XQ400 Power Module Caterpillar


Voltage Regulators

Usage:

XQG400 AL5

------ DANGER! ------

DANGER: Shock/Electrocution Hazard-Do not operate this equipment or work on this equipment unless you have read and understand the instructions and warnings in the Operation and Maintenance Manual. Failure to follow the instructions or heed the warnings will result in serious injury or death.


------ WARNING! ------

Personal injury or death can result from high voltage.

When power generation equipment must be in operation to make tests and/or adjustments, high voltage and current are present.

Improper test equipment can fail and present a high voltage shock hazard to its user.

Make sure the testing equipment is designed for and correctly operated for high voltage and current tests being made.

When servicing or repairing electric power generation equipment:

  • Make sure the unit is off-line (disconnected from utility and/or other generators power service) , and either locked out or tagged DO NOT OPERATE.

  • Remove all fuses.

  • Make sure the generator engine is stopped.

  • Make sure all batteries are disconnected.

  • Make sure all capacitors are discharged.

Failure to do so could result in personal injury or death. Make sure residual voltage in the rotor, stator and the generator is discharged.


------ WARNING! ------

Accidental engine starting can cause injury or death to personnel working on the equipment.

To avoid accidental engine starting, disconnect the battery cable from the negative (−) battery terminal. Completely tape all metal surfaces of the disconnected battery cable end in order to prevent contact with other metal surfaces which could activate the engine electrical system.

Place a Do Not Operate tag at the Start/Stop switch location to inform personnel that the equipment is being worked on.


The voltage regulator is located in the enclosure for the control panel or in the terminal box on the generator.



Illustration 1g03827032
The voltage regulator is located in the terminal box on the generator or in the enclosure for the control panel.


Illustration 2g03798553

The generator set may include one of the following voltage regulators.

Integrated Voltage Regulator (IVR)

The Integrated Voltage Regulator (IVR) provides excitation current to the generator. The IVR is controlled by the IVR function in the EMCP4. The IVR function allows the EMCP4 to control the generator voltage, optimize transient performance, and provide feature specification.

The excitation module may interface with any of the following excitation systems: Self Excitation (SE), Internal Excitation (IE) and Permanent Magnet (PMG) excitation systems.

For additional information about the IVR, see Application and Installation, LEBE0006, and Special Instruction, REHS9106.



Illustration 3g03712568
Excitation Module 10 (EM10)
(1) Connector P3
(2) Connector P2
(3) Connector P4

EMCP IVR Connection

To regulate the generator terminal voltage, the EMCP communicates the desired excitation command to the excitation module through a pulse width modulation (PWM) signal. A twisted pair of shielded cable must be used for the communication link. Table 1 details the connections to be made between the EMCP and Excitation Module.

Table 1
EMCP 4.1 and EMCP 4.2 Connections to Excitation Module (70-pin connector) 
EMCP 4.1 and EMCP 4.2 70-Pin Connector  Excitation Module 3-Pin Connector 
Digital Output #2 / IVR CS+  68  CS+  P3-2 
Battery negative splice  60 or 65  CS-  P3-3 
Battery negative splice  60 or 65  Shield  P3-1 
EMCP 4.3 and EMCP 4.4 Connections to Excitation Module (120-pin connector) 
EMCP 4.3 and EMCP 4.4 120-Pin Connector  Excitation Module 3-Pin Connector 
PWM Output #2 Positive  28  CS+  P3-2 
PWM Output #2 Negative  CS-  P3-3 
Shield  19  Shield  P3-1 

Table 2 provides information on the technical specification of the EM10 and EM15 modules. Selection of the appropriate module must be determined by the following:

  • Nominal and maximum generator excitation current at full load (standby 0.8 PF).

  • The maximum AC voltage input.

