G3306B Generator Sets Caterpillar


Generator Lead Connections

Usage:

XQG135 AL4

Lead Numbering

The Wye (Star) configurations and the Delta configurations are the most common generator lead connections. The following three-phase connection diagrams illustrate the proper connection and lead identification.

The leads are numbered clockwise from the top and from the outside inward. The diagrams show lead numbering for the six and twelve lead generators.

Wye Configuration Diagrams

6 Lead




Illustration 1g00611486

6 Lead Wye Configuration

Terminals T4, T5, and T6 become neutral connection when the terminals are tied together.

12 Lead




Illustration 2g00661863

12 Lead Wye Configuration - High Voltage

Terminals T10, T11, and T12 become neutral connection when the terminals are tied together.




Illustration 3g00611608

12 Lead Wye Configuration - Low Voltage

Terminals T10, T11, and T12 become neutral connection when the terminals are tied together.

Delta Configuration Diagrams

6 Lead




Illustration 4g00669319

6 Lead Delta Configuration

12 Lead




Illustration 5g00669312

12 Lead Delta Configuration

Terminals T6 and T9 become the neutral connection when the terminals are tied together and grounded. This position reflects the terminal T2 and T10 connection as the high phase.

Grounding the Frame

In any generator set installation, the frame of the generator is positively connected to an earth ground. This connection is the first one that is made at the installation. This connection is the last one that should be removed. The ground connection must be flexible in order to avoid possible breakage in later operation.

Ground connection cable or straps should have at least the current carrying capacity of the largest line lead to the connected load. Joints in cables or straps must be clean, free of electrical resistance, and protected from possible oxidation. Bolted ground connection joints eventually oxidize. The joints are frequent sources of radio frequency interference (RFI). Silver soldered and bolted joints are electrically and mechanically sound.

Neutral Connections

The generators with grounded configuration usually have the neutral grounded when the generator is installed. However, there are some cases when definite measures can be taken in order to prevent ground faults on the load side. The purpose of the grounding of the neutral is to prevent load side equipment damage. The purpose of the grounding of the neutral is also to prevent harm to personnel.

If the neutral wire and one of the phase leads becomes grounded, the excessive current will open a load circuit breaker to isolate the fault. The excessive current will collapse the generator voltage, if the circuit breaker does not trip first. The result depends on the particular generator electrical characteristics, type of fault and trip rating of the circuit breaker. An undervoltage device may be required in order to provide an adequate short circuit protection.

There are some instances in which grounding the neutral wire is undesirable. An ungrounded generator neutral lead is acceptable in applications in which definite measures have been taken to prevent grounds to the phase leads. Examples of such measures are ground fault protective circuits. Ground fault protection requires that the entire group of distribution circuits should be studied and treated as a system. The owner should engage a certified and registered consultant if a new distribution system is being developed. The owner should also engage a certified and registered consultant if an existing system should be modified for the ground fault protection.

Neutral resistors and reactors may be added to the system for two reasons: to provide protection during faults and to limit neutral currents.

Single Units

In a three-phase, four-wire system, the neutral wire should be grounded according to local wiring codes.

In applications, in which definite measures are taken in order to prevent grounds to the load leads, an ungrounded neutral can be used. Be sure to check your local wiring codes.

Multiple Units

Operation of multiple generators in parallel, having all neutrals grounded, may result in the circulating current through the neutral connections. In order to eliminate the possibility of circulating currents, ground the neutral of only one generator. If multiple generators are alternated on line, a switch should be installed in the neutral ground circuit of each generator. In this case all neutral ground circuits except one can be opened. Be sure that one of the neutral ground circuits is closed.

Parallel to Utility

When a Wye (Star) connected generator operates in parallel with a utility system (infinite bus) with the secondary of the step-down transformer also a Wye connection, the following may happen. The grounding of both Wye neutrals may result in circulating currents through the neutrals. Also, the coordination of ground fault protection requires an entire system study. A study should be done by a certified and registered consultant who is familiar with generator systems. The study will determine which grounding method should be used.

Caterpillar Information System:

G3306B Generator Sets Declaration of Conformity
G3306B Generator Sets Product Description
G3306B Generator Sets Model View Illustrations
XQC1600 Power Module Fuel System Primary Filter/Water Separator - Drain
390F Excavator Fan Guard - Remove and Install - Rear
390F Excavator C18 Engine Supplement Engine - Remove and Install
C175-16 Petroleum Generator Set Engines Control Panel
390F Excavator C18 Engine Supplement Engine Rear Mount - Remove and Install
C4.4 Engines for Caterpillar Built Machines Crankshaft Rear Seal - Install
C4.4 Engines for Caterpillar Built Machines Crankshaft Rear Seal - Remove
C27 and C32 Engines for Caterpillar Built Machines Vibration Damper and Pulley - Remove and Install
C27 and C32 Engines for Caterpillar Built Machines Water Temperature Regulator Housing - Remove and Install
390F Excavator Machine Systems Travel Parking Brake
G3306B Generator Sets Product Storage
390F Excavator Fan Guard - Remove and Install
Using the 453-3204 Pressure and Temperature Test Group{0374, 0599, 0706, 0708, 0709, 0731, 0732, 0738, 1408, 1439} Using the 453-3204 Pressure and Temperature Test Group{0374, 0599, 0706, 0708, 0709, 0731, 0732, 0738, 1408, 1439}
C4.4 Marine Generator Set Fuel System Primary Filter (Water Separator) Element - Replace
C4.4 Marine Generator Set Fuel System Primary Filter/Water Separator - Drain
XQC1600 Power Module Engine Crankcase Breather - Clean
C13, C15, and C18 Tier 4 Final Engines Oil Temperature Is High
C4.4 Marine Generator Set Fuel System Secondary Filter - Replace
390F Excavator Fan - Remove and Install
C3.3B and C3.8 Engines for Caterpillar Built Machines Intake Manifold Air Temperature Is High
C4.4 Marine Generator Set Switch (Coolant Level) - Remove and Install - Coolant Level Switch for Sea water Cooled Engines
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.