Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Caterpillar


Alarm Modules

Usage:

3516B 1NW



Illustration 1g00321237

Alarm Module

(1) Amber indicators. (2) Red indicators. (3) Lamp test switch. (4) Alarm silence switch. (5) Horn.

The alarm module (ALM) is an attachment. The ALM is located on the instrument panel. Red indicators (2) and amber indicators (1) are the visual indicators. The horn (5) is the audible indicator. The ALM is designed to be powered by only a 24 DCV battery system or a 32 DCV battery system.

There are six versions of the basic module. The modules are either alarm modules or a remote annunciator. The term "remote annunciator" is used but the annunciator is the same basic alarm module. The versions are listed below.

  • NFPA 99 Standby alarm module.

  • NFPA 99 Remote annunciator which is used with a standby NFPA 99 Alarm module.

  • NFPA 110 Standby alarm module which is used with NFPA 110 Remote annunciator panel. See Systems Operation, "Alarm Module Control (NFPA 110)".

  • Prime power single engine alarm module .

  • Prime power multiple engine alarm module.

  • EMCP II+ remote annunciator.

The only difference between these modules is in the graphics film on the front of the panel and the jumper wires on the rear. See the Testing And Adjusting, "DC Schematic". The NFPA 99 remote annunciator and the remote annunciator for the EMCP II have a lamp test switch.

The alarm module (ALM) gives a warning of conditions that are becoming a problem. The warning occurs before conditions are severe enough to shut down the engine.

If an alarm fault develops with the ECS in the COOLDOWN/STOP or AUTO positions, then the fault is indicated by the optional alarm module and/or the remote annunciator.

Description of Change

Note: In the following description, the word "annunciator" may mean "alarm module" or "remote annunciator module".

The annunciator module receives data from switch inputs, internal circuitry, and a serial data link from the GSC.

Switch Inputs

Four inputs are available as connections for the switch inputs. Switch inputs are activated when the inputs are connected to the "B-". See Table 1.

Internal Circuitry

Internal circuitry is used in order to determine if the DC battery supply voltage is too low. The setpoint is set at the factory at 24 DCV.

Data Link

The annunciator module receives data from the generator set control (GSC) by a serial data link. The items that are included in this data stream of information are listed below.

  1. Coolant temperature has exceeded the high temperature alarm setpoint that is programmed into the GSC.

  1. Oil pressure is below the low oil pressure alarm setpoint that is programmed into the GSC.

  1. Coolant temperature is below the setpoint for the low temperature alarm that is programmed into the GSC.

  1. The engine control switch (ECS) is not in the MAN/START position or the AUTO position.

  1. Oil pressure is below the setpoint for the low oil pressure shutdown that is programmed into the GSC.

  1. Coolant temperature has exceeded the setpoint for the high water temperature shutdown that is programmed into the GSC.

  1. The engine has failed to start.

  1. The engine speed exceeded the setpoint for the engine overspeed that is programmed into the GSC.

  1. The engine is shut down due to a coolant loss fault.

  1. The engine shut down due to a spare fault.

  1. The engine shut down due to an emergency stop fault.

  1. The engine shut down due to a diagnostic fault.

The first eight items control the operation of the indicators and horn. See Table 1 for more information. The last four items control the operation of the horn only.

A maximum of three modules are connected to the serial data link: alarm, CIM and RDM. The maximum distance between a module and the GSC is 305 m (1000 ft).

The data link will malfunction under the following conditions with multiple modules:

  • One of the modules is powered down.

  • The module that is powered down remains connected to the data link.

If the two conditions that are above are present, the indicators that are controlled by the data link of the other modules will flash at 0.5 Hz.

Indicator And Horn Operation

Table 1
Indicator And Horn Function    
Indicator
Color    
NFPA 99 ALM     NFPA 100
ALM    
NFPA 99 RAN     Prime Power
Single Engine    
Prime Power
Multi Engine    
EMCP RAN    
1 Amber     High Coolant
Temp Alarm
LI, H, LAT, TD    
High Coolant
Temp Alarm
LI, H, LAT, TD    
Gen On Load
SW(3)    
High Coolant Temp Alarm
LI, H, LAT, TD    
High Coolant Temp Alarm
LI, H, LAT, TD    
High Coolant Temp Alarm
LI, H, LAT, TD    
2 Amber     Low Coolant Temp Alarm
LI, H, LAT    
Low Coolant Temp Alarm
LI, H, LAT    
Low Coolant Temp Alarm
LI, H, LAT    
Low Coolant Level Alarm
SW(2), H    
Low Coolant Level Alarm
SW(2), H    
Low Coolant Temp Alarm
LI, H, LAT    
3 Amber     Low Oil Press Alarm
LI, H, LAT    
Low Oil Press Alarm
LI, H, LAT    
Charger Malfunction
SW(4), TIM    
Low Oil Press Alarm
LI, H, LAT    
Low Oil Press Alarm
LI, H, LAT    
Low Oil Press Alarm
LI, H, LAT    
4 Amber     Low Fuel Level
SW(1), H    
Low Fuel Level
SW(1), H    
Low Fuel Level
SW(1), H    
Low Oil Level
SW(1), H    
Low Oil Level
SW(1), H    
Not In Auto
LI, H    
5 Red     Not In Auto
LI, H    
Not In Auto
LI, H    
High Coolant Temp Shutdown (1)
LI, H, TD    
Low DCV
INT, TIM    
Not In Auto
LI, H    
High Coolant Temp Shutdown (1)
LI, H, TD    
6 Red     Low DCV
INT, TIM    
Low DCV
INT, TIM    
Low Oil Press Shutdown (1)
LI, H    
Spare
SW(3)    
Low DCV
INT, TIM    
Low DCV
INT, TIM    
7 Red     Spare
SW(3)    
Charger Malfunction
SW(4), TIM    
Overcrank Shutdown (1)
LI, H    
Not Used     Spare
SW(3)    
Overcrank Shutdown (1)
LI, H    
8 Red     Spare
SW(4)    
Air Damper Closed (2)     Overspeed Shutdown (1)
LI, H    
Not Used     Spare
SW(4)    
Overspeed Shutdown (1)
LI, H    
( 1 ) Latched by the GSC
( 2 ) Air Damper Switch to be supplied by customer.