Table 2
EM10 and EM15 Technical Specifications 
  EM10  EM15 
Compatible Generator Excitation Types  Permanent Magnet (PM) Self-Excitation (SE) Internal Excitation (IE/AREP)(1) 
Nominal Field Current Output  6A  7A 
Maximum (forcing) Field Current Output  10A  15A 
Maximum AC Voltage Input  180Vms  240Vms 
(1) Internal Excitation (IE is also referred to as “Auxiliary Regulation Excitation Principle”(AREP)

IVR Excitation Module Connections

The EM10 and EM15 excitation modules have three plug type multiple-pin connectors. The connectors are labeled P2, P3, and P4 as shown in illustration 3. Table 3 describes the signal and function of each connector pin.

Table 3
Excitation Module Connections 
Terminal  Label  Signal/Function 
P2-1  F+  Exciter Field Positive 
P2-2  F-  Exciter Field Negative 
P3-1  Shield  Excitation Command Control Signal Shield 
P3-2  CS+  Excitation Command Control Signal Positive 
P3-3  CS-  Excitation Command Control Signal Negative 
P4-1  X2  Excitation Power Supply Input X2 
P4-2  Z1  Excitation Power Supply Input Z1 
P4-3  X1  Excitation Power Supply Input X1 
P4-4  Z2  Excitation Power Supply Input Z2 

Note: The X2 and Z1 connections are internally linked within the excitation module. The link provides a point of common connection for the auxiliary windings where an AREP or IE excitation supply is available. Also, the X2 and Z1 connections may be linked externally to the excitation module. Only three connections (X1, X2, and Z2) are needed for the EM. Refer to Systems Operation/Test and Adjust/Troubleshooting, UENR1209, "Integrated Voltage Regulator Connections" for excitation module wiring connections. The wiring diagrams are for self-excitation (shunt), auxiliary windings (AREP/IE), and permanent magnet (PM) configurations.

The voltage regulator knee frequency must be configured for your specific package requirements. The knee frequency for 50 Hz operation will usually be between 48.0 and 49.8 Hz. For 60 Hz operation, the parameter must be set between 58.0 to 59.8 Hz.

Refer to Illustration 2 for an example under-frequency roll-off (loading) profile.



Illustration 4g03487998
Under-frequency (loading) profile slope1 = 1.0 V/Hz, slope2 = 2.0 V/Hz

Caterpillar Information System:

C4.4 Generator Sets Fuel System Secondary Filter - Replace
3412 Generator Set Engine Shutdown Occurs Intermittently
C4.4 Generator Sets Engine Oil and Filter - Change
794 AC Off-Highway Truck Brakes, Indicators and Gauges - Test
3412 Generator Set Engine Overspeeds
3412 Generator Set Engine Misfires, Runs Rough or Is Unstable
C4.4 Generator Sets Generator Operation
3412 Generator Set Engine Does Not Crank
3412 Generator Set Engine Cranks but Does Not Start
3412 Generator Set Coolant Temperature Is Low
2015/02/20 Top End and Major Overhaul Foundational Kits Are Available for 3516 Electric Power Engines {1000}
2015/02/20 Top End and Major Overhaul Foundational Kits Are Available for 3508 Petroleum Engines {1000}
C9.3 Marine Engines Pressure Sensor (Auxiliary)
C9.3 Marine Engines Piston and Rings
C8.7 Marine Engine Engine Support (Front) - Remove and Install
C8.7 Marine Engine Engine Support (Rear) - Remove and Install
G3612 and G3616 Engines Crankcase Pressure Sensor - Remove and Install
3512E Tier 4 Final Engines for Land Electric Drilling Fuel Rail Pressure Problem
XQC1200 and XQC1600 Power Modules Crankcase Pressure Sensor - Remove and Install
2015/02/27 A New Method to Prevent Water from Being Trapped in Fuel Heaters is Available {1250, 1296}
C8.7 Marine Engine Water Temperature Regulator - Remove and Install
New Sensor Kit Is Now Used On Certain Cat® Products {1000, 1439, 1718, 1906, 1907, 1912, 1917, 1923, 1924, 1925, 1929, 7400, 7422} New Sensor Kit Is Now Used On Certain Cat® Products {1000, 1439, 1718, 1906, 1907, 1912, 1917, 1923, 1924, 1925, 1929, 7400, 7422}
C18 Generator Set Walk-Around Inspection
C18 Generator Set Water Pump - Inspect
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.