The main purpose for the digital inputs is to add additional monitoring capabilities for the engine or the generator. The inputs can be configured by navigating to the "EVENT I/P FUNCTIONS" parameter under the "SETPOINTS" menu.
Note: There are eight digital inputs on EMCP 3.2 and EMCP 3.3. There are six digital inputs on EMCP 3.1. On all three levels of controls, the first and second digital inputs are dedicated and cannot be programmed.
The digital inputs of the EMCP 3 are tied to an internal pull-up resistor inside the control. Therefore, if there is no connection to a digital input, then the digital input will read as a logical high. A ground or battery negative input should be wired to each EMCP 3 digital input. If an active high configuration is desired, then the ground or battery negative input should be wired through a normally closed switch. If an Active Low configuration is desired, then the ground or battery negative input should be wired through a normally open switch.
Digital input #1 is dedicated for Emergency Stop and digital input #2 is dedicated for Remote Initiate. The other four or six inputs can be configured to trigger alarms or shutdowns in the EMCP 3. In the EMCP 3 software, digital inputs 3 through 8 are linked to functions that are called "EVENT INPUT FUNCTIONS". In the EMCP 3.1 software, digital inputs 3 through 6 are linked to functions that are called "EVENT INPUT FUNCTIONS". Digital inputs #1 and #2 are dedicated inputs. Therefore, digital input #3 is linked to event input function #1, digital input #4 is linked to event input function #2, and so on. Refer to Illustration 1.
Illustration 1 | g01228372 |
Digital Input #1 - Digital input #1 is used for "Emergency Stop". The input must be wired to battery negative through an emergency stop switch. The input can be set to activate on an active high (normally closed contact) or an active low (normally open contact). If the operator wants to enable the "Reduced Power Mode", then the emergency stop must be configured for active low.
Reference: Testing and Adjusting , "Electronic Control Module (Generator Set) - Configure"
Activating the emergency stop input will either cause the generator set to stop immediately or will prevent the generator set from starting. Once digital input #1 goes active, the engine will not start until the event is reset.
Reference: System Operation , "Event Resetting"
Digital Input #2 - Digital input #2 is used for remotely starting and stopping the generator set. The input must be wired to battery negative through a "Remote Initiate" switch. The input can be set to activate on an active high (normally closed contact) or an active low (normally open contact). If the input is active, and the EMCP 3 is in the "AUTO" mode, then the engine will attempt to start and run. Once the input becomes inactive, the engine will enter into cool down (if programmed to do so) and will then stop.
All remaining inputs can be configured.
Reference: Call outs that are used in this section can be found on the EMCP 3 control panel in Systems Operation, "Electronic Control Module (Generator Set)".
The keys listed below are used for programming the EMCP 3 and navigating within the menu structure.
Reference: Refer to Systems Operation, "Electronic Control Module (Generator Set)" for an explanation of the function keys and the navigation keys. The function keys include the enter and escape keys. The navigation keys include the scroll left, scroll right, scroll up, and scroll down) keys.
Escape (9) - Used to navigate up (backward) through the menu structure and to back out of data entry screens during set point programming.
Enter key (10) - Select a highlighted menu item or save a programmed value.
Scroll Right key (11) - During numeric data entry, choose the digit to edit. During certain set point adjustments, select or deselect a check box.
Scroll Down key (12) - Move down through the main menu or navigate within a list in order to highlight one of the items. Also used to decrement digits (0-9).
Scroll Up key (13) - Move up through the main menu or navigate within a list in order to highlight one of the items. Also used to increment digits (0-9).
Scroll Left key (14) - During numeric data entry, choose the digit to edit. During certain set point adjustments, select or deselect a check box.
Programming the Active State of the Digital Input
Reference: For an example of programming a digital input for a fuel level switch, see Systems Operation, "Setpoint Programming".
In order to program the "Active State" of the digital input, perform the following steps:
- On the EMCP 3, navigate to the digital inputs menu as follows.
- At the "MAIN MENU" use the arrow keys and enter key to select "CONFIGURE".
- Use the arrow keys and enter key to select "SETPOINTS".
- Use the arrow keys and enter key to select "I/O".
- Use the arrow keys to select "DIGITAL INPUTS".
- Using the navigation keys, select the digital input that is to be programmed and press the enter key. The current configuration will be displayed.
- Press the enter key a second time. The current configuration will be highlighted.
- Use the navigation keys in order to change the current configuration to the desired setting.
- Press the enter key in order to save the setting.
Programming the Event Input Functions
Note: Each event input function corresponds to a specific digital input. The event input function #1 corresponds to digital input #3. The event input function #2 corresponds to digital input #4 and so on. Refer to Illustration 1.
Note: The possibility exists to set the event input function to a value for which no event response configuration exists. Examples of such events are high oil pressure warning or high oil pressure shutdown. If the event is made active and the event does occur, then no events will be triggered since no event response configuration exists.
- Perform the following steps in order to navigate to the EVENT I/P FUNCTIONS menu to program the "Event Input" functions.
- At the "MAIN MENU" use the arrow keys and enter key to select "CONFIGURE".
- Use the arrow keys and enter key to select "SETPOINTS".
- Use the arrow keys and enter key to select "EVENTS".
- Use the arrow keys and enter key to select "EVENT I/P FUNCTIONS".
- Use the arrow keys and enter key to set the "Active State". The active state should always be set to active "HIGH".
- Use the arrow keys and enter key to set the "Time Delay". Press the enter key to select "Time Delay" and enter the desired value using the navigation keys.
- Set the "Suspect Parameter Number" (SPN). Press the enter key in order to choose the SPN. The available parameters are listed in Table 1.
Show/hide table
Table 1 Available Parameters Pressures Air Filter Differential Pressure
Engine Oil Pressure
Fire Extinguisher Pressure
Fuel Filter Differential Pressure
Oil Filter Differential Pressure
Starting Air Pressure
Gas PressureTemperatures Ambient Air Temperature
Engine Coolant Temperature
Engine Oil Temperature
Exhaust Temperature
Rear Bearing Temperature
Right Exhaust Temperature
Left Exhaust Temperature
Generator Winding 1 Temperature
Generator Winding 2 Temperature
Generator Winding 3 TemperatureLevels Engine Coolant Level
Engine Oil Level
Fuel Level
External Tank Fuel LevelOther Air Damper Closed
ATS in Normal Position
ATS in Emergency Position
Battery Charger Failure
Battery Charging System Voltage
Battery Voltage
Fuel Leak Detected
Custom Event
Earth Fault
Earth Leakage
Generator Frequency
Generator Voltage
Generator Current
Generator Power
Generator Circuit Breaker Closed
Utility Breaker Closed
Generator Circuit Breaker Open
Utility Breaker Open
Loss of Utility
Utility to Generator Transfer Failure
Generator to Utility Transfer Failure
Engine Inlet Manifold Charge Combustion
EPS Supplying Load
Custom Event(1)Show/hide table(1) For the Input Function setpoint value name "Custom Event", the corresponding setpoint value will be dictated by the information in Table 2. Show/hide tableTable 2 Custom Event Set Point Value for Event Input Functions cVue Block Block Instance Set Point Value Description 1 701 Custom Event (Instance 1 only) 2 702 Custom Event (Instance 2 only) 3 703 Custom Event (Instance 3 only) 4 704 Custom Event (Instance 4 only) 5 705 Custom Event (Instance 5 only) 6 706 Custom Event (Instance 6 only) 7 707 Custom Event (Instance 7 only) 8 708 Custom Event (Instance 8 only) - Set the "Failure Mode Identifier" (FMI). The following identifiers are available:
- High warning (example: High Temperature Warning)
- Low warning (example: Low Temperature Warning)
- High shutdown
- Low shutdown
- Status (Condition Exists)