Clearance for the Door
Illustration 1 | g00821917 |
Generator Set Start Module door-clearance requirements |
The Generator Set Start Module can be anchored to the floor or the Generator Set Start Module can be mounted on a wall. When the generator set Start module is being installed, ensure that a radius of 519 mm (20.43 inch) is maintained for door swing. Refer to Illustration 1.
Floor Mounting
Illustration 2 | g00821922 |
Generator Set Start Module floor mount clearance requirements (A) 51 mm (2.00 inch) (B) 236 mm (9.29 inch) (C) Provisions for 5/16 inch mounting hardware (floor mount option) (D) 229 mm (9.02 inch) (E) 160 mm (6.30 inch) (F) 25 mm (0.98 inch) (G) 25 mm (0.98 inch) (H) 457 mm (17.99 inch) (I) 507 mm (19.96 inch) (J) 1067 mm (42.00 inch) (K) 903 mm (35.55 inch) |
Inspect the installation location. Ensure that the floor meets the load requirements of the Generator Set Start Module. Ensure that there is sufficient space between the Generator Set Start Module and any obstructions. Refer to Illustration 2.
Wall Mounting
Illustration 3 | g00822188 |
Generator Set Start Module wall mounting dimensions (A) 64 mm (2.52 inch) (B) 381 mm (15.00 inch) (C) 556 mm (21.89 inch) (D) Mounting holes (Qty 4) - provisions for 5/16 inch mounting hardware (E) 332 mm (13.07 inch) |
Inspect the installation location. Ensure that the wall meets the load requirements of the Generator Set Start Module. Ensure that sufficient clearance for the door is maintained.
The Generator Set Start Module has four mounting holes (D). These mounting holes are located on the back panel. These holes will accommodate 5/16 inch mounting hardware. Refer to Illustration 3.