Electronic Modular Control Panel II+ (EMCP II+) Caterpillar


Engine Does Not Shutdown (for MUI Engines)

Usage:

3412C 9EP
System Operation Description:

The engine does not shut down when a shutdown fault occurs.




Illustration 1g00798215

Fuel Control Relay For ETR Systems

Note: The setpoint P023 for the GSC+ must be correct for the engine application. Ensure that the setpointP023 is programmed correctly for the engine application before continuing with this procedure.

There are several possible causes for an engine that is not shutting down when a shutdown fault occurs.

  • Operator Error: The operating conditions of the generator may not be understood by the operator. Ensure that the condition is one that should cause an engine shutdown.

  • Programming Error-Fault Is Overridden Or Disabled: It is possible to program the GSC+ in order to override certain shutdown faults. An overridden shutdown fault will be treated as an alarm fault. The YELLOW fault alarm indicator will be FLASHING instead of the RED fault shutdown indicator. No fault indicators or fault codes are shown on the GSC+ if the GSC+ is programmed in order to disable a particular fault. In such cases, check any of the setpoints that are related to that particular fault. For example, a generator is not shutting down when an overvoltage fault occurs. Verify that the Overvoltage Shutdown Enable setpoint P104 is programmed correctly.

  • Programming Error - Setpoints Incorrect For Application Or Customer Needs: It is possible to program the GSC+ setpoints to a value that does not allow the situation to be recognized by the GSC+ as a shutdown condition. In this case, check the appropriate setpoints for correct values. For example, if the generator is not shutting down when a high coolant temperature condition occurs, make sure setpoint P015 (High Water Temperature Shutdown) is correct for the application.

  • Faulty Component: Some examples of faulty components that could prevent the GSC+ from shutting down the engine are: GSC+ and a broken or shorted harness wire. In this case, the GSC+ will be issuing a command to shut down the engine due to a diagnostic code, but the engine remains running.

Test Step 1. CHECK FOR DIAGNOSTIC CODES

  1. Check the GSC+ for a diagnostic code on the upper display.

Expected Result:

The GSC+ should show a diagnostic code on the upper display.

Results:

  • YES - The GSC+ shows a diagnostic code on the upper display.

    Repair: See theTesting and Adjusting section of this book for the diagnostic code that is displayed on the GSC+.

    Stop.

  • NO - The GSC+ does NOT show a diagnostic code on the upper display. Proceed to Test Step 2.

Test Step 2. CHECK THE YELLOW FAULT ALARM INDICATOR

  1. Check the display area of the GSC+ for the yellow fault alarm indicator.

Expected Result:

The yellow fault alarm indicator should be illuminated CONTINUOUSLY.

Results:

  • YES - The yellow fault alarm indicator is illuminated CONTINUOUSLY.

    Repair: The GSC+ has been programmed to override the normal shutdown response and the GSC+ treats the condition as an alarm fault. The engine will continue to run. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2-0". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5-0".

    Stop.

  • NO - The yellow fault alarm indicator is not illuminated at all. Proceed to Test Step 3.

Test Step 3. CHECK FOR RED FAULT SHUTDOWN INDICATOR.

  1. Check the display area of the GSC+ for the red fault shutdown indicator.

Expected Result:

The red fault shutdown indicator should be FLASHING.

Results:

  • YES - The red fault shutdown indicator is FLASHING and the engine remains running. Proceed to Test Step 4.

  • NO - All fault indicators are OFF. A problem that is occurring should cause the GSC+ to shut down the engine. It is possible to program the GSC+ setpoints to a value that does not allow the situation to be recognized by the GSC+ as a shutdown condition.

    Repair: Check the appropriate setpoints for correct values. In order to view the setpoints, see Systems Operation, "Engine/Generator Setpoint Viewing OP2-0". In order to reprogram the setpoints, see Systems Operation, "Engine/Generator Programming OP5-0".

    Stop.

Test Step 4. CHECK THE SYSTEM BY USING THE ESPB.

The engine remains running and the fault shutdown indicator is FLASHING.

  1. Push the emergency stop push button (ESPB).

Expected Result:

The engine should shut down.

Results:

  • OK - The engine does shutdown. The relay module is faulty.

    Repair: Replace the GSC+ relay module. See Testing and Adjusting, "Relay Module - Replace". Verify that the repair corrects the problem.

    Stop.

  • NOT OK - The engine does NOT shut down. Proceed to Test Step 5.

Test Step 5. CHECK GSC+ SETPOINT P001 (FUEL SOLENOID TYPE)

The engine remains running after pushing the ESPB and the red fault shutdown indicator is flashing.

  1. Check setpoint P001 (Fuel Solenoid Type). In order to view the setpoints, see Systems Operation, "Engine/Generator Setpoint Viewing OP2-0".

Expected Result:

Setpoint P001 should be programmed to "0".

Results:

  • YES - Setpoint P001 is programmed to "0". Proceed to Test Step 6.

  • NO - Setpoint P001 is programmed to "1". The setpoint is programmed incorrectly.

    Repair: Reprogram the setpoint to a value of "0". In order to reprogram the setpoint, see Systems Operation, "Engine/Generator Programming OP5-0".

    Stop.

Test Step 6. CHECK VOLTAGE AT THE FUEL CONTROL SOLENOID

The engine remains running after pushing the ESPB and the red fault shutdown indicator is FLASHING.

  1. At the fuel control solenoid (FCS), measure the voltage.

Expected Result:

The voltage measured at the fuel control solenoid should be approximately the same as the nominal battery voltage (+/- 2 volts).

Results:

  • OK - The battery voltage is correct at the FCS. The FCS has failed or there is a problem with the engine fuel system.

    Repair: Refer to the appropriate engine service manual. Replace the FCS or repair the fuel system.

    Stop.

  • NOT OK - Battery voltage is not correct at the FCS. The Emergency Fuel Control Relay (EFCR) has failed.

    Repair: Replace the Emergency Fuel Control Relay (EFCR). Verify that the repair corrects the problem.

    Stop.

Caterpillar Information System:

2001/05/01 Corrections to Specifications Module, SENR3863-01, "G3406 Engine" {1102}
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Programmable Logic Controller
Electronic Modular Control Panel II+ (EMCP II+) Engine Does Not Shutdown (for EUI Engines)
3412C Engine Spacer Plate - Remove and Install
3412C Engine Fuel Injection Pump - Remove
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Configuration
Electronic Modular Control Panel II+ (EMCP II+) Starting Motor Remains Engaged (for MUI Engines)
C-10 and C-12 Industrial Engines Fuel Transfer Pump
Electronic Modular Control Panel II+ (EMCP II+) Fault Identification
Electronic Modular Control Panel II+ (EMCP II+) Service Tools
G3600 Engines Control Panel
Electronic Modular Control Panel II+ (EMCP II+) General Information
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Setpoints
Electronic Modular Control Panel II+ (EMCP II+) GSC Operation Is Erratic
Electronic Modular Control Panel II+ (EMCP II+) Indicators of Alarm Module or Remote Annunciator Are Constantly Flashing
Electronic Modular Control Panel II+ (EMCP II+) Troubleshooting Diagnostic Codes
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0100 - FMI 02 (for EUI Engines)
3412C Engine Automatic Timing Advance - Remove
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0100 - FMI 02 (for MUI and PEEC Engines)
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0100 - FMI 03
3412C Engine Automatic Timing Advance - Install
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0100 - FMI 04
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0110 - FMI 02 (for EUI Engines)
Electronic Modular Control Panel II+ (EMCP II+) GSC CID 0110 - FMI 02 (for MUI and PEEC Engines)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.