G3516B Engines Caterpillar


MID 036 - CID 0145 - FMI 03 12 Volt DC Power Supply short to +batt

Usage:

G3516B 7EZ
Conditions Which Generate This Code:

The Electronic Control Module (ECM) has been powered for at least five seconds. The 12 volt sensor supply voltage becomes greater than 14.2 V for at least one second.

System Response:

If the engine is running, the fuel is shut off. The shutdown output is activated. The code is logged.

Possible Performance Effect:

The engine is shut down or the engine will not start.

Troubleshooting:

Test Step 1. Perform the following diagnostic procedure: "Engine Speed/Timing Sensor"

Results:

  • OK - STOP

Caterpillar Information System:

Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.