Generator Set Start Module Caterpillar


Electrical Connections

Usage:

UPS 250 APZ

Electrical Connections

The Generator Set Start Module should be installed per the National Electrical Code (NEC) and other applicable codes. The size of the cable and the size of the conduit should be based on Start Module specifications. Class 1 wiring methods should be used.




Illustration 1g00822212

Generator Set Start Module - Right Side View

(1) 24 DCV Output/Control Power/Ground - Bottom Entry or Side Entry Options

(2) ACV Input - Bottom Entry Option or Side Entry Option

(A) 310 mm (12.20 inch)

In order to allow for cables to enter into the Start Module, holes must be drilled in the bottom of the lower access panel or holes must be drilled in the side of the lower access panel (1, 2). Refer to Illustration 1. The location of the holes will depend on whether the floor mounting option is employed or the wall mounting option is employed. The input cables and the output cables must be routed in separate conduits.

Generator Set Start Module Control Power (UPS 250 Model Only)




Illustration 2g00822251

Generator Set Start Module Terminal Block

(3) Output - To Generator Set +24 DCV

(4) Output - To Generator Set -24 DCV

(5) Input - From Generator Set +24 DCV

(6) Input - From Generator Set -24 DCV

------ WARNING! ------

The inside compartments of the Generator Set Starting Module can contain the risk of electric shock or hazardous energy levels. Personal inuury can result from Electric Shock. Do not touch live electric parts.

----------------------

The Generator Set Start Module's Control Power Signals come from the connected generator and from the UPS. During starting attempts, either the battery for the generator set or the Caterpillar UPS will provide power for the Generator Set Control Circuits.

Note: Used on UPS 250 models only.

Use the following information to assemble the wires:

  • Wire size must be between #10 AWG and #14 AWG.

  • In order to connect the wire to the terminals, attach ring lugs (# 8 AWG) to the wire.

  • Maximum length of the wire is 15.24 m (50.00 ft).

Generator Set Start Module 24 DCV Output Cable




Illustration 3g00822262

24 DCV Output Power Cable connection location

(7) AC Connector

(B) 610 mm (24.00 inch)

(C) 914 mm (36.00 inch)

(D) 24 DCV terminal locations (3/8 inch hardware)

------ WARNING! ------

The inside compartments of the Generator Set Starting Module can contain the risk of electric shock or hazardous energy levels. Personal inuury can result from Electric Shock. Do not touch live electric parts.

----------------------

Use the "+" terminal and the "-" terminal (D) in order to connect the 24 DCV output power cable to the generator. The "+" terminal and the "-" terminal (D) are located in the lower access compartment of the Generator Set Start Module. Refer to Illustration 3.

Configure the cable as follows:

  • 3/0 cable minimum

  • 3/8 inch lug hardware

  • maximum cable length from the generator set is 7.62 m (25.00 ft)

  • torque the wiring at these terminals to 63.72 N·m (47 lb ft)

  • nonferrous type conduit in order to avoid heating

UPS to Generator Set Start Module Cable




Illustration 4g00822493

Generator Set Start Module AC Input Connector

(8) Cable shielding

(9) Terminal lugs (#6 AWG wire) for 1/4 inch studs

(10) AC input connector

(11) "A" phase

(12) Ground

(13) "B" phase

(14) "C" phase

The cable that is used to connect to the UPS must comply with the following parameters. This cable is not included.

  • Maximum length of the cable is 152.4 m (500 ft).

  • Cable must be run in conduit.

  • Cable must comply with all local ordinances.

Connect one end of the Generator Set Start Module AC cable to the Start Module's AC Input Connector (7) .

Note: Penetration of the cabinet wall requires a female threaded fitting on the end of the conduit in order to accommodate strain relief.

The remaining end of the Generator Set Start Module AC cable is connected to the AC output terminal blocks which are located inside the UPS. Depending on the UPS model, the UPS AC Output Terminals can be found in one of two locations. Refer to Illustration 5 and Illustration 6.

