UPSB220 Uninterruptible Power Supply Caterpillar


UPS Isolation

Usage:

UPSB 220 JFA

------ DANGER! ------

Working with electrical circuits is hazardous. Bodily contact with electrical potential will cause personal injury or death. Ensure that personnel are trained in proper operating procedures in order to ensure safe operation.



NOTICE

Installation compliance with all local, state, and regional electrical codes and ordinances must be completed by qualified personnel that are trained and certified. Operation of the UPS should only be carried out by trained personnel. The compliance also includes the operations that are related to the battery cabinet.


Single UPS

The instructions in this section allow the user to perform the following:

  • Isolate the UPS from the source of electricity.

  • Supply the load directly by the normal or the bypass AC source.




Illustration 1g02361044

(1) Rectifier/charger light

(2) Battery light

(3) Static-bypass light

(4) Inverter light

(5) Load light

(6) Buzzer

(7) Inverter ON button

(8) Inverter OFF button

(9) Scroll Up/Increment key

(10) Scroll Down/Decrement key

(11) Validate key

(12) Main Menu key

(13) Voltage Measurement key

(14) Current Measurement key

(15) Frequence and Power Measurement key

(16) Anomaly light

(17) Primary Message key

(18) Battery key

(19) Forced-transfer

(20) Alarm reset

(21) Buzzer reset

(22) Display




Illustration 2g02359656

(7) Inverter ON button

(8) Inverter OFF button

(23) "Q3BP"

(24) "Q5N"

(25) "Q4S"

(26) "QF1"

(27) "Q1"

  1. Shut down the UPS by pressing the OFF button (8) for 3 seconds.

    The load is no longer protected by the UPS.

  1. Close bypass switch "Q3BP" (23) .

  1. Open isolating switch "Q5N" (24) .

  1. Open isolating switch "Q4S" (25) .

  1. Open isolating switch "QF1" (26) .

  1. Open isolating switch "Q1" (27) .

    The UPS is powered down once the capacitors have discharged.

    Note: Wait a minimum of 5 minutes for the capacitors to discharge. Ensure that the capacitors are at zero energy prior to performing maintenance within the cabinets.

  1. Wait until the display and LED lights go off.

The UPS system is no longer protecting the electrical load. The UPS continues to be supplied with AC power. Maintenance or servicing for the UPS can now be carried out.

------ WARNING! ------

Bodily contact with electrical potential can cause bodily injury or death.

To avoid the possibility of injury or death, ensure that the main power supply has been disconnected before performing any maintenance or removing any modules.

----------------------

Parallel UPS With External Bypass Cabinet


NOTICE

Caution must be taken with parallel units with external maintenance bypass.

The following information applies when "CB1" (MBP) is closed and "CB2" (UPS Isolation) is open.

During maintenance operation, each UPS display will show the message, "LOAD PROTECTED", when the UPS is placed in on-line mode.

In the on-line mode, the critical load is not protected because the power to the load is supplied by the maintenance bypass power.





Illustration 3g02359836

(7) Inverter ON button

(8) Inverter OFF button

(23) "Q3BP"

(23a) "Q3BP External Bypass Unit"

(24) "Q1"

(25) "QF1"

(26) "Q5N"

(26a) "Q5N External Bypass Unit"

(27) "Q1"

The instructions in this section allow the user to perform the following:

  • Isolate the Parallel UPS System from the source of electricity

  • Supply the load directly by the normal or the bypass AC source

  1. Shut down all of the UPS by pressing the OFF buttons (8) for 3 seconds.

  1. Close the parallel system bypass switch "Q3BP" (23a) on the external bypass unit.

  1. Open the parallel system output isolation switch "Q5N" (26a) on the external bypass unit.

  1. Open isolating switch "Q1" (24) ans (27) on each of the UPS units.

  1. Open battery isolating switch "QF1" (25) on each of the UPS units.

  1. Open output isolating switch "Q5N" (26) on each of the UPS units.

The UPS system is no longer protecting the electrical load. The UPS continues to be supplied with AC power. Maintenance or servicing for the UPS system can now be carried out.

------ WARNING! ------

Bodily contact with electrical potential can cause bodily injury or death.

To avoid the possibility of injury or death, ensure that the main power supply has been disconnected before performing any maintenance or removing any modules.

----------------------

Caterpillar Information System:

TA19 Transmission Pump Drive - Remove
UPSB220 Uninterruptible Power Supply Battery Service
C27 and C32 Engines Engine Oil Pan - Remove and Install
C32 Generator Set Product Description
C3.4B Engines for Caterpillar Built Machines Introduction
C32 Generator Set Safety Messages
C32 Generator Set Model View Illustrations
2011/02/24 A New Bracket Is Now Used on Certain C32 Marine Engines {1059, 1154}
Installation of CAESultra for Landfill Compactors, Motor Graders, Wheel Dozers, and Wheel Loaders{1408, 7009, 7010, 7338, 733T, 7490, 7604} Installation of CAESultra for Landfill Compactors, Motor Graders, Wheel Dozers, and Wheel Loaders{1408, 7009, 7010, 7338, 733T, 7490, 7604}
UPSB220 Uninterruptible Power Supply Battery Circuit Breaker Installation
UPSB220 Uninterruptible Power Supply Temperature Monitor Installation
C27 Petroleum Engine Cylinder Head - Install
CG137-08 and CG137-12 Industrial Engines Diagnostic Trouble Codes
312E, 312F, 313F, 316E, 316F, 318E, 318F, 320E, 320F, 323E, 323F, 324E, 325F, 326F, 329E, 329F, 330F, 335F, 336E, 336F, 340F, 349E, 349F, 352F, 374F and 390F Excavators and 336E MHPU and 349E MHPU Mobile Hydraulic Power Units Air Conditioning and Hea Air Conditioning Performance - Test
3512B Oil Well Servicing Engines Exhaust Shield
C3.4B Engines for Caterpillar Built Machines Basic Engine
2011/05/16 Special Instruction, REHS5043, "Installation of the Water-Cooled Throttle for G3500C and G3500E Generator Set Engines Is Available" {1265}
CG137-08 and CG137-12 Industrial Engines Engine Monitoring Parameters
C3.4B Engines for Caterpillar Built Machines Lubrication System
C3.4B Engines for Caterpillar Built Machines Engine Oil Pressure - Test
3512B Oil Well Servicing Engines Air Shutoff
C3.4B Engines for Caterpillar Built Machines Cooling System - Check
C3.4B Engines for Caterpillar Built Machines Cooling System - Test
C3.4B Engines for Caterpillar Built Machines Electrical System
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.