EMCP3 Caterpillar


Digital Input Programming

Usage:

G3306 07Y
There are two separate procedures that must be performed in order to program the EMCP 3 digital inputs. The first procedure involves programming the active state of the input as either "Active High" or as "Active Low". The second procedure involves programming the event input functions.

Digital Inputs

The main purpose for the digital inputs is to add additional monitoring capabilities for the engine or the generator. The inputs can be configured by navigating to the "EVENT I/P FUNCTIONS" parameter under the "SETPOINTS" menu.

Note: There are eight digital inputs on EMCP 3.2 and EMCP 3.3. There are six digital inputs on EMCP 3.1. On all three levels of controls, the first and second digital inputs are dedicated and cannot be programmed.

The digital inputs of the EMCP 3 are tied to an internal pull-up resistor inside the control. Therefore, if there is no connection to a digital input, then the digital input will read as a logical high. A ground or battery negative input should be wired to each EMCP 3 digital input. If an active high configuration is desired, then the ground or battery negative input should be wired through a normally closed switch. If an Active Low configuration is desired, then the ground or battery negative input should be wired through a normally open switch.

Digital input #1 is dedicated for Emergency Stop and digital input #2 is dedicated for Remote Initiate. The other four or six inputs can be configured to trigger alarms or shutdowns in the EMCP 3. In the EMCP 3 software, digital inputs 3 through 8 are linked to functions that are called "EVENT INPUT FUNCTIONS". In the EMCP 3.1 software, digital inputs 3 through 6 are linked to functions that are called "EVENT INPUT FUNCTIONS". Digital inputs #1 and #2 are dedicated inputs. Therefore, digital input #3 is linked to event input function #1, digital input #4 is linked to event input function #2, and so on. Refer to Illustration 1.



Illustration 1g01228372

Digital Input #1 - Digital input #1 is used for "Emergency Stop". The input must be wired to battery negative through an emergency stop switch. The input can be set to activate on an active high (normally closed contact) or an active low (normally open contact). If the operator wants to enable the "Reduced Power Mode", then the emergency stop must be configured for active low.

Reference: Testing and Adjusting , "Electronic Control Module (Generator Set) - Configure"

Activating the emergency stop input will either cause the generator set to stop immediately or will prevent the generator set from starting. Once digital input #1 goes active, the engine will not start until the event is reset.

Reference: System Operation , "Event Resetting"

Digital Input #2 - Digital input #2 is used for remotely starting and stopping the generator set. The input must be wired to battery negative through a "Remote Initiate" switch. The input can be set to activate on an active high (normally closed contact) or an active low (normally open contact). If the input is active, and the EMCP 3 is in the "AUTO" mode, then the engine will attempt to start and run. Once the input becomes inactive, the engine will enter into cool down (if programmed to do so) and will then stop.

All remaining inputs can be configured.

Function and Navigation Keys

Reference: Call outs that are used in this section can be found on the EMCP 3 control panel in Systems Operation, "Electronic Control Module (Generator Set)".

The keys listed below are used for programming the EMCP 3 and navigating within the menu structure.

Reference: Refer to Systems Operation, "Electronic Control Module (Generator Set)" for an explanation of the function keys and the navigation keys. The function keys include the enter and escape keys. The navigation keys include the scroll left, scroll right, scroll up, and scroll down) keys.

Escape (9) - Used to navigate up (backward) through the menu structure and to back out of data entry screens during set point programming.

Enter key (10) - Select a highlighted menu item or save a programmed value.

Scroll Right key (11) - During numeric data entry, choose the digit to edit. During certain set point adjustments, select or deselect a check box.

Scroll Down key (12) - Move down through the main menu or navigate within a list in order to highlight one of the items. Also used to decrement digits (0-9).

Scroll Up key (13) - Move up through the main menu or navigate within a list in order to highlight one of the items. Also used to increment digits (0-9).

Scroll Left key (14) - During numeric data entry, choose the digit to edit. During certain set point adjustments, select or deselect a check box.

Programming the Active State of the Digital Input

Reference: For an example of programming a digital input for a fuel level switch, see Systems Operation, "Setpoint Programming".

In order to program the "Active State" of the digital input, perform the following steps:

  1. On the EMCP 3, navigate to the digital inputs menu as follows.

    1. At the "MAIN MENU" use the arrow keys and enter key to select "CONFIGURE".

    2. Use the arrow keys and enter key to select "SETPOINTS".

    3. Use the arrow keys and enter key to select "I/O".

    4. Use the arrow keys to select "DIGITAL INPUTS".

  2. Using the navigation keys, select the digital input that is to be programmed and press the enter key. The current configuration will be displayed.

  3. Press the enter key a second time. The current configuration will be highlighted.

  4. Use the navigation keys in order to change the current configuration to the desired setting.

  5. Press the enter key in order to save the setting.

Programming the Event Input Functions

Note: Each event input function corresponds to a specific digital input. The event input function #1 corresponds to digital input #3. The event input function #2 corresponds to digital input #4 and so on. Refer to Illustration 1.

Note: The possibility exists to set the event input function to a value for which no event response configuration exists. Examples of such events are high oil pressure warning or high oil pressure shutdown. If the event is made active and the event does occur, then no events will be triggered since no event response configuration exists.

