulation     Heavy Polyester Polyamide Imide    
Connection (2)     Series     2 Parallel Star     -    
Line Leads     4 - #14 (25 inch)     6 - #10 (12 inch)     -    
( 1 ) See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram 10
( 2 ) See Specifications, "Connection Diagrams for Exciter" Connection Diagram C

Caterpillar Information System:

C-9 Engine for TK711, TK721, TK722, TK732, TK741, TK751, and TK752 Track Feller Bunchers Replacing the ECM
Programmable Relay Control Module (PRCM) Customer Device Problem
Generator Set Control Panel for Switchgear Conversion Control Board
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0110 - FMI 02 (for EUI Engines)
3126B and 3126E On-highway Engines Injection Actuation Pressure Control Valve Circuit - Test
2000/07/01 New Timing Control Module Used {1900, 1901}
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>9Y-0390</B> Generator through <B>9Y-0533</B> Generator
3500 Generator Set Engines Coolant Temperature Switch
JF Series Starting Motor Service Tools
3500 Engines For Caterpillar Built Power Modules Engine Speed Sensor
PM3516 Power Modules Maintenance Recommendations
3500 Engines For Caterpillar Built Power Modules Starting Motor
3126B Engine for Caterpillar Built Machines Turbocharger
3126B and 3126E On-highway Engines Injection Actuation Pressure Sensor - Test
2000/07/01 New Water Pumps With Improved Resistance To Shock Loads Used {1361}
3500 Generator Set Engines Fuel Injector Timing
3176C and 3196 Engines for Caterpillar Built Machines Fuel System Pressure - Test
3500 Generator Set Engines Fuel Injector Synchronization
3054 and 3056 Industrial and Generator Set Engines Gear Group - Inspect
3500 Generator Set Engines Fuel Setting
2001/07/01 New Unit Injector Sleeves and O-ring Seals Are Now Available {1290}
2000/07/01 New Caterpillar Digital Ignition System (CDIS) Provides Improvements Over Magneto Systems {1550, 1552}
3500 Generator Set Engines Restriction of Air Inlet and Exhaust
3500 Generator Set Engines Measuring Inlet Manifold Pressure
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.