Winding Data for 5N-9081 Generator through 5N-9432 Generator
5N-9081 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 5.6 (6,6,4,6,6)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 6 - #15     | 1 - #17     | -     | |
Mean Length Turn     | 934.7 mm (36.8 inch)     |
-     | -     | |
Copper Weight     | 29.2 kg (64.3 lb)     |
438.1 kg (965.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     | 0.025 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     | -     | 0.56 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calc.)     | 365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 - 965.2 mm (38.0 inch)     |
#10 - 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9082 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 228.6 mm (9.0 inch)     |
228.6 mm (9.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.4(3,4,3,4,3)     | -     | -     | |
Turns/Pole     | -     | 96     | -     | |
No. & Wire Size     | 6 - #15     | 1 - #9     | -     | |
Mean Length Turn     | 960.1 mm (37.8 inch)     |
-     | -     | |
Copper Weight     | 18.6 kg (40.95 lb)     |
18.2 kg (40.04 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0148 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.80 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 160     | 9     | ||
No. & Size Wire     | 1 - #16.5     | 1 - #14     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
113.3 mm (4.46 inch)     |
254.0 mm (10.0 inch)     |
||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.5 kg (3.4 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 914.4 mm (36.0 inch)     |
#10 139.7 mm (5.5 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
5N-9083 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 203.2 mm (8.0 inch)     |
203.2 mm (8.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 14     | -     | -     | |
Turns/Coil     | 3.4(4,3,3,3,4)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 8 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1135.4 mm (44.7 inch)     |
-     | -     | |
Copper Weight     | 34.9 kg (77.0 lb)     |
34.2 kg (75.4 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.01 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.63 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14.5     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.7 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #01 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9084 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 5     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 7 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 934.7 mm (36.8 inch)     |
-     | -     | |
Copper Weight     | 29.3 kg (64.7 lb)     |
29.9 kg (65.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.01 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.63 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 95     | 6     | ||
No. & Size Wire     | 1 - #14.5     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.7 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9085 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 228.6 mm (9.0 inch)     |
228.6 mm (9.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 5     | -     | -     | |
Turns/Pole     | -     | 96     | -     | |
No. & Wire Size     | 5 - #15     | 1 - #9     | -     | |
Mean Length Turn     | 960.1 mm (37.8 inch)     |
-     | -     | |
Copper Weight     | 17.2 kg (37.98 lb)     |
18.2 kg (40.04 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.033 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.80 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 160     | 9     | ||
No. & Size Wire     | 1 - #16.5     | 1 - #14     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
113.3 mm (4.46 inch)     |
254.0 mm (10.0 inch)     |
||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.5 kg (3.4 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 914.4 mm (36.0 inch)     |
#10 139.7 mm (5.5 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #05 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).
5N-9086 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 203.2 mm (8.0 inch)     |
203.2 mm (8.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 4.65(4,4,5,5,5)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 7 - #15     | 1 - #7     | -     | |
Mean Length Turn     | 1036.3 mm (40.8 inch)     |
-     | -     | |
Copper Weight     | 27.2 kg (60.0 lb)     |
34.2 kg (75.4 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #4     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0192 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.630 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #05 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).
5N-9087 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 152.4 mm (6.0 inch)     |
152.4 mm (6.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 7     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 6 - #16     | 1 - #7     | -     | |
Mean Length Turn     | 934.7 mm (36.8 inch)     |
-     | -     | |
Copper Weight     | 27.9 kg (61.6 lb)     |
29.9 kg (65.9 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.0366 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.56 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
Note: Wires 20, 22, and 24 are brought out as tap connections between 4th and 5th coil (18 turns from T0).