Table 2
ALM = Alarm Module    
H = Horn is sounded    
INT = The signal source is internal to the module    
LAT = LATCHED alarm fault    
LI = The data link from the GSC is the signal source    
RAN = Remote Annunciator    
SW = One of 4 switches is the signal source (the number in parentheses indicates which switch is the signal source    
TD = A 10 second delay occurs before the fault is annunciated    
TIM = A 60 second delay occurs before the fault is annunciated    

When an alarm fault occurs, the corresponding indicator flashes. The indicator flashes at two hertz and the horn sounds. If the alarm fault is NOT LATCHED, the indicator turns off when the alarm fault ceases. The horn also turns off when the alarm fault ceases. If the alarm fault is LATCHED, the indicator continues to flash until the "acknowledge/silence" input is activated. See Table 1 for LATCHED alarm faults as well as the indicator and horn functions for each operating mode.

Normally switch input 3 (terminal 10) and switch input 4 (terminal 11) only operate indicators 7 and 8. However, switch inputs 3 and 4 can be made to also operate the horn. Connect terminal 10 ("sw input 3") to terminal 3 and connect terminal 11 ("sw input 4") to terminal 4.

Alarm Silence

Activating the alarm silence switch (4) causes the horn to cease and the indicator to stay on continuously.

Data Link Malfunction

If the data link malfunctions, the indicators that are controlled by the data link flash at 0.5 hertz. The switch controlled indicators function normally.

Lamp Test

Activating the lamp test switch (3) results in sounding the horn and turning on all indicators continuously for 10 seconds or until the switch is deactivated.

Mode Selection

Table 3
Mode Selection And Switch Input Connections (1)    
Input     Mode
SEL1    
Mode SEL2     Switch 1     Switch 2     Switch 3     Switch 4    
Terminal     5     6     8     9     10     11    
Mode                            
NFPA 99 Alarm     (Float)     (Float)     Low Fuel Level     (Float)     Spare     Spare    
NFPA 110 Alarm     (Float)     (B-)     Low Fuel Level     (Float)     Air Damper
Closed    
Charger
Malfunction    
NFPA 99
Remote
Annunciator    
(B-)     (Float)     Low Fuel Level     (Float)     Gen On Load     Charger
Malfunction    
Prime Power
Single Engine    
(Float)     (Float)     Low Oil Level     (B-)     (Spare)     Low Coolant
Level    
Prime Power
Multi Engine    
(B-)     (B-)     Low Oil Level     Low Coolant
Level    
(Spare)     (Spare)    
EMCP RAN     (Float)     (B-)     (Float)     (B-)     (Float)     (Float)    
( 1 ) NOTE: Connections in parentheses are required to select the mode specified

The annunciator module operates in one of the six modes described in Table 3. The modes are selected by connections made to the mode select inputs (terminals 5 and 6) and switch 2 input (terminal 9) as shown in Table 3.

Caterpillar Information System:

3618 Engine Crankcase Explosion Relief Valve - Remove and Install
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Programmable Kilowatt Level Output
C9 On-Highway Truck Engines Unit Injector Hydraulic Pump - Install
Caterpillar Monitoring System for Electronic Modular Control Panel Modes Of Operation
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Programmable Spare Output
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Programmable Spare Relay Outputs
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Diagnostic Codes
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines SP Fault Codes
3612 and 3616 Engines Engine Oil Pump - Assemble
3500B High Displacement Locomotive Engines Electronic Control Module (ECM)
3500 Spark Ignited Engines Gas Pressure Regulator
3612 and 3616 Engines Engine Oil Pump - Disassemble
3612 and 3616 Engines Water Pump - Remove - Jacket Water Pump
EMCPII+ for Gas Engines Alarm Module Control (NFPA 110)
SR4 HV and SR4B HV Generators Generator Terminal Connections
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Alarm Module Control (Custom)
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Relay Driver Module
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Synchronizing Lights Module
SR4 HV and SR4B HV Generators Parallel Operation
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines Customer Interface Module
3612 and 3616 Engines Water Pump - Install - Jacket Water Pump
EMCPII+ for Gas Engines System Communication Module (Customer)
Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines General Information
EMCPII+ for Gas Engines Component Location
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.