In order to connect the Generator Set Start Module AC cable to the AC output terminal blocks, perform the following steps:

  1. Strip a sufficient amount of cable shielding from the cable so that terminal lugs can be attached.

  1. Attach terminal lugs to the cable. Terminal lugs should be sized for 1/4 inch studs.

  1. Attach the cable to the Caterpillar UPS AC Output Terminals.

UPS 250 AC Out Terminal Location

On the UPS 250 (the 50 Hz and 60 Hz units), the AC output terminals are located on the AC capacitor bank panel. The ground connection is located on the Generator Set Start Module Inductor Panel.




Illustration 5g00822978

UPS 300 AC Output terminal location.

UPS 300 Series AC Output Terminal Location

On the following models, the AC Output terminals and the ground terminal are located on the Generator Set Start Module Inductor Panel:

  • UPS 250 (50 Hz unit)

  • UPS 300 (60 Hz unit)

  • UPS 500 (50 Hz unit)

  • UPS 600 (60 Hz unit)

  • UPS 750 (50 Hz unit)

  • UPS 900 (60 Hz unit)




Illustration 6g00822965

UPS 250 Series AC Out terminal location

Grounding

The grounding wire should meet the following parameters:

  • # 6 AWG wire

  • a lug which will accommodate a 1/4 inch stud

  • maximum length of 15.24 m (50 ft)

If the 24 DCV output cable is shorter than the Generator Set Start Module's AC cable, run a ground wire from the generator set to the ground stud. The ground stud is located in the lower access compartment. Disconnect and insulate the AC ground from the upper cabinet.

If the 24 DCV output cable is longer than the Generator Set Start Module's AC cable, no modification is necessary. Do not run a ground wire from the generator set.

Disconnecting the Generator Set Start Module

------ WARNING! ------

The inside compartments of the Generator Set Starting Module can contain the risk of electric shock or hazardous energy levels. Personal inuury can result from Electric Shock. Do not touch live electric parts.

----------------------

In order to disconnect the Generator Set Start Module from the UPS power source, unplug the Generator Set Start Module's AC cable connector. The Generator Set Start Module's AC cable connector (7) is located inside the Lower Access Compartment. Refer to Illustration 3. Ensure that the start module is not attempting to start the engine.

Caterpillar Information System:

3054 and 3056 Marine Generator Sets Engine Crankcase Breather - Clean/Replace
SPS343 Skid Mounted Pumper Product Lifting
3500B and 3500 Marine Propulsion Engines with EUI Option Engine Operation
3408E and 3412E Industrial Engines Analog Sensor Supply Circuit - Test
3408E and 3412E Industrial Engines System Overview
Generator Set Start Module Mounting
C-15 and C-16 Industrial Engines Maintenance Interval Schedule - C-16
G3406 Engine Valve Lash and Valve Bridge Adjustment
SBF214 and SUF557 Skid Mounted Power Packs Product Lifting
Determining the Correct Part Numbers for Main Bearings and Cylinder Head Gaskets{1124, 1201, 1203} Determining the Correct Part Numbers for Main Bearings and Cylinder Head Gaskets{1124, 1201, 1203}
Generator Set Start Module Model View Illustrations
Generator Set Start Module Site Preparation
3500B and 3500 Marine Propulsion Engines with EUI Option Engine Rating Definitions
3126 Truck Engine Fuel Filter Lines
SPS343 Skid Mounted Pumper Cooling System Coolant Level - Check
G3406 Engine Crankshaft Position for Valve Lash Setting
2007/01/29 Coolant Recommendation for 3618 Engines {1350, 1352, 1395}
C0.5, C0.7, C1.1/3011C, C1.5/3013C, C1.6 and C2.2/3024C/3024CT Industrial Engines and Engines for Caterpillar Built Machines Flywheel - Inspect
C0.5, C0.7, C1.1/3011C, C1.5/3013C, C1.6 and C2.2/3024C/3024CT Industrial Engines and Engines for Caterpillar Built Machines Gear Group - Inspect
3054 and 3056 Marine Generator Sets Cooling System Coolant (DEAC) - Change
3512B and 3512C Engines For Caterpillar Built Machines Hydraulic Starting System
3054 and 3056 Marine Generator Sets Cooling System Coolant (ELC) - Change
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 144-1811 Generator through 144-1951 Generator
SR4 and SR4B Electric Power Generation Rewind Data Winding Data for 147-9437 Generator through 147-9497 Generator
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.