Illustration 1 | g00844346 |
ALARM INDICATOR - This indicator shows when an alarm condition is present. The Alarm Mode on the display will detail the exact nature of the alarm. When the indicator is not illuminated, no alarm is active. A shutdown alarm is present when the indicator is flashing. The shutdown alarm has not been silenced. When the indicator is steady, a warning alarm is present or a shutdown alarm that has been silenced is present.
Illustration 2 | g00845660 |
PROGRAMMABLE INDICATORS - The programmable indicators can be configured by the user in order to indicate any one of over 100 different functionalities. Indicators can be configured to indicate any of the following functions: indications, warnings and shutdowns and status indications.. Indications consist of the monitoring of a digital input and indicating the associated functioning user's equipment. The display would show "BATTERY CHARGER ON", for example. Warnings and shutdowns are specific indications of particular warning or shutdown conditions. For example, the display would show "LOW OIL PRESSURE SHUTDOWN". Status indications indicate specific functions or sequences that are derived from the operating state of the module. For example, the display would show "SAFETY ON".