Electronic Modular Control Panel II (EMCP II) Caterpillar


GSC CID 0268 - FMI 02

Usage:

3412C 4BZ
Conditions Which Generate This Code:

A portion of memory within the GSC stores the setpoints of important generator set conditions. The setpoints are listed below.

  • engine/generator setpoint programming OP5

  • spare input/output programming OP6

  • voltmeter/ammeter programming OP8

The GSC detects a CID 0268 FMI 02 when the setpoint data is invalid or the setpoint data is out of range. After detecting a CID 0268 FMI 02, the GSC sets the affected setpoints to the default value. For more information regarding setpoints and default values, see the topics that are listed below.

  • Systems Operation, "Engine/Generator Programming OP5"

  • Systems Operation, "Spare Input/Output Programming OP6"

  • Systems Operation, "Voltmeter/Ammeter Programming OP8"

The possible cause of a CID 0268 FMI 02 is electrical interference.

This procedure is designed to correct an active CID 0268 FMI 02 or the procedure is designed to correct an inactive CID 0268 FMI 02. Clear the diagnostic code from the fault log after troubleshooting is complete.

The GSC treats a CID 0268 FMI 02 as an alarm fault or the GSC treats a CID 0268 FMI 02 as a shutdown fault. The treatment depends on the particular setpoint with bad data. The ring gear teeth P09 setpoint and the engine overspeed P10 setpoints are treated as shutdown faults when the particular data is corrupted. All other setpoints are treated as alarm faults when the particular data is corrupted.

Note: Verify that the contact 6 to contact 9 jumper is NOT installed on the engine control switch (ECS). The contacts 6 to 9 jumper must be temporarily installed if the indicator for the shutdown fault is FLASHING. The GSC setpoints must be programmed in the OFF/RESET position when a shutdown fault is active. If the alarm for the fault indicator is FLASHING the GSC can be programmed with the ECS in the OFF/RESET position or the COOLDOWN/STOP position.

Test Step 1. CHECK THE SETPOINTS.

  1. View the setpoints that are stored in the memory of the GSC. See Systems Operation, "Engine/Generator Setpoint Viewing OP2-0".

  1. Also check Systems Operation, "Spare Input/Output Programming (OP6)" and Systems Operation, "Voltmeter/Ammeter Programming (OP8)".

  1. Compare the stored setpoints to the specified setpoints of the particular generator set.

Expected Result:

The stored setpoints and the specified setpoints should match.

Results:

  • OK - All the setpoints match. Start the engine. Check the upper display for a CID 0268 FMI 02. If the diagnostic code was inactive prior to performing this procedure, then these steps should have corrected the problem.

    Repair: If the diagnostic code remains active, The GSC may have failed. It is unlikely that the GSC has failed. Exit this procedure and perform this entire procedure again. If the problem remains, replace the GSC. See Testing And Adjusting, "EMCP Electronic Control (Generator Set) - Replace".

    Stop.

  • NOT OK - One or more of the setpoints do not match.

    Repair: Program the setpoints. See the following sections.

    • Systems Operation, "Engine/Generator Programming OP5"

    • Systems Operation, "Spare Input/Output Programming OP6"

    • Systems Operation, "Voltmeter/Ammeter Programming OP8"

    Stop.

Caterpillar Information System:

2002/05/01 The New 204-8041 Gauge Group Is Available To Measure The Top Ring Groove On Pistons {1214}
Electronic Modular Control Panel II (EMCP II) Display of Voltage or Current is Inaccurate
3126B and 3126E On-highway Engines 0111-03 Coolant Level voltage high (12)
Electronic Modular Control Panel II (EMCP II) Alarm Modules
3412E, C30 and C32 Marine Engines Piston Cooling Jets - Remove and Install
Electronic Modular Control Panel II (EMCP II) Fault Description
3054 and 3056 Marine Generator Set Engines Lubrication System
Electronic Modular Control Panel II (EMCP II) Engine Setpoint Verification OP9
Electronic Modular Control Panel II (EMCP II) Voltmeter/Ammeter Programming OP8
Electronic Modular Control Panel II (EMCP II) Hourmeter Programming OP7
3126B and 3126E Truck Engine Exhaust Particulate Filter Diagnostic Module - Test
3054 and 3056 Industrial and Generator Set Engines Connecting Rod
120H, 12H, 135H, 140H, 143H, 160H and 163H Motor Graders Electrical Connector - Inspect
Electronic Modular Control Panel II (EMCP II) EMCP Electronic Control (AC Transformer Box) - Replace
3412E, C30 and C32 Marine Engines Pistons and Connecting Rods - Remove
Electronic Modular Control Panel II (EMCP II) EMCP Electronic Control (Generator Set) - Replace
3500 Generator Set Engines Engine Oil Cooler Bypass and Cooling Jet Sequence Valves
3412E, C30 and C32 Marine Engines Pistons and Connecting Rods - Install
PMG3516 Power Module Fuel Metering Valve - Check - Raptor
3126B and 3126E On-highway Engines 0111-04 Coolant Level voltage low (12)
C7 and C9 On-Highway Engines Cooling Fan Circuit and A/C High Pressure Switch Circuit - Test
K65-12B Voltage Regulator Dimensions
3054 and 3056 Industrial and Generator Set Engines Engine Oil Filter Base
K65-12B Voltage Regulator Stability - Adjust
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.