Electronic Modular Control Panel II (EMCP II) Caterpillar


Engine Does Not Shutdown (for PEEC Engines)

Usage:

3412C 4BZ
System Operation Description:

The engine does not shut down when a shutdown fault occurs.

There are several possible causes why an engine is not shutting down when a shutdown fault occurs:




Illustration 1g00519201

System Schematic For Unexpected Shutdown

Note: It is extremely important that GSC setpoint P23 is correct for the engine application. Make certain setpoint P23 is programmed correctly for the engine application before continuing with this procedure.

Note: It is extremely important that GSC setpoint P01 is correct for the engine. All generator sets packaged in Larne, Ireland with serial numbers (your list of S/N's) must ALWAYS have this setpoint programmed to 0 (ETR fuel solenoid) for both fuel solenoid types (ETR or ETS).

There are several possible causes why an engine is not shutting down when a shutdown fault occurs.

  • Operator Error: The operating conditions of the generator may not be understood by the operator. Ensure that the condition is one that should cause an engine shutdown.

  • Programming Error - Fault Is Overridden Or Disabled: It is possible to program the GSC in order to override certain shutdown faults. An overridden shutdown fault will be treated as an alarm fault. The YELLOW fault alarm indicator will be FLASHING instead of the RED fault shutdown indicator. If the GSC is programmed in order to disable a particular fault, there will not be any fault indicators or codes shown on the GSC. In these cases, it is a good idea to check any setpoints related to that fault. For example, if a genset is not shutting down when an overvoltage fault occurs, make sure setpoint P104(Overvoltage shutdown enable) is programmed correctly.

  • Programming Error - Setpoints Incorrect For Application Or Customer Needs: It is possible to program the GSC setpoints to a value that does not allow the situation to be recognized by the GSC as a shutdown condition. In this case, check the appropriate setpoints for correct values. For example, if the genset is not shutting down when a high coolant temperature condition occurs, make sure setpoint P15 (High Water Temperature Shutdown) is correct for the application.

  • Faulty Component: Some examples of faulty components that could prevent the GSC from shutting down the engine are: PEEC, GSC and a broken or shorted harness wire.. In this case, the GSC or PEEC will be issuing a command to shut down the engine due to a diagnostic code, but the engine remains running.

Test Step 1. CHECK FOR DIAGNOSTIC CODES

  1. Check the GSC for a diagnostic code on the upper display.

Expected Result:

The GSC should show a diagnostic code on the upper display.

Results:

  • YES - The GSC shows a diagnostic code on the upper display.

    Repair: See theTesting and Adjusting section of this book for the diagnostic code that is displayed on the GSC.

    Stop.

  • NO - The GSC does NOT show a diagnostic code on the upper display. Proceed to Test Step 2.

Test Step 2. CHECK THE YELLOW FAULT ALARM INDICATOR

  1. Check the display area of the GSC for the yellow fault alarm indicator.

Expected Result:

The fault alarm indicator should be illuminated CONTINUOUSLY.

Results:

  • YES - The fault alarm indicator is illuminated CONTINUOUSLY.

    Repair: The GSC has been programmed to override the normal shutdown response and the GSC treats the condition as an alarm fault. The engine will continue to run. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2-0". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5-0".

    Stop.

  • NO - The yellow fault alarm indicator is not illuminated at all. Proceed to Test Step 3.

Test Step 3. CHECK FOR RED FAULT SHUTDOWN INDICATOR.

  1. Check the display area of the GSC for a red fault shutdown indicator.

Expected Result:

The red fault shutdown indicator should be FLASHING.

Results:

  • YES - The red fault shutdown indicator is FLASHING and the engine remains running. Proceed to Test Step 4.

  • NO - All fault indicators are OFF. A problem that is occurring should cause the GSC to shut down the engine. It is possible to program the GSC setpoints to a value that does not allow the situation to be recognized by the GSC as a shutdown condition.

    Repair: Check the appropriate setpoints for correct values. In order to view the setpoints, see System Operation, "Engine/Generator Setpoint Viewing OP2-0". In order to reprogram the setpoints, see System Operation, "Engine/Generator Programming OP5-0"

    Stop.

Test Step 4. CHECK THE SYSTEM BY USING THE ESPB.

The engine remains running and the red fault shutdown indicator is FLASHING.

  1. Push the emergency stop push button (ESPB).

Expected Result:

The engine should shut down.

Results:

  • OK - The engine does shutdown.

    Repair: Replace the PEEC or the ESDR. Verify that the repair corrects the problem.

    Stop.

  • NOT OK - The engine does NOT shut down. There is an engine problem.

    Repair: Check the fuel shutoff solenoid (FSOS) and the engine fuel system. Refer to the appropriate engine service manuals.

    Stop.

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) AC Offset Adjustment OP10
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for MUI 3412C, 3508,3512, 3516 Engines)
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for MUI 3306B, 3406C Engines)
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for EUI Engines)
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for MUI 3412C, 3508, 3512, 3516 Engines)
G3304 and G3306 Engines General Information (Cooling System)
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for EUI and PEEC Engines)
G3304 and G3306 Engines General Information (Lubrication System)
Electronic Modular Control Panel II (EMCP II) System Communication Module (Customer)
Electronic Modular Control Panel II (EMCP II) Relay Driver Module
G3406 Engine Measuring Engine Oil Pressure
G3304 and G3306 Engines Engine Oil Pressure is Low
Electronic Modular Control Panel II (EMCP II) GSC Operation Is Erratic
Electronic Modular Control Panel II (EMCP II) Display of Voltage or Current Is Zero
Electronic Modular Control Panel II (EMCP II) Normal Mode
Electronic Modular Control Panel II (EMCP II) Fault Log Clearing OP4
G3406 Engine Air Inlet and Exhaust System Components
G3406 Engine Finding the Top Center Position for the No. 1 Piston
Electronic Modular Control Panel II (EMCP II) SP Fault Codes
Electronic Modular Control Panel II (EMCP II) Indicators of Alarm Module or Remote Annunciator Are Constantly Flashing
Electronic Modular Control Panel II (EMCP II) Alarm Module Control (Custom)
Electronic Modular Control Panel II (EMCP II) GSC CID 0100 - FMI 02 (for EUI Engines)
Electronic Modular Control Panel II (EMCP II) GSC CID 0100 - FMI 02 (for MUI and PEEC Engines)
Electronic Modular Control Panel II (EMCP II) GSC CID 0100 - FMI 03
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.