Electronic Modular Control Panel II+ (EMCP II+) Caterpillar


Fault Identification

Usage:

3412C 9EP

Table 1
Fault Identification    
Indicator
left side of GSC+    
Fault Code on upper display     DIAG Indicator     Fault Type     See Topic    
Fault Alarm     CID FMI (1)     Flashing     Active Alarm     Troubleshooting Diagnostic Codes    
SP1, SP2, SP3, SP4 (1) Absent     Active Alarm     Diagnostic System Procedures, "SP Fault Code"    
AL1 thru AL15 (1) Absent     Active Alarm     Diagnostic System Procedures, "AL Fault Code"    
Fault Shutdown     CID FMI     Flashing     Active Shutdown     Troubleshooting Diagnostic Codes    
SP1, SP2, SP3, SP4 Absent     Active Shutdown     Diagnostic System Procedures, "SP Fault Code"    
AL5 thru AL15 (1) Absent     Active Alarm     Diagnostic System Procedures, "AL Fault Code"    
Dedicated Shutdown:        
Flashing     Absent     Absent     Active Alarm     Troubleshooting Dedicated Shutdown Indicators    
On Continuously     Absent     Absent     Active Shutdown    
None     CID FMI (2)     On Continuously     Inactive Alarm     Troubleshooting Diagnostic Codes    
CID FMI (2) On Continuously     Inactive Shutdown     Troubleshooting Diagnostic Codes    
SP1, SP2, SP3, SP4 Absent     Inactive Shutdown     Diagnostic System Procedures, "SP Fault Code"    
AL5 through AL15 (1) Absent     Inactive Alarm     Diagnostic System Procedures, "AL Fault Code"    
Absent Absent     Undiagnosed Shutdown     Symptom Procedures    
( 1 ) Fault code is shown after alarm codes key is pressed.
( 2 ) Fault Code is stored in the fault log of the GSC+. To view the fault code, see Systems Operation, "Fault Log Viewing OP1" within the topic Service Mode.



Illustration 1g00614724

GSC+ Display Area

(1) Dedicated shutdown indicators

(2) Spare fault indicators

(3) Fault shutdown indicator

(4) Fault alarm indicator

(5) Upper display

(6) Lower display

(7) Keypad

(8) DIAG indicator

Faults that are detected and diagnosed by the GSC+ are shown to service personnel in the display area of the GSC+. The GSC+ uses dedicated shutdown indicators (1), fault shutdown indicator (3), fault alarm indicator (4), "DIAG" indicator (8), upper display (5) and lower display (6) to tell service personnel about a fault. Perform the following procedure in order to identify the fault that is detected by the GSC+.

Note: The "DIAG" indicator (8) functions when diagnostic information is available from the GSC+.

  1. Make a note of the indicators that are functioning on the left side of the "GSC+".

  1. View the fault code on the upper display (5). If the fault alarm indicator (4) is FLASHING and no fault code is present on the upper display (5), press the alarm codes key in order to view the fault code.

  1. Make a note of whether or not "DIAG" indicator (8) is FLASHING ON CONTINUOUSLY or ABSENT.

  1. On the fault identification chart, look at the first column. Locate the fault indicator that is functioning.

  1. Go to the second column in the chart. Find the fault code that is presently shown on the upper display (5) .

  1. Go to the third column in the chart which describes the status of "DIAG" indicator (8) .

  1. Read the last two columns in order to find the type of fault and corresponding topic within this module.

Caterpillar Information System:

Electronic Modular Control Panel II+ (EMCP II+) Service Tools
G3600 Engines Control Panel
Electronic Modular Control Panel II+ (EMCP II+) General Information
C-9 Industrial Engine E100 Low Engine Oil Pressure Warning
C-9 Industrial Engine E040 Low Engine Oil Pressure Shutdown
C-9 Industrial Engine E039 Low Engine Oil Pressure Derate
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Shutdown Mode
Electronic Modular Control Panel II+ (EMCP II+) SP Fault Codes
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Alarm Mode
G3516B Engines E042 Low System Voltage Shutdown
3034 Marine Engine Cooling System Coolant (ELC) - Change
Electronic Modular Control Panel II+ (EMCP II+) AL Fault Codes
C-10 and C-12 Industrial Engines Fuel Transfer Pump
Electronic Modular Control Panel II+ (EMCP II+) Starting Motor Remains Engaged (for MUI Engines)
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Configuration
3412C Engine Fuel Injection Pump - Remove
3412C Engine Spacer Plate - Remove and Install
Electronic Modular Control Panel II+ (EMCP II+) Engine Does Not Shutdown (for EUI Engines)
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Programmable Logic Controller
2001/05/01 Corrections to Specifications Module, SENR3863-01, "G3406 Engine" {1102}
Electronic Modular Control Panel II+ (EMCP II+) Engine Does Not Shutdown (for MUI Engines)
3606, 3608, 3612 and 3616 Engines and C280-12, C280-16, C280-6 and C280-8 Marine Engines Control Panel Setpoints
Electronic Modular Control Panel II+ (EMCP II+) GSC Operation Is Erratic
Electronic Modular Control Panel II+ (EMCP II+) Indicators of Alarm Module or Remote Annunciator Are Constantly Flashing
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.