Coolant Temperature Is Low
Use this procedure in order to troubleshoot a low coolant temperature.
- Faulty water temperature regulator
- Long idle periods
- Light loads
Show/hide table
Troubleshooting Test Steps | Value | Results |
---|---|---|
1. Check for a Faulty Water Temperature Regulator. A. A regulator that is stuck open can cause overcooling. Overcooling also occurs when the water temperature regulator is stuck between the open and closed position. B. Coolant leaks that are around the water temperature regulator can cause overcooling. |
Water Temperature Regulator |
Result : The water temperature regulator is OK. Proceed to Test Step 2. Result : The water temperature regulator is NOT OK. Repair : Replace the water temperature regulator. If the problem is not resolved, proceed to Test Step 2. |
2. Check for Light Engine Loads. |
Engine Load |
Result : The engine load is light for the applied application. Repair : Increase the engine load to minimum load for the applied application. |
Caterpillar Information System:
2015/02/20 Top End and Major Overhaul Foundational Kits Are Available for 3516 Electric Power Engines {1000}
2015/02/20 Top End and Major Overhaul Foundational Kits Are Available for 3508 Petroleum Engines {1000}
3412 Generator Set Coolant Temperature Is High
3412 Generator Set Boost Pressure Is Low
G3612 and G3616 Engines Air Inlet Elbow - Remove and Install
3412 Generator Set Boost Pressure Is High
3412 Generator Set Acceleration Is Poor or Throttle Response Is Poor
C9.3 Marine Engines Exhaust Temperature Sensor
C18 Generator Set Generator Start-up Checklist
C18 Generator Set Refill Capacities
3516C Marine Engines Crankshaft - Remove and Install
G3500H 60Hz Generator Sets Starting Motor - Inspect
3412 Generator Set Engine Cranks but Does Not Start
3412 Generator Set Engine Does Not Crank
C4.4 Generator Sets Generator Operation
3412 Generator Set Engine Misfires, Runs Rough or Is Unstable
3412 Generator Set Engine Overspeeds
794 AC Off-Highway Truck Brakes, Indicators and Gauges - Test
C4.4 Generator Sets Engine Oil and Filter - Change
3412 Generator Set Engine Shutdown Occurs Intermittently
C4.4 Generator Sets Fuel System Secondary Filter - Replace
XQ400 Power Module Voltage Regulators
C9.3 Marine Engines Pressure Sensor (Auxiliary)
C9.3 Marine Engines Piston and Rings