Electronic Modular Control Panel II (EMCP II) Caterpillar


AC Offset Adjustment OP10

Usage:

3412C 4BZ
OP10 is the option for adjusting the voltmeter readings of the GSC. This adjustment may be necessary when generator sets are operated in parallel. The GSC AC voltage measurements are calibrated at the factory. An accurate standard is used. However, when two generator sets are paralleled, the application may require the paralleled generator sets to have exactly the same voltage value. The AC offset of one GSC is changed to match the voltage value of another generator set.

Note: It is NOT recommended that the AC offset be altered under any other circumstances. Performing this procedure takes the GSC out of factory calibration.

Note: The adjusted voltages are used for the display only. The adjusted voltages will not be sent over the CATData Link to other modules. The customer communication module is another module that may receive information over the CATData Link.

Procedure For Voltmeter Offset Adjustment

The paralleled generator sets must be running at rated speed. The generator sets can then have the voltage adjustment made.

Note: Service mode cannot be entered when the ECS is in the AUTO position.

  1. Enter service mode on the GSC that is being adjusted. Enter the password. "OP 1" is showing on lower display. For more information, see the Service Manual, "Service Mode". For more information, see the Service Manual, "Password Entry OP3".

  1. Press "SCROLL UP" key nine times. "OP 10" is showing on the lower display.

  1. Press "SELECT" key. "AC CAL" is showing on lower display. The present A-B voltage value is showing on the upper display.

  1. Press "SELECT" key. The voltage value is flashing.

  1. Press the "SCROLL UP" key or press the "SCROLL DOWN" key in order to adjust the voltage. Adjust the value to exactly match the other generator set(s) that are running in parallel. Voltage value continues to flash.

  1. Press "ENTER" key. The value of the setpoint stops flashing.

  1. Press "SCROLL UP" key. Repeat steps 3, 4, 5 and 6 for the B-C voltage and the C-A voltage.

  1. Press "EXIT" key. "OP 1" is showing on the lower display.

  1. Press "EXIT" key. The display returns to the normal state.

Caterpillar Information System:

Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for MUI 3412C, 3508,3512, 3516 Engines)
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for MUI 3306B, 3406C Engines)
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for EUI Engines)
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for MUI 3412C, 3508, 3512, 3516 Engines)
G3304 and G3306 Engines General Information (Cooling System)
Electronic Modular Control Panel II (EMCP II) Starting Motor Remains Engaged (for EUI and PEEC Engines)
G3304 and G3306 Engines General Information (Lubrication System)
Electronic Modular Control Panel II (EMCP II) System Communication Module (Customer)
Electronic Modular Control Panel II (EMCP II) Relay Driver Module
G3406 Engine Measuring Engine Oil Pressure
G3304 and G3306 Engines Engine Oil Pressure is Low
G3304 and G3306 Engines Engine Oil Pressure is High
Electronic Modular Control Panel II (EMCP II) Engine Does Not Shutdown (for PEEC Engines)
Electronic Modular Control Panel II (EMCP II) GSC Operation Is Erratic
Electronic Modular Control Panel II (EMCP II) Display of Voltage or Current Is Zero
Electronic Modular Control Panel II (EMCP II) Normal Mode
Electronic Modular Control Panel II (EMCP II) Fault Log Clearing OP4
G3406 Engine Air Inlet and Exhaust System Components
G3406 Engine Finding the Top Center Position for the No. 1 Piston
Electronic Modular Control Panel II (EMCP II) SP Fault Codes
Electronic Modular Control Panel II (EMCP II) Indicators of Alarm Module or Remote Annunciator Are Constantly Flashing
Electronic Modular Control Panel II (EMCP II) Alarm Module Control (Custom)
Electronic Modular Control Panel II (EMCP II) GSC CID 0100 - FMI 02 (for EUI Engines)
Electronic Modular Control Panel II (EMCP II) GSC CID 0100 - FMI 02 (for MUI and PEEC Engines)
Back to top
The names Caterpillar, John Deere, JD, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
CH-Part.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only.