5N-9088 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 228.6 mm (9.0 inch)     |
228.6 mm (9.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 4     | -     | -     | |
Turns/Pole     | -     | 96     | -     | |
No. & Wire Size     | 5 - #15     | 1 - #9     | -     | |
Mean Length Turn     | 960.1 mm (37.8 inch)     |
-     | -     | |
Copper Weight     | 17.2 kg (37.98 lb)     |
18.2 kg (40.04 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #6     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.021 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.80 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 50.8 mm (2.0 inch)     |
50.8 mm (2.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 160     | 9     | ||
No. & Size Wire     | 1 - #16.5     | 1 - #14     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
113.3 mm (4.46 inch)     |
254.0 mm (10.0 inch)     |
||
Copper Weight     | 2.7 kg (6.0 lb)     |
1.5 kg (3.4 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 914.4 mm (36.0 inch)     |
#10 139.7 mm (5.5 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #31 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram E |
5N-9089 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 203.2 mm (8.0 inch)     |
203.2 mm (8.0 inch)     |
-     | |
Slots     | 60     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 3.6(3,3,4,4,4)     | -     | -     | |
Turns/Pole     | -     | 110     | -     | |
No. & Wire Size     | 7 - #14     | 1 - #7     | -     | |
Mean Length Turn     | 1036.3 mm (40.8 inch)     |
-     | -     | |
Copper Weight     | 30.5 kg (67.2 lb)     |
442.4 kg (975.4 lb)     |
-     | |
Inside Connection (1)     | 4/2 Parallel Star     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 10 - #2     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
0.012 ohms     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 0.63 ohms     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 76.2 mm (3.0 inch)     |
76.2 mm (3.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 105     | 6     | ||
No. & Size Wire     | 1 - #15     | 2 - #14.5     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
365.8 mm (14.4 inch)     |
304.8 mm (12.0 inch)     |
||
Copper Weight     | 3.9 kg (8.5 lb)     |
3.4 kg (7.5 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #02 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram A |
5N-9432 Generator
Show/hide table
MAIN STATOR AND ROTOR WINDING DATA     | ||||
ITEM     | STATOR     | ROTOR (RANDOM WOUND)     |
ROTOR (FORM WOUND)     |
|
Stack Height     | 424.2 mm (16.7 inch)     |
431.8 mm (17.0 inch)     |
-     | |
Slots     | 54 (1)     | -     | -     | |
Coil Throw     | 1 - 12     | -     | -     | |
Turns/Coil     | 1     | -     | -     | |
Turns/Pole     | -     | 160     | -     | |
No. & Wire Size     | 30 - #13     | 1 - #7 sq     | -     | |
Mean Length Turn     | 1648.5 mm (64.9 inch)     |
-     | -     | |
Copper Weight     | 64.2 kg (141.5 lb)     |
98.4744 kg (217.1 lb)     |
-     | |
Inside Connection (1)     | 4 in Series     | 4 in Series     | -     | |
Line Leads (No. & Size)     | 20 - #00     | -     | -     | |
Terminal bolt size     | 3/8 inch     | -     | -     | |
Low Voltage connected line resistance at 25 ° C (77 ° F)     |
.0131     | -     | -     | |
Field lead resistance at 25 ° C (77 ° F)     |
-     | 1.17     | -     | |
EXCITER WINDING DATA     | ||||
Exciter Frequency (Hz)     | 90 Hz     | |||
Exciter Poles     | 6     | |||
ITEM     | STATOR (FIELD)     | ROTOR (ARMATURE)     | ||
Stack Length     | 127.0000 mm (5.0 inch)     |
127.0000 mm (5.0 inch)     |
||
Coils/Group     | 1     | 2     | ||
Slots (Coils)     | 6     | 36     | ||
Turns (Coils)     | 250     | 6     | ||
No. & Size Wire     | 1 - #18     | 2 - #15     | ||
Coil Throw     | 1 - 2     | 1 - 6     | ||
Mean Length Turn (Calculated)     |
464.8 mm (18.3 inch)     |
406.4 mm (16.0 inch)     |
||
Copper Weight     | 5.2 kg (11.5 lb)     |
2.7 kg (5.9 lb)     |
||
Insulation     | Heavy Nytherm     | |||
Connection (2)     | Series     | 2 Parallel Star     | ||
Line Leads     | #14 965.2 mm (38.0 inch)     |
#10 152.4 mm (6.0 inch)     |
Show/hide table
( 1 ) | Wind 6 coil groups with 4 coils per group, wind 6 coil groups with 5 coils per group. Put coil groups in stator (4,5,4,5-etc). |
( 1 ) | See Specifications, "Connection Diagrams for Main Stator and Main Rotor" Connection Diagram #36 |
( 2 ) | See Specifications, "Connection Diagrams for Exciter" Connection Diagram H |
Note: Wires 20, 22, and 24 are brought out as tap connections between the 9th and 10th coil (9 turns from T0).
Caterpillar Information System:
G3408 and G3412 Engines Product Description
3500B Engines Exhaust Manifold
G3406 Engine Product Description
G3408 and G3412 Engines Safety Messages
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for <B>5N-8891</B> Generator through <B>5N-8911</B> Generator
3126E Engine for Combat and Tactical Vehicles Flash Programming
3034 Industrial Engine Governor - Remove
G3406 Engine Refill Capacities
3126B and 3126E On-highway Engines Sensors and Electrical Connectors
325, 325B and 325L Excavators Travel Motor
SR4 HV and SR4B HV Generators Fire Prevention and Explosion Prevention
G3408 and G3412 Engines Valve Data Sheet
3412 Generator Set Engines Basic Engine
325, 325B and 325L Excavators Travel Counterbalance Valve
3034 Industrial Engine Governor - Install
C-10 and C-12 Engines Model View Illustrations
3500B Engines for Caterpillar Built Power Modules Engine Oil Pan
G3516B Engines MID 036 - CID 0017 - FMI 06 Fuel Shutoff Valve short to ground
G3516B Engines MID 036 - CID 0017 - FMI 12 Fuel Shutoff Valve malfunction
G3516B Engines MID 036 - CID 0041 - FMI 03 8 Volt DC Supply short to +batt
G3516B Engines MID 036 - CID 0041 - FMI 04 8 Volt DC Supply short to ground
2000/04/01 Use the Proper Electronic Troubleshooting Guide {1000}
325, 325B and 325L Excavators Track Roller (Single Flange)
2000/07/01 Improvements to Turbocharger Water Lines Groups Help Prevent Leaks {1052, 1380}