  1. Perform the following steps in order to navigate to the EVENT I/P FUNCTIONS menu to program the "Event Input" functions.

    1. At the "MAIN MENU" use the arrow keys and enter key to select "CONFIGURE".

    2. Use the arrow keys and enter key to select "SETPOINTS".

    3. Use the arrow keys and enter key to select "EVENTS".

    4. Use the arrow keys and enter key to select "EVENT I/P FUNCTIONS".

  2. Use the arrow keys and enter key to set the "Active State". The active state should always be set to active "HIGH".

  3. Use the arrow keys and enter key to set the "Time Delay". Press the enter key to select "Time Delay" and enter the desired value using the navigation keys.

  4. Set the "Suspect Parameter Number" (SPN). Press the enter key in order to choose the SPN. The available parameters are listed in Table 1.

    Table 1
    Available Parameters 
    Pressures 
    Air Filter Differential Pressure
    Engine Oil Pressure
    Fire Extinguisher Pressure
    Fuel Filter Differential Pressure
    Oil Filter Differential Pressure
    Starting Air Pressure
    Gas Pressure 
    Temperatures 
    Ambient Air Temperature
    Engine Coolant Temperature
    Engine Oil Temperature
    Exhaust Temperature
    Rear Bearing Temperature
    Right Exhaust Temperature
    Left Exhaust Temperature
    Generator Winding 1 Temperature
    Generator Winding 2 Temperature
    Generator Winding 3 Temperature 
    Levels 
    Engine Coolant Level
    Engine Oil Level
    Fuel Level
    External Tank Fuel Level 
    Other 
    Air Damper Closed
    ATS in Normal Position
    ATS in Emergency Position
    Battery Charger Failure
    Battery Charging System Voltage
    Battery Voltage
    Fuel Leak Detected
    Custom Event
    Earth Fault
    Earth Leakage
    Generator Frequency
    Generator Voltage
    Generator Current
    Generator Power
    Generator Circuit Breaker Closed
    Utility Breaker Closed
    Generator Circuit Breaker Open
    Utility Breaker Open
    Loss of Utility
    Utility to Generator Transfer Failure
    Generator to Utility Transfer Failure
    Engine Inlet Manifold Charge Combustion
    EPS Supplying Load
    Custom Event(1) 
    (1) For the Input Function setpoint value name "Custom Event", the corresponding setpoint value will be dictated by the information in Table 2.

    Table 2
    Custom Event Set Point Value for Event Input Functions cVue Block 
    Block Instance  Set Point Value  Description 
    701  Custom Event (Instance 1 only) 
    702  Custom Event (Instance 2 only) 
    703  Custom Event (Instance 3 only) 
    704  Custom Event (Instance 4 only) 
    705  Custom Event (Instance 5 only) 
    706  Custom Event (Instance 6 only)  
    707  Custom Event (Instance 7 only)  
    708  Custom Event (Instance 8 only) 

  5. Set the "Failure Mode Identifier" (FMI). The following identifiers are available:

    • High warning (example: High Temperature Warning)

    • Low warning (example: Low Temperature Warning)

    • High shutdown

    • Low shutdown

    • Status (Condition Exists)

Caterpillar Information System:

EMCP3 Component Location
3500 Engines for Caterpillar Built Generator Sets Prelube Pressure Switch
2004/08/01 An Improved Injection Actuation Pressure Sensor Is Now Used {1925}
3412E, C30 and C32 Marine Engines Engine Oil Pump - Install
3508B Industrial Engines Engine Oil Temperature Sensor
3508B, 3512B, and 3516B High Displacement Generator Sets Walk-Around Inspection
3412E, C30 and C32 Marine Engines Engine Oil Pump - Assemble
C15 and C18 Industrial Engines Water Pump - Install
C15 and C18 Industrial Engines Water Pump - Remove
2004/08/01 A New Exhaust Seal is Used {1059}
C15 and C18 Industrial Engines Engine Oil Cooler - Install
C15 and C18 Industrial Engines Engine Oil Cooler - Remove
EMCP3 Spare Analog Input Programming
2004/08/01 An Improved Injection Actuation Pressure Sensor Is Now Used {1925}
C9 Marine Engines and C9 Marine Generator Sets Alternator and Regulator
C9 Marine Engines and C9 Marine Generator Sets Alternator and Regulator
Installation of the Uninterruptible Power Supply (Single-Module System){4480} Installation of the Uninterruptible Power Supply (Single-Module System){4480}
C9 Marine Engines and C9 Marine Generator Sets Electric Starting Motor
C15 and C18 Industrial Engines Water Temperature Regulator Housing - Remove and Install
C9 Marine Engines and C9 Marine Generator Sets Electric Starting Motor
C9 Marine Engines and C9 Marine Generator Sets Electric Starting Motor
2004/08/01 Maintenance Considerations for Engines in Landfill Applications {1000}
G3612 and G3616 Engines Product Description
TH31-C9I, TH31-C9P, TH31-C9T, TH35-C13I, TH35-C13T, TH35-C15I and TH35-C15T Petroleum Power Train Packages and TH31-E61 and TH35-E81 Petroleum Transmissions Transmission Bypass Valve (Transmission Oil Filter)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.