Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Caterpillar


Relay Driver Module

Usage:

3516B 1NW



Illustration 1g00327305

(1) Relay driver module

(2) Relay board (optional)

The relay driver module (RDM) is an optional module that can be used to expand the number of available outputs on the GSC+. The RDM outputs are controlled by the customer communication module (CCM). The RDM provides nine additional outputs for the customer. The RDM outputs are individually controlled by a serial data link from the GSC+. The outputs may drive the optional relay board, or the outputs can be directly connected to horns, lamps, or other devices. The relay board contains nine relays. Each of the relays have one set of Normally Opened contacts and one set of Normally Closed contacts that are used for customers.

Output Test

If an output test signal is received by the RDM, then the RDM activates all outputs for ten seconds. The outputs remain active until the output test signal is deactivated. To perform an output test, connect terminal 5 of the RDM to terminal 7 of the RDM with a jumper.

When the data link malfunctions, R1 output (terminal 2 of RDM) will FLASH at a rate of 0.5 Hz. Relays R2 through R9 will maintain the present state or relays R2 through R9 will default to the OFF position.

Specifications

  • The maximum distance between the RDM and the GSC+ is 305 m (1000 ft).

  • The operating voltage range is from 15 to 45 DCV. The RDM is designed to operate when the RDM is powered by 24 DCV or when the RDM is powered by 32 DCV.

  • The RDM is capable of operating with an earth ground or without an earth ground.

  • The RDM must share a common ground with the GSC+ and the relay board.

  • The terminals that are on the RDM are push on blade type connectors (6.4 mm (.25 inch)).

  • The terminals on the relay board are 6-32 screw terminals.

  • The driver outputs of the RDM are intended to power incandescent lamps. Also, the driver outputs of the RDM are intended to power relay loads. The driver outputs sink up to 600 mA at 15 DCV to 45 DCV. The driver outputs are protected against short circuits to "B+".

  • The relay outputs of the relay board are protected by 1 amp fuses. The contacts are flashed with silver. The contact is rated as 1 Amp at 28 DCV. The relay coils draw 20 mA at 24 DCV.

Note: The GSC+ diagnoses a fault in the Relay Driver Module circuit. See Testing and Adjusting, "CID 475 Relay Driver Module" for more information. The CID 475 procedure contains schematics for relay driver module installation purposes.

Caterpillar Information System:

Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Alarm Module Control (Custom)
SR4 HV and SR4B HV Generators Generator Terminal Connections
EMCPII+ for Gas Engines Alarm Module Control (NFPA 110)
3612 and 3616 Engines Water Pump - Remove - Jacket Water Pump
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Alarm Modules
3618 Engine Crankcase Explosion Relief Valve - Remove and Install
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Programmable Kilowatt Level Output
C9 On-Highway Truck Engines Unit Injector Hydraulic Pump - Install
Caterpillar Monitoring System for Electronic Modular Control Panel Modes Of Operation
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Programmable Spare Output
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Programmable Spare Relay Outputs
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Diagnostic Codes
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Synchronizing Lights Module
SR4 HV and SR4B HV Generators Parallel Operation
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Customer Interface Module
3612 and 3616 Engines Water Pump - Install - Jacket Water Pump
EMCPII+ for Gas Engines System Communication Module (Customer)
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines General Information
EMCPII+ for Gas Engines Component Location
EMCPII+ for Gas Engines Data Link
Caterpillar Monitoring System for Electronic Modular Control Panel Normal Mode
3126B Truck Engine Idler Pulley - Remove
3126B Truck Engine Idler Pulley - Install
3606 and 3608 Engines Engine Oil Coolers - Remove
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.