UPS 250, UPS 300, UPS 301, UPS 500, UPS 600, UPS 750 and UPS 900 Uninterruptible Power Supplies Caterpillar


System Shutdown

Usage:

UPS 250 CNM

Shutting Down the Single Module System (SMS)

  • Single Module System (SMS) with a Bypass Cabinet

  • SMS without a Bypass Cabinet

Pre-Shutdown




    Illustration 1g00863047

  1. Connect a personal computer (PC) to the "RS-232/RS-485" port. The port is located on the bottom back corner of the system's System Input/Output Board. Refer to Illustration 1. The System Input/Output Board is located in the System Cabinet.

    Note: Refer to Systems Operation, Testing and Adjusting, RENR2476, "Component Location (System Cabinet)" for the location of the board.

  1. Rotate the switch to the corresponding MMU.

  1. Boot the PC.

  1. Run the UPS View software by double clicking over the icon on your PC.

  1. Click on the "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.



    Illustration 2g00697157

  1. Enter a valid "User Name" and then enter a valid "Password". Refer to Illustration 7.

    After the password has been entered, the menu options will change. The menu bar will contain a "Calibrate" option.

  1. Depress the <Ctrl><X> keys and hold the <Ctrl><X> keys. This is done in order to bring the system to 0 RPM.

  1. The system will prompt you to confirm the option. Depress the <Y> key or select "Yes".

    Note: This procedure is only available once during a 24 hour period.

    Note: A minimum of 15 minutes is required in order to lower the speed of the flywheel to 0 RPM.

    Note: A minimum of 15 minutes is required in order to secure the rotor.

SMS with a Bypass Cabinet

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Single Module System (SMS)" section before proceeding with this procedure.



    Illustration 3g01796613

    User Interface Panel on the Flywheel Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the Flywheel Cabinet to the "Bypass" position. Refer to Illustration 5.

  1. Remove the key from the keyswitch (1). Secure the key.

  1. Verify that the system enters the bypass mode. The "On Bypass" LED on the user interface panel will light when the system enters the bypass mode. Refer to Illustration 5.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.



    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 4g01797996

    Side view of the Bypass Cabinet

    (10) Bypass Switch

    (11) Output Switch

    (12) Input Switch

  1. Close the Bypass Switch (10) that is located in the Bypass Cabinet. Refer to Illustration 4.

  1. Open the Output Switch (11) that is located in the Bypass Cabinet. Refer to Illustration 4.

  1. Open the Input Switch (12) that is located in the Bypass Cabinet. Refer to Illustration 4.

  1. Remove facility power from the input bus of the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

SMS without a Bypass Cabinet

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Single Module System (SMS)" section before proceeding with this procedure.



    Illustration 5g01796613

    User Interface Panel on the Flywheel Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the Flywheel Cabinet to the "Bypass" position. Refer to Illustration 5.

  1. Remove the key from the keyswitch (1). Secure the key.

  1. Verify that the system enters the bypass mode. The "On Bypass" LED on the user interface panel will light when the system enters the bypass mode. Refer to Illustration 5.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.



    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.


  1. Remove the electrical input to the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Remove facility power from the input bus of the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Shutting Down the Multiple Module System (MMS)

  • Single Input without Switches

  • Single Input with Three Switches

  • Dual Input without Switches

  • Dual Input with Two Switches

  • Dual Input with Three Switches

Pre-Shutdown




    Illustration 6g00863047

  1. Connect a personal computer (PC) to the "RS-232/RS-485" port on the Parallel Cabinet Interface Board. The port is located on the bottom back corner of the system's Parallel Cabinet Interface Board. Refer to Illustration 6. The Parallel Cabinet Interface Board is located in the System Cabinet.

    Note: Refer to Systems Operation, Testing and Adjusting, RENR2476, "Component Location (System Cabinet)" for the location of the board.

  1. Rotate the switch to the corresponding MMU.

  1. Boot the PC.

  1. Run the UPS View software by double clicking over the icon on your PC.

  1. Click on the "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.



    Illustration 7g00697157

  1. Enter a valid "User Name" and then enter a valid "Password". Refer to Illustration 7.

    After the password has been entered, the menu options will change. The menu bar will contain a "Calibrate" option.

  1. Depress the <Ctrl><X> keys and hold the <Ctrl><X> keys. This is done in order to bring the system to 0 RPM.

  1. The system will prompt you to confirm the option. Depress the <Y> key or select "Yes".

    Note: This procedure is only available once during a 24 hour period.

    Note: A minimum of 15 minutes is required in order to lower the speed of the flywheel to 0 RPM.

    Note: A minimum of 15 minutes is required in order to secure the rotor.

  1. Repeat this procedure for each MMU.

Single Input without Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 8g01798275

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 8.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 9g00948144

  1. Hit the "Home" button on the user interface panel of each MMU. Verify that the MMU is in the "Bypassed" mode. Refer to Illustration 9.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 10g01796613

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 10.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.


  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.



    Illustration 11g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 11.

  1. Open the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 11.

  1. Disconnect the utility from the input bus of the system.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Single Input with Three Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 12g01796613

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 12.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.



    Illustration 13g01798275

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 13.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 14g00948144

  1. Hit the "Home" button on the user interface panel of each MMU. Verify that the MMU is in the "Bypassed" mode. Refer to Illustration 19.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 15g01797234

    (3) Maintenance Bypass Switch

    (8) Key

  1. Insert the key (8) into the Maintenance Bypass Switch (3) in the Input/Output Cabinet. Refer to Illustration 15.

    Note: Although the keys are similar in appearance, the key (8) for the Maintenance Bypass Switch (3) is different from the key for the user interface panel.

  1. Turn the key (8) for the Maintenance Bypass Switch counterclockwise.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 16g01802293

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

    (5) Input Isolation Switch

  1. Close the Maintenance Bypass Switch (3) that is located in the Input/Output Cabinet. Refer to Illustration 16.



    Illustration 17g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 17.

  1. Open the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 16.

  1. Open the Input Isolation Switch (5) that is located in the Input/Output Cabinet. Refer to Illustration 16.

  1. Install safety locks by using the tabs for lockout on the front of the switches in the Input/Output Cabinet.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Dual Input without Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 18g01798275

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 18.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 19g00948144

  1. Hit the "Home" button on the user interface panel of each MMU. Verify that the MMU is in the "Bypassed" mode. Refer to Illustration 19.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 20g01796613

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the Bypass position. Refer to Illustration 20.

  1. Remove the key from the keyswitch (1). Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.


  1. Close the external maintenance bypass switch.



    Illustration 21g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 21.

  1. Open the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 21.

  1. Disconnect the utility from the input bus of the system.

  1. Disconnect the electrical path from the output of the system in order to protect the system for electrical backfeed prevention.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Dual Input with Two Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 22g01798275

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 22.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 23g00948144

  1. Hit the "Home" button on the user interface panel of each MMU. Verify that the MMU is in the "Bypassed" mode. Refer to Illustration 23.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 24g01796613

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 24.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 25g01797234

    (3) Maintenance Bypass Switch

    (8) Key

  1. Insert the key (8) into the Maintenance Bypass Switch (3) in the Input/Output Cabinet. Refer to Illustration 25.

    Note: Although the keys are similar in appearance, the key (8) for the Maintenance Bypass Switch (3) is different from the key for the user interface panel.

  1. Turn the key (8) for the Maintenance Bypass Switch counterclockwise.



    Illustration 26g01798373

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

  1. Close the Maintenance Bypass Switch (3) that is located in the Input/Output Cabinet. Refer to Illustration 26.



    Illustration 27g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 27.

  1. Open the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 26.

  1. Install safety locks by using the tabs for lockout on the front of the switches in the Input/Output Cabinet.

  1. Open the Input Isolation Switches (6) that are located in the System Cabinet for each MMU. Refer to Illustration 27.

  1. Disconnect the utility from the input bus of the system.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Dual Input with Three Switches

  1. Perform the "Pre-Shutdown" procedure in the "Shutting Down a Multiple Module System (MMS)" section before proceeding with this procedure.



    Illustration 28g01798275

    User Interface Panel on the MMU

    (2) Keyswitch

  1. Turn the keyswitch (2) on each MMU to the "Bypass" position. Refer to Illustration 28.

  1. Remove the key from the keyswitch (2) on each MMU. Secure the keys.



    Illustration 29g00948144

  1. Hit the "Home" button on the user interface panel of each MMU. Verify that the MMU is in the "Bypassed" mode. Refer to Illustration 29.


    NOTICE

    Do not proceed with this procedure if the system does not enter the bypass mode. Equipment damage and load interruption may occur. Contact your local Caterpillar Dealership.





    Illustration 30g01796613

    User Interface Panel on the System Cabinet

    (1) Keyswitch

  1. Turn the keyswitch (1) on the System Cabinet to the "Bypass" position. Refer to Illustration 30.

  1. Remove the key from the keyswitch (1) on the System Cabinet. Secure the key.


    NOTICE

    Make sure that the electrical path to the load of the facility is not affected when you perform the following steps. Do not allow the load of the facility to be dropped.





    Illustration 31g01797234

    (3) Maintenance Bypass Switch

    (8) Key

  1. Insert the key (8) into the Maintenance Bypass Switch (3) in the Input/Output Cabinet. Refer to Illustration 31.

    Note: Although the keys are similar in appearance, the key (8) for the Maintenance Bypass Switch (3) is different from the key for the user interface panel.

  1. Turn the key (8) for the Maintenance Bypass Switch counterclockwise.



    Illustration 32g01798373

    Input/Output Cabinet

    (3) Maintenance Bypass Switch

    (4) Output Isolation Switch

    (5) Input Isolation Switch

  1. Close the Maintenance Bypass Switch (3) that is located in the Input/Output Cabinet. Refer to Illustration 32.

  1. Open the Output Isolation Switch (4) that is located in the Input/Output Cabinet. Refer to Illustration 32.



    Illustration 33g01779897

    System Cabinet

    The switches go from MMU 1 to MMU 4 in a descending order.

    (6) Input Isolation Switches

    (7) Output Isolation Switches

  1. Open the Output Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 33.

  1. Open the Input Isolation Switches (7) that are located in the System Cabinet for each MMU. Refer to Illustration 33.

  1. Open the Input Isolation Switch (5) that is located in the Input/Output Cabinet. Refer to Illustration 32.

  1. Install safety locks by using the tabs for lockout on the front of the switches in the Input/Output Cabinet.

  1. Remove utility power from the input bus for the system.

  1. Allow the capacitor banks to bleed down for approximately 5 minutes in order to dissipate any residual energy that may exist in the following components: the bus, the armature leads and the fuses.

Caterpillar Information System:

C18 Fire Pump Engine Zinc Rods - Inspect/Replace
C18 Fire Pump Engine Heat Exchanger - Inspect
2009/01/26 Adjustment of the Circuit Breaker Is Required During Setup of Generator Set {1420}
C18 Fire Pump Engine Diagnostic Flash Code Retrieval
TH48-E70-C27I, TH48-E70-C32I and TH48-E70-C32P Petroleum Power Train packages and TH48-E70 Petroleum Transmission Power Train Electronic Control System Transmission Fill - Calibrate
XQ175 Rental Generator Set Safety Messages
374F Excavator Machine System Track Adjuster
G3500B Engines Exhaust Temperature - Test
2009/01/05 Rocker Assembly Seals {1100, 1107, 1123}
2009/01/05 An Updated Torque Procedure Is Used for the Shutoff Valve Assembly on Certain Engines {1329, 1380, 1395}
C18 Fire Pump Engine Engine Speed/Timing Sensor - Clean/Inspect
G3508B, G3512B, G3512B, G3516B and G3520B Petroleum Engines Flywheel Housing - Remove
2009/01/05 New Rain Caps Are Used on Some Generator Sets {1061, 1062, 1072}
G3508B, G3512B, G3512B, G3516B and G3520B Petroleum Engines Flywheel Housing - Install
3600 and C280 Diesel Engine Fluids Recommendations Biodiesel
2009/01/26 Final Drive Duo-Cone Seal Assembly Information Update {7561}
797F and 797F XQ Off-Highway Truck/Tractor Braking System Brake Hydraulic System
797F and 797F XQ Off-Highway Truck/Tractor Braking System Electronic Control Module (Brake)
G3500B Engines Air/Fuel Ratio Problem
G3516 Petroleum Engines Valve Cover and Spark Plug - Remove and Install
2009/01/12 Adding Heat Shrink To The Harness Reduces Warnings {1273, 1408}
Wiring Improvements For The Contactor On The Control Group For Jacket Water Heaters, Space Heaters, And Some Battery Chargers On The 3412C, The 3406C, The 3456C, The C9, The C15, And The C18 Generator Sets{1435} Wiring Improvements For The Contactor On The Control Group For Jacket Water Heaters, Space Heaters, And Some Battery Chargers On The 3412C, The 3406C, The 3456C, The C9, The C15, And The C18 Generator Sets{1435}
G3508B, G3512B, G3512B, G3516B and G3520B Petroleum Engines Rocker Shaft and Push Rod - Install
G3508J, G3516J, and G3520J Engines Nitrogen Oxide Sensor - Remove and Install
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.