Electronic Modular Control Panel II (EMCP II) For MUI Engines Caterpillar


Fault Identification

Usage:

3304 02B

Table 1
Fault Identification    
Indicator     Fault Code     DIAG Indicator     Fault Type     See Topic    
Fault
Alarm    
CID FMI (1)     Flashing     Active Alarm     Troubleshooting Diagnostic Codes    
SP1, SP2, SP3 (1) Not Present     Active Alarm     SP Fault Code - Troubleshoot    
AL1, AL2, AL3 (1) Not Present     Active Alarm     AL Fault Codes - Troubleshoot    
Dedicated
Shutdown    
Not Present     Not Present     Active Alarm     Troubleshooting Dedicated Shutdown Indicators    
Not Present Not Present     Active Shutdown    
Fault
Shutdown    
CID FMI     Flashing     Active Shutdown     Troubleshooting Diagnostic Codes    
SP1, SP2, SP3 Not Present     Active Shutdown     SP Fault Codes - Troubleshoot    
None     CID FMI (2)     On Continuously     Inactive Alarm     Troubleshooting Diagnostic Codes    
CID FMI (2) On Continuously     Inactive Shutdown     Troubleshooting Diagnostic Codes    
SP1, SP2, SP3 Not Present     Inactive Shutdown     SP Fault Codes - Troubleshoot    
Not Present Not Present     Undiagnosed Shutdown     Troubleshooting Undiagnosed Problems    
( 1 ) Fault code is shown after the alarm code key is pressed.
( 2 ) Diagnostic code is stored in the fault log of the GSC. In order to view the fault code, see Systems Operation, "Fault Log Viewing OP1".



Illustration 1g00595806

GSC Display Area

(1) Dedicated shutdown indicators. (2) Fault shutdown indicator. (3) Fault alarm indicator. (4) Upper display. (5) DIAG indicator. (6) Lower display.

Faults that are detected and diagnosed by the GSC are shown to service personnel in the display area of the GSC. The GSC uses dedicated shutdown indicators (1), fault shutdown indicator (2), fault alarm indicator (3), "DIAG" indicator (5), upper display (4) and lower display (6) to tell service personnel about a fault. Perform the following procedure in order to identify the fault that is detected by the GSC.

Note: "DIAG" indicator (8) functions (either FLASHING or ON CONTINUOUSLY) whenever the diagnostic information is available from the GSC.

  1. Note the indicators that are functioning on the left side of the GSC.

  1. View the diagnostic code on upper display (4). If the fault alarm indicator (3) is FLASHING and no diagnostic code is present on upper display (4), press the alarm codes key to view the fault code.

  1. Note whether or not "DIAG" indicator (5) is FLASHING, ON CONTINUOUSLY, or NOT PRESENT.

  1. Look at the first column on the table 1 and locate the fault indicator that is functioning.

  1. Go to the second column in the table 1 and find the fault code that is presently shown on upper display (4).

  1. Go to the third column in the table 1 which describes the status of "DIAG" indicator (5) .

  1. Read the last two columns in order to find the type of fault and the corresponding topic.

Caterpillar Information System:

3500B and 3500B High Displacement Generator Set Engines Engine Monitoring System
3406E and 3456 Generator Set Engines Flywheel Housing - Remove and Install
Electronic Modular Control Panel II (EMCP II) For MUI Engines Relay (Overcurrent)
Accessing Flash Software for Machines{7610, 7620} Accessing Flash Software for Machines{7610, 7620}
3500B Engines and 3500 Engines with EUI Option Air Shutoff System
3176C and 3196 Engines for Caterpillar Built Machines Cylinder Liner Projection - Inspect
3126B Marine Engine Aftercooler
3126B Marine Engine Turbocharger
3408E and 3412E Engines for Caterpillar Built Machines Cylinder Block - Inspect
3176C and 3196 Engines for Caterpillar Built Machines Main Bearings - Inspect
3114, 3116 and 3126 Industrial, Marine and Generator Set Engines Piston and Rings
Electronic Modular Control Panel II (EMCP II) For MUI Engines Relay (Overvoltage)
3126B Marine Engine Auxiliary Water Pump
3306C Engines for Caterpillar Built Machines Flywheel - Inspect
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 100 FMI 2 Pressure Sensor (Engine Oil) Incorrect Signal - Test
3408E and 3412E Engines for Caterpillar Built Machines Flywheel Housing - Inspect
3176C and 3196 Engines for Caterpillar Built Machines Vibration Damper - Check
C-10 and C-12 Truck Engines Slave Piston Lash - Adjust
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 100 FMI 3 Pressure Sensor (Engine Oil) Voltage Above Normal - Test
C-10 and C-12 Truck Engines Control Valve (Compression Brake) - Test
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 100 FMI 4 Pressure Sensor (Engine Oil) Voltage Below Normal - Test
CIPI UNDERCARRIAGE Arrangements: 9Q5221, 9Q5234, 9Q5243, 9Q5245, 9Q5246, 9Q5247, 9Q5385, 9Q5433, 9Q5482, 9Q5622, 9Q5661, 9Q5719, 9Q5720, 9Q5721, 9Q5722, 9Q5830, 9Q5840, 9Q5857, 9Q5874, 9Q5883, 9Q5930 and 9Q5940 Commercial Oils
C-10 and C-12 Truck Engines Solenoid Valve (Compression Brake) - Test
Electronic Modular Control Panel II (EMCP II) For MUI Engines CID 110 FMI 2 Temperature Sensor (Engine Coolant) Incorrect Signal - Test
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.