UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Caterpillar


Diode Rectifier

Usage:

ES12F CZE



Illustration 1g01281486

Location (3-Phase Diode Rectifier)

(1) 3-Phase Diode Rectifier




Illustration 2g01281488

(1) 3-Phase Diode Rectifier

The 3-phase Diode Rectifier is located on the upper left panel in the Inverter Cabinet beneath the Neutral Bus Fuses.

The Diode Rectifier is part of the DC Bus Precharge Circuit. The Diode Rectifier converts the incoming AC power to DC. This conversion ensures one-way current flow through the pre-charge circuit.

Removal

  1. Perform steps in the Systems Operation, Testing and Adjusting, "Internal Component Preremoval Steps (Inverter Cabinet)" in order to de-energize the system and gain access to internal components.

  1. Remove all seven wires from the rectifier using a hex key.

  1. Remove the two screws that hold the rectifier to the cabinet panel.

Installation

  1. Position the rectifier on the upper left panel of the cabinet.

  1. Attach the rectifier using two screws.



    Illustration 3g01281490

    3-Phase Diode Rectifier Wire Connections

  1. Connect the seven wires to the rectifier.

    Each wire is labeled as to its location.

    Refer to Illustration 3.

  1. Torque the hex bolts appropriately.

Caterpillar Information System:

Obtaining Oil Sample for Analysis {1302, 1348, 3030, 3080, 3278, 4011, 4070, 5050, 5056, 5095, 7542} Obtaining Oil Sample for Analysis {1302, 1348, 3030, 3080, 3278, 4011, 4070, 5050, 5056, 5095, 7542}
2006/06/01 Improved Seal on Filters {1308}
Reset the Real Time Clock After Maintenance for On-Highway Truck Engines{1900, 1901} Reset the Real Time Clock After Maintenance for On-Highway Truck Engines{1900, 1901}
C175-16 Engine for 795F Series AC Off-Highway Trucks Crankshaft - Type 1
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Current Transformer (Inverter Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Fuse Switch
G3508, G3512 and G3516 Engines Camshaft - Install
G3508, G3512 and G3516 Engines Camshaft - Remove
120M, 12M, 140M and 160M Motor Graders Drive Chain - Check
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys System Fuse (Inverter Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Digital Gate Logic PWA
Troubleshooting the Flywheel Housing for Failures of the Bolts{1157, 1157} Troubleshooting the Flywheel Housing for Failures of the Bolts{1157, 1157}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys General Purpose Interface PWA (Inverter Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Thermistor (Inverter Cabinet)
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Transformer (T7)
Set and Test the Overspeed Verification Switch{7410, 7427, 7490} Set and Test the Overspeed Verification Switch{7410, 7427, 7490}
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Fan (Inverter Cabinet)
C4.4 Industrial Engine Connecting Rod - Inspect
C175-16 Locomotive Engine Connecting Rod and Main Bearing Journals
C175-16 Locomotive Engine Crankshaft Wear Sleeves and Seals
C4.4 Industrial Engine Cylinder Head - Inspect
UPS 1000S/ UPS 1200S Uninterruptible Power Supplys Internal Component Preremoval Steps (Flywheel Cabinet)
C13, C15, and C18 Tier 4 Final Engines Cylinder Block
C13, C15, and C18 Tier 4 Final Engines Connecting